Vanguard Firewerks VFRMV18PA Owner'S Operation And Installation Manual Download Page 7

www.desatech.com

114745-01B

7

1.  Determine the volume of the space (length x 

width x height).

 

Length x Width x Height = ________ cu. ft. 

 

(volume of space)

 

Example: 

Space size 20 ft. (length) x 16 ft. 

(width) x 8 ft. (ceiling height) = 2560 cu. ft. 

(volume of space)

If additional ventilation to adjoining room is sup-

plied with grills or openings, add the volume of 

these rooms to the total volume of the space. 
2.  Multiply the space volume by 20 to determine 

the maximum Btu/Hr the space can support.

 

____________(volume  of  space)  x  20  = 

(Maximum Btu/Hr the space can support)

 

Example:

 2560 cu. ft. (volume of space) x 

20 = 51,200 (maximum Btu/Hr the space can 

support)

3.  Add the Btu/Hr of all fuel burning appliances 

in the space.

 

Vent-free appliance 

_________Btu/Hr

 

Gas water appliance* 

_________Btu/Hr

 

Gas furnace            

_________Btu/Hr

 

Vented gas appliance 

_________Btu/Hr

 

Gas fireplace logs     

_________Btu/Hr

 

Other gas appliances*  +_________Btu/Hr

 

Total 

=_________Btu/Hr

 

* Do not include direct-vent gas appliances. 

Direct-vent draws combustion air from the 

outdoors and vents to the outdoors.

 

Example: 

 

Gas water appliance 

_________Btu/Hr

 

Vent-free appliance  

+_________Btu/Hr

 

Total 

=_________Btu/Hr

4.  Compare the maximum Btu/Hr the space can 

support with the actual amount of Btu/Hr used.

 

 ___________ Btu/Hr (maximum the space 

 

 

can support) 

 

 ____________Btu/Hr (actual amount of 

 

 

Btu/Hr used)

 

Example: 

51,200  Btu/Hr  (maximum  the  

 

space can support) 

 

 

73,000 Btu/Hr (actual amount of  

 

 

Btu/Hr used)

AIR FOR COMBUSTION 

AND VENTILATION

Continued

The space in the previous example is a confined 

space because the actual Btu/Hr used is more than 

the maximum Btu/Hr the space can support. You 

must provide additional fresh air. Your options 

are as follows:
A.  Rework worksheet, adding the space of an 

adjoining room. If the extra space provides an 

unconfined space, remove door to adjoining 

room or add ventilation grills between rooms. 

See 

Ventilation Air From Inside Building

.

B.  Vent room directly to the outdoors. See 

Ven-

tilation Air From Outdoors, 

page 8.

C.  Install  a  lower  Btu/Hr  appliance,  if  lower 

Btu/Hr size makes room unconfined. 

 

If  the  actual  Btu/Hr  used  is  less  than  the 

maximum Btu/Hr the space can support, the 

space is an unconfined space. You will need 

no additional fresh air ventilation. 

 WARNING: If the area in which 

the appliance may be operated 

is smaller than that defined as 

an  unconfined  space  or  if  the 

building  is  of  unusually  tight 

construction, provide adequate 

combustion and ventilation air 

by one of the methods described 

in the 

National Fuel Gas Code, 

ANSI Z223.1/NFPA 54 Section 5.3

 

or applicable local codes. 

VENTILATION AIR

Ventilation Air From Inside Building 

This fresh air would come from an adjoining un-

confined space. When ventilating to an adjoining 

unconfined space, you must provide two perma-

nent openings: one within 12" of the ceiling and 

one within 12" of the floor on the wall connecting 

the two spaces (see options 1 and 2, Figure 2 on 

page 8). You can also remove door into adjoining 

room (see option 3, Figure 2). Follow the 

National 

Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 

5.3, Air for Combustion and Ventilation

 for re-

quired size of ventilation grills or ducts.

40,000
33,000
73,000

Summary of Contents for Firewerks VFRMV18PA

Page 1: ...ry to light any appliance Do not touch any electrical switch do not use any phone in your building Immediatelycallyourgassupplierfromaneighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a quali fied installer service agency or the gas supplier UNVENTED VENT FREE GAS LOG HEATER OWNER S OPE...

Page 2: ...oom in which it is installed Provi sions for adequate combustion and ventilation air must be provided Refer to Air for Combustion and Ventilation section on page 6 of this manual This appliance may be installed in an aftermarket per manently located manufactured mobile home where not prohibited by local codes This appliance is only for use with the type of gas indi cated on the rating plate This a...

Page 3: ...on of this log set WARNING Any change to this log set or its controls can be dangerous WARNING Donotuseablow erinsert heatexchangerinsertor otheraccessorynotapprovedfor use with this appliance WARNING This appliance is equipped with natural or pro pane LP gas Field conversion is not permitted WARNING Donotallow fans toblowdirectlyintothefireplace Avoidanydraftsthatalterburner flame patterns Ceiling ...

Page 4: ...ing and Maintenance page 20 SAFETY INFORMATION Continued 8 Before using furniture polish wax carpet cleaner or similar products turn heater off If heated the vapors from these products may create a white powder residue within the burner box or on adjacent walls and furniture 9 This heater needs fresh outside air ventilation to run properly this heater has an Oxygen De pletion Sensing ODS safety sh...

Page 5: ...here are four optional remote controls that can be purchased separately Wall switch Hand held ON OFF remote Wall thermostat Hand held thermostat remote See Accessories page 26 Thewallthermostatorhand heldthermostatmaynot be used where vented decorative listings is required PRODUCT FEATURES OPERATION This heater is clean burning It requires no outside venting There is no heat loss out a vent or up ...

Page 6: ...t provide additional fresh air Unusually tight construction is defined as construction where a Walls and ceilings exposed to the out side atmosphere have a continuous water vapor retarder with a rating of one perm 6 x 10 11 kg per pa sec m2 or less with openings gasketed or sealed and b weather stripping has been added on openable windows and doors and c caulking or sealants are applied to areas su...

Page 7: ...LATION Continued The space in the previous example is a confined space because the actual Btu Hr used is more than the maximum Btu Hr the space can support You must provide additional fresh air Your options are as follows A Rework worksheet adding the space of an adjoining room If the extra space provides an unconfined space remove door to adjoining room or add ventilation grills between rooms See V...

Page 8: ...ntilation Grills Into Adjoining Room Option 2 Ventilation Grills Into Adjoining Room Option 1 12 12 INSTALLATION NOTICE This heater is intended for use as supplemental heat Use this heater along with your primary heating system Do not installthisheaterasyourprimary heating source If you have a central heating system you may run system s circulating blower while using heater This will help circulat...

Page 9: ...P for your unit If your gas supply is not correct do not install in fireplace Call dealer where you bought the appliance for proper type of appliance INSTALLATION Continued WARNING This appliance is equipped for natural or pro pane LP gas Field conversion is not permitted INSTALLATION AND CLEARANCES FOR VENT FREE OPERATION WARNING Maintain the minimum clearances If you can provide greater clearance...

Page 10: ...terial A Figure 5 Heat Resistant Material Slate Marble Tile etc Above Fireplace Noncombustible Requirements for Material Distance A Safe Installation 12 or more N o n c o m b u s t i b l e material OK Between 8 and 12 24 Models Install fireplace hood accessory GA6050 GA6052 GA6053 see Accessories page 26 18 Model Noncom bustible material OK Less than 8 Noncombustible material must be extended to at...

Page 11: ...Minimum Non Combustible Material 8 Min 14 1 2 18 5 8 22 1 2 All minimum distances are in inches 26 2 1 2 6 8 10 12 Distances to Underside of Mantel Hood GA6050 GA6052 or GA6053 Top of Fireplace Opening Underside of Mantel Shelf NOTICE Surface temperatures ofadjacentwallsandmantelsbe comehotduringoperation Walls and mantels above the firebox may become hot to the touch If installed properly these te...

Page 12: ...lamp Damper Damper Clamp Damper Manufactured Fireplace Masonry Fireplace Damper Clamp Damper See chart below for minimum permanent flue opening you must provide Attach damper clamp so the minimum permanent flue opening will be maintained at all times Area of Various Standard Round Flues Diameter ins Area sq ins 5 20 sq inches 6 29 sq inches 7 39 sq inches 8 51 sq inches Chimney Minimum Permanent Hei...

Page 13: ...tems Needed Before installing heater make sure you have the items listed below external regulator supplied by installer piping check local codes sealant resistant to propane LP gas equipment shutoff valve test gauge connection sediment trap tee joint pipe wrench approved flexible gas line with gas connector if allowed by local codes provided ACSAdesign certified equipment shutoff valve with 1 8 NPT ...

Page 14: ...rom going into heater controls If sediment trap is not installed or is installed wrong heater may not run properly INSTALLATION Continued CAUTION Avoid damage to gas control Hold gas control with wrench when connecting it to gas piping and or fittings CHECKING GAS CONNECTIONS WARNING Testallgaspiping and connections for leaks after installing or servicing Correct all leaks at once WARNING Never use...

Page 15: ...gas or opening main gas valve located on or near gas meter for natural gas or using compressed air 3 Check all joints from gas meter to equipment shutoff valve for natural gas or propane LP supply to equipment shutoff valve for propane LP see Figure 15 or 16 Apply noncorrosive leak detection fluid to all joints Bubbles form ing show a leak 4 Correct all leaks at once INSTALLATION Continued Figure 1...

Page 16: ...spect the appliance and to replace any part of the control system and any gas control which has been under water LIGHTING INSTRUCTIONS WARNING If fireplace has glass doors never operate this heater with glass doors closed If you op erateheaterwithdoorsclosed heat buildup inside fireplace will cause glass to burst Also if fireplace opening has vents at the bottom you must open the vents before operati...

Page 17: ...ntact a qualified service person or gas supplier for repairs Note If pilot goes out repeat steps 4 through 8 page 16 OPERATING HEATER Continued Figure 17 Control Knob and Ignitor Button Location Manual Controlled Piezo Ignitor Switch in OFF Position Control Knob Flame Adjustment Knob 9 Slightly push in and turn control knob coun terclockwise to the ON position 10 Wait one minute and switch selector...

Page 18: ...Selector Switch in REMOTE Position Control Knob Flame Adjustment Knob ON OFF SERIES MODEL GHRCB Hold the control button on the hand held remote until burner turns on Hold the con trol button again until burner turns off see Figure 20 To Lock press both buttons on hand held remote control until light stops flashing Hand held remote control is now locked If the fire is on it will be turned off automat...

Page 19: ...ly receives signals from the hand held remote to control the room temperature If the hand held remote is misplaced obstructed or for any reason cannot transmit to the receiver the receiver will shut off the fireplace after 8 minutes OPERATING HEATER Continued Key Pad Lock Feature This feature allows the user to lock unlock the keypad on the hand held remote in the MANU or AUTO mode to prevent inadv...

Page 20: ...ep control areas burners and circulating air passageways of heater clean Inspect these areas of heater before each use Have heater inspected yearly by a qualified service person Heater may need more frequent cleaning due to excessive lint fromcarpeting pethair bedding material etc WARNING Failure to keep the primary air openings of the burner clean may result in soot ing and property damage BURNER ...

Page 21: ...r repeat steps 3 and 4 Clean the pilot assembly also A yellow tip on the pilot flame indicates dust and dirt in the pilot as sembly There is a small pilot air inlet hole about two inches from where the pilot flame comes out of the pilot assembly see Figure 27 With the unit off lightly blow air through the air inlet hole in the same direction as gas flow You may blow through a drinking straw if compre...

Page 22: ...e LP only 6 ODS pilot is clogged 7 Gas regulator setting is not correct REMEDY 1 Reconnect ignitor cable 2 Free ignitor cable if pinched by any metal or tubing Keep ignitor cable dry 3 Tighten nut holding piezo ig nitortobasepaneloflogset Nut is located behind base panel 4 Replace ignitor cable 5 Replace piezo ignitor 6 Replace pilot assembly for remote ready units Replace ignitor electrode for va...

Page 23: ... knob pressed in 30 seconds 3 Wait one minute for safety in terlock system to reset Repeat ignition operation 4 Fully open equipment shutoff valve 5 A Contact local natural or propane LP gas company B Clean ODS pilot see Cleaning and Maintenance page 20 or replace ODS pilot assembly 6 Hand tighten until snug then tighten 1 4 turn more 7 Replace pilot assembly 8 Replace control valve 1 Contact loca...

Page 24: ...ion and let warm up for a minute 2 Operate burners until air is removed from line Have gas line checked by local natural or propane LP gas company 3 Observe minimum instal lation clearances see pages 9 through 12 4 Clean burners see Cleaning and Maintenance page 20 or replace burner orifice s 1 Turn heater off when using furniture polish wax carpet cleaners or similar products 1 Refer to Air for Co...

Page 25: ...clogged 1 Gas leak See Warning statement at top of page 2 Control valve or gas control defective 1 Foreign matter between control valve and burner 2 Gas leak See Warning statement at top of page 1 Hand held remote control is too close to heater REMEDY 1 Open window to ventilate room Stop using odor caus ing products while heater is running 2 Refill supply tank propane LP only 3 Locateandcorrectalll...

Page 26: ...gas purchase date Usually we will ask you to return the part to the factory PARTS NOT UNDER WARRANTY Contact authorized dealers of this product If they canʼtsupplyoriginalreplacementpart s callDESA at 1 866 672 6040 for referral information When calling DESA have ready model and serial numbers of your heater the replacement part number SERVICE HINTS When Gas Pressure Is Too Low pilot will not stay...

Page 27: ... the gas log heater to be turned on and off by using a hand held remote control ACCESSORIES Continued FB36CA FB42C SERIES CIRCULATING FB36NCA FB42NC SERIES NON CIRCULATING Not Shown For all models DAMPER CLAMP GA6080 Not Shown For all models Permanently opens chimney flue damper for vented operation LAVA ROCK GA6060 Not Shown For all models Order when additional rock is desired 1 8 lb bag CLEANING ...

Page 28: ...www desatech com 114745 01B 28 ILLUSTRATED PARTS BREAKDOWN VFRMV18NA VFRMV18PA VFRMV24NA Shown VFRMV24PA 1 2 3 4 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 24 24 24 24 24 24 5 25 26 27 ...

Page 29: ... 114793 01 114793 01 114793 01 Piezo Switch Bracket 1 14 097159 04 097159 04 097159 04 097159 04 Piezo 1 15 14579 14579 14579 14579 Rocker Switch 1 16 111817 01 111817 01 111817 01 111817 01 Main Gas Line 1 17 114804 01 114804 01 114804 01 114804 01 ODS Pilot Line 1 18 103784 01 103784 01 103784 01 103784 01 ON PILOT OFF Knob Extension 1 19 103784 02 103784 02 103784 02 103784 02 HI LO Knob Extens...

Page 30: ...______________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ _______________________________________...

Page 31: ...______________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ _______________________________________...

Page 32: ...ter MUST be installed by a qualified installer in accordance with all local codes and instructions furnished with the unit This warranty does not apply to parts that are not in original condition because of normal wear and tear or parts that fail or become damaged as a result of misuse accidents lack of proper maintenance or defects caused by improper installation Travel diagnostic cost labor trans...

Reviews: