CAST IRON STOVE AND BURNER SYSTEM

105499

SDVBN(A) AND SDVBP(A)

Figure 39 - Gas Connection

* The A.G.A. design-certified manual shutoff valve may be supplied with the appliance or
you can purchase it from your dealer.

 CAUTION: Use only new,

black iron or steel pipe. Inter-
nally-tinned copper tubing may
be used in certain areas. Check
your local codes. Use pipe of 1/2"
diameter or greater to allow
proper gas volume to burner sys-
tem. If pipe is too small, undue
loss of pressure will occur.

Installation must include a manual shutoff
valve, union, and plugged 1/8" NPT tap.
Locate NPT tap within reach for test gauge
hook up. NPT tap must be upstream from
burner system (see Figure 39).

IMPORTANT:

 Install main gas valve

(manual shutoff valve) in an accessible lo-
cation. The main gas valve is for turning on
and shutting off the gas to the appliance.

Check your building codes for any special
requirements for locating manual shutoff
valve to stoves.

For propane/LP connections only, the in-
staller must supply an external regulator.
The external regulator will reduce incoming
gas pressure. You must reduce incoming
gas pressure to between 11 and 14 inches of
water. If you do not reduce incoming gas
pressure, burner system regulator damage
could occur. Install external regulator with
the vent pointing down as shown in Figure
38. Pointing the vent down protects it from
freezing rain or sleet.

STOVE AND
DIRECT-VENT
BURNER SYSTEM
INSTALLATION

INSTALLING GAS PIPING TO
STOVE/BURNER SYSTEM
LOCATION

Installation Items Needed

Before installing stove and burner system,
make sure you have the items listed below.

• external regulator (supplied by installer)

• piping (check local codes)

• sealant (resistant to propane/LP gas)

• manual shutoff valve *

• test gauge connection *

• sediment trap

• tee joint

• pipe wrench

• approved flexible gas line with gas con-

nector (if allowed by local codes) (not
provided)

*  An A.G.A. design-certified manual shutoff
valve with 1/8" NPT tap is an acceptable
alternative to test gauge connection. Pur-
chase the A.G.A. design-certified manual
shutoff valve from your dealer.

 WARNING: A qualified ser-

vice person must connect burner
system to gas supply. Follow all
local codes.

 CAUTION: For propane/LP

units, never connect burner sys-
tem directly to the propane/LP
supply. This burner system re-
quires an external regulator (not
supplied). Install the external regu-
lator between the burner system
and propane/LP supply.

  CAUTION: Use pipe joint seal-

ant that is resistant to liquid pe-
troleum (LP) gas.

Figure 38 - External Regulator with Vent
Pointing Down (Propane/LP Only)

Propane/LP
Supply Tank

External
Regulator

Vent
Pointing
Down

We recommend that you install a sediment
trap/drip leg in supply line as shown in
Figure 39. Locate sediment trap/drip leg
where it is within reach for cleaning. Install
in piping system between fuel supply and
burner system. Locate sediment trap/drip
leg where trapped matter is not likely to
freeze. A sediment trap traps moisture and
contaminants. This keeps them from going
into burner system gas controls. If sediment
trap/drip leg is not installed or is installed
wrong, burner system may not run properly.

A.G.A. Design-Certified Manual
Shutoff Valve with 1/8" NPT Tap*

3" Minimum

Propane/LP - From
External Regulator
(11" W.C. to 14"
W.C. Pressure)

Approved Flexible
Gas Line

Cap    Pipe Nipple    Tee Joint

Sediment Trap/Drip Leg

Natural - From Gas
Meter (5" W.C. to 10.5"
W.C. Pressure )

CHECK GAS TYPE

Use proper gas type for the burner system
unit you are installing. If you have conflict-
ing gas types, do not install burner system.
See dealer where you purchased the stove
and burner system for proper burner system
according to your gas type.

Apply pipe joint sealant lightly to male
threads. This will prevent excess sealant
from going into pipe. Excess sealant in pipe
could result in clogged burner system valves.

Summary of Contents for SDVBN

Page 1: ...consult a qualified installer ser vice agency or the gas supplier WARNING If the information in this manual is not followedexactly afireorexplosionmayresultcaus ing property damage personal injury or...

Page 2: ...installedbyaquali fied service person The glass door must be properly seated and sealed If this unit is not properly installed by a qualified service person with glass door properly seated and sealed...

Page 3: ...er system has a piezo ignitor This system requires no matches batteries or other sources to light burner system Figure1 VanguardDirect VentBurnerSystemShownInstalledinApprovedVanguard Cast Iron Stove...

Page 4: ...see Figure 3 and Figure 4 on page 5 4 This stove is a freestanding unit de signed to set directly on the floor If your stove is to be installed directly on carpeting vinyl tile or any combustible mate...

Page 5: ...t Wood From The Bottom of The Stove Figure 9 Locating Threaded Holes for StoveBottom Legs andDoorAttachment Figure 6 Removing Back Panel Bolt Product Identification Label Back Stove Panel Pallet Wood...

Page 6: ...law Make final adjustment and door leveling after stove is in nor mal standing position 13 Carefully lift stove back up on its four attached legs 14 Set top grate into stove top INSTALLING DIRECT VENT...

Page 7: ...n ob NOTICE If installing blower in an existingstoveburnersystemwith gas connections shut off gas supply and disconnect stove burner system from gas supply Contact a qualified service per son to do th...

Page 8: ...l over vent pipe connec tion on burner system Rear cover will rest on the bottom ledge of the stove body 2 Usingscrewsprovided attachrearcover to back of stove body See Figure 17 IMPORTANT This rear c...

Page 9: ...paved driveway located on public property 84 inches 2133mm minimum M clearance under veranda porch deck 12 inches 305mm minimum N clearance above a roof shall extend a minimum of 24 inches 610mm abov...

Page 10: ...Termination Vertical Termination It is important to select the proper length of vent pipe for the type of termination you choose It is also important to note the wall thickness For Horizontal Terminat...

Page 11: ...Rigid vent pipes and fittings have spe cial twist lock connections Assemble the desired combination of pipe and el bows to the appliance adaptor with pipe seams oriented towards the wall or floor Twi...

Page 12: ...up Insure proper clearance of 1 to combustibles is maintained At tach the vent cap with four wood screws supplied see Figure 23 Note Re place the wood screws with appropri ate fasteners for stucco br...

Page 13: ...e 14 show different configurations for venting with horizontal termination Each figure includes a chart with vertical mini mum maximum and horizontal maximum dimensions which must be met Seal all conn...

Page 14: ...30 to avoid cutting loadbearing members Note Pay spe cial attention to these installation in structions for required clearances air space to combustibles when passing through ceilings walls roofs encl...

Page 15: ...outer pipe connection with high temperature sili cone sealant as specified in the second warning statement on page 10 Note If the vent pipe passes through any occupiedareasabovethefirstfloor includin...

Page 16: ...ith high temperature sili conesealantasspecifiedinthesecondwarn ing statement on page 10 Venting with Two 90 Elbows Vertical V Horizontal H1 Horizontal H2 5 min 2 max 6 min 4 max 7 min 6 max 8 min 8 m...

Page 17: ...Support RoofFlashing RTVSilicone Ver tical Termination and 26 screws D1000BK 7 x 12 Black Coaxial Pipe 1 pk D1010BK 7 x 24 Black Coaxial Pipe 1 pk D1020BK 7 x 48 Black Coaxial Pipe 1 pk D1030BK 7 Adj...

Page 18: ...s line with gas con nector if allowed by local codes not provided AnA G A design certifiedmanualshutoff valve with 1 8 NPT tap is an acceptable alternative to test gauge connection Pur chase the A G A...

Page 19: ...ed fittings for leaks CHECKING GAS CONNECTIONS WARNING Test all gas pip ing and connections for leaks after installing or servicing Cor rect all leaks at once WARNING Neveruseanopen flame to check for...

Page 20: ...off valve see Figure 41 2 Open propane LPsupply tank valve for propane LPburner system or main gas valve located on or near gas meter for natural gas burner system 3 Make sure control knob of burner s...

Page 21: ...erminal W and R Figure 44 Control Valve Terminals W R Terminal W Terminal R Continued To Control Switch or Optional Accessory 5 Gently remove the cover of the ther mostat from the base Grasp the sides...

Page 22: ...ery clip andconnecttoterminals seeFigure48 5 Place receiver into valve bracket and align holes see Figure 49 6 Use push in fasteners included with receiver to secure to bracket 7 Connect the wires fro...

Page 23: ...No 4 WARNING The glass door must be securely in place before running this burner system Do notrunthisburnersystemifglass is missing or broken NOTICE Do not put lava rock on burner or under burner Plac...

Page 24: ...n the gas control knob Never use tools If the knob will not push in or turn by hand don t try to repair it call a qualified service technician Force or attempted repair may result in a fire or explosi...

Page 25: ...or OFF buttons on the hand held remote control unit Inautomode theroomtemperature iscontrolledbythethermostatinthe hand held remote control unit To increase the room temperature press the top arrow o...

Page 26: ...rols are located on the left side of the switch bracket to the left just inside the door Both the GA3700 manual blower and the DA3610T thermostatically controlled blower have an ON setting and an OFF...

Page 27: ...edbythemanufacturershould be used when replacing broken ordamagedglassdoorpanel see ReplacementParts page31 This glass door panel is a complete unit No substitute materials may be used If glass has be...

Page 28: ...gged pilot 5 Thermocouple connection loose at con trol valve 6 Thermocouple damaged 7 Control valve damaged REMEDY 1 Reconnect ignitor cable 2 Free ignitor cable if pinched by any metal or tubing Keep...

Page 29: ...emoved from line Have gas line checked by local pro pane LP or natural gas company 3 Clean burner see Cleaning and Maintenance page 27 or replace burner orifice 1 Adjust the log set so that the flame...

Page 30: ...ontrol valve defective 1 Gas leak See Warning statement above 1 Improper log placement 2 Air holes at burner inlet blocked 3 Burner flame holes blocked OBSERVED PROBLEM Burner system produces unwanted...

Page 31: ...Wiringerrorscancause improper and dangerous opera tion Verify proper operation af ter servicing Note Use only original replacement parts Thiswillprotectyourwarrantycoveragefor parts replaced under wa...

Page 32: ...1 0 w c Thermal Efficiency 70 70 Dimension Inches mm HxWxD Stove and Burner System 27 x 26 1 4 x 26 1 8 27 x 26 1 4 x 26 1 8 685 8 x 666 7 x 663 4mm 685 8 x 666 7 x 663 4mm Carton Insert Only 23 1 4 x...

Page 33: ...tems THERMOSTATICALLY CONTROLLED BLOWER KIT DA3610T Provides better heat distribution Blower turns off and on automatically as needed Completeinstallationandoperationinstruc tions included in this man...

Page 34: ...D BURNER SYSTEM 105499 SDVBN A AND SDVBP A ILLUSTRATED PARTS BREAKDOWN SDVBN A SDVBP A LO H I P I L O T OFF ON 24 27 19 20 21 23 26 1 26 4 26 2 26 3 29 30 4 25 1 2 4 4 7 8 9 10 11 13 12 31 15 16 17 18...

Page 35: ...l 1 105523 02 Burner Propane LP 1 20 104506 01 Orifice Natural 1 104506 18 Orifice Propane LP 1 21 104507 01 Brass Elbow 1 22 104508 01 Brass Fitting 2 23 105493 01 Aluminum Tubing Assy 1 24 104510 01...

Page 36: ...IRON STOVE AND BURNER SYSTEM 105499 SDVBN A AND SDVBP A ILLUSTRATED PARTS BREAKDOWN AMITY SCIVF SERIES PSCIVF SERIES Indicates Color Suffix Designation 1 2 5 8 7 4 6 5 5 7 1 7 2 5 4 7 3 3 AMITY STOVE...

Page 37: ...eg Metallic Charcoal 4 Total Per Stove 1 104175 07 One Leg Porcelain Enamel Red 4 Total Per Stove 1 104175 08 One Leg Porcelain Enamel Teal Green 4 Total Per Stove 1 104175 09 One Leg Porcelain Enamel...

Page 38: ...ostsrelatedtorepairingadefectivestoveandburnersystemwillbetheresponsibilityoftheowner TOTHEFULLEXTENTALLOWEDBYTHELAWOFTHEJURISDICTIONTHATGOVERNSTHESALEOFTHEPRODUCT THIS EXPRESS WARRANTY EXCLUDES ANY A...

Reviews: