Vanguard FBST Owner'S Operation And Installation Manual Download Page 7

www.desatech.com

105116-01D

The space in the above example is a confined 

space because the actual Btu/Hr used is more than 

the maximum Btu/Hr the space can support. You 

must provide additional fresh air. Your options 

are as follows:

A.  Rework work sheet, adding the space of an 

adjoining room. If the extra space provides an 

unconfined space, remove door to adjoining 

room or add ventilation grills between rooms. 

See 

Ventilation Air from Inside Building

.

B.  Vent room directly to the outdoors. See 

Ven-

tilation Air from Outdoors

.

C.  Install a lower Btu/Hr gas log heater, if lower 

Btu/Hr size makes room unconfined. 

If the actual Btu/Hr used is less than the maxi

-

mum Btu/Hr the space can support, the space is 

an unconfined space. You will need no additional 

fresh air ventilation. 

  WARNING:  If  the  area  in 

which  the  firebox  and  gas  log 

heater  may  be  operated  is 

smaller  than  that  defined  as 

an  unconfined  space  or  if  the 

building  is  of  unusually  tight 

construction, provide adequate 

combustion and ventilation air 

by one of the methods described 

in the 

National Fuel Gas Code, 

ANS Z223.1/NFPA 54, Section 5.3

 

or applicable local codes.

VENTILATION AIR

Ventilation Air From Inside Building 

This fresh air would come from an adjoining un

-

confined space. When ventilating to an adjoining 

unconfined space, you must provide two perma

-

nent openings: one within 12" of the ceiling and 

one within 12" of the floor on the wall connecting 

the two spaces (see option 1, Figure 3). You can 

also remove door into adjoining room (see op

-

tion 2, Figure 3). Follow the 

National Fuel Gas 

Code ANS Z223.1/NFPA 54, Section 5.3, Air for 

Combustion and Ventilation

 for required size of 

ventilation grills or ducts. 

aiR FOR COMBUSTiON 

aND VENTiLaTiON

Continued

  WARNING:  Rework  work-

sheet, adding the space of the 

adjoining unconfined space. The 

combined  spaces  must  have 

enough  fresh  air  to  supply  all 

appliances in both spaces.

Figure 3 - Ventilation Air from Inside 

Building

Or

Remove

Door into
Adjoining

Room,
Option

2

Ventilation

Grills 

Into Adjoining 

Room,

Option 1

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or 

ducts. You must provide two permanent openings: 

one within 12" of the ceiling and one within 12" 

of the floor. Connect these items directly to the 

outdoors or spaces open to the outdoors. These 

spaces include attics and crawl spaces. Follow the 

National Fuel Gas Code ANS Z223.1/NFPA 54, 

Section 5.3, Air for Combustion and Ventilation

 for 

required size of ventilation grills or ducts.

IMPORTANT:

 Do not provide openings for inlet 

or outlet air into attic if attic has a thermostat-

controlled power vent. Heated air entering the attic 

will activate the power vent.

Figure 4 - Ventilation Air from Outdoors

Outlet

Air

Ventilated

Attic 

Outlet

Air

Inlet

Air

Inlet Air

Ventilated 

Crawl Space

To 

Crawl

Space

To Attic

Summary of Contents for FBST

Page 1: ...ce WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch Do not use any phone in your building Immediatelycallyourgassupplierfromaneighbor s phone Follow the...

Page 2: ...local codes Aftermarket Completion of sale not for purpose of resale from the manufacturer State of Massachusetts The installation must be made by a licensed plumber or gas fitter in the Commonwealth...

Page 3: ...een hood and brick liner in place Make sure these parts are in place and screens are closed before running firebox The supplied hoods may not be replaced with hoods which may be provided with a log he...

Page 4: ...ng model num ber serial number clearances etc is located directly above thebricklinerandundertheheat shield See Figure 20 page 15 Product Features Operation This firebox is designed for use with appro...

Page 5: ...to insure proper fresh air for this and other fuel burning appliances in your home Today s homes are built more energy efficient than ever New materials increased insulation and new construction meth...

Page 6: ...ating only if there are doorless passageways or ventilation grills between them AIR FOR COMBUSTION AND VENTILATION Continued DETERMINING FRESH AIR FLOW FOR Firebox LOCATION Determining if You Have a C...

Page 7: ...two perma nent openings one within 12 of the ceiling and one within 12 of the floor on the wall connecting the two spaces see option 1 Figure 3 You can also remove door into adjoining room see op tio...

Page 8: ...cause mildew to form from too much moisture See Air for Combustion and Ventilation page 5 IMPORTANT Make sure the firebox is level If firebox is not level log set will not work properly Note Your Vang...

Page 9: ...mes Wire mesh Screen Firebox Top Mantel Shelf 3 6 9 1 4 Combustible Material 1 1 2 Max Thickness Note All vertical measurements are from top of fireplace hood to bottom of mantel shelf These minimum c...

Page 10: ...Wiring Firebox page 12 5 Carefully set firebox in front of rough open ing IMPORTANT If installing brass trim kit see instructions included with brass trim accessory You must install shoulder screws fr...

Page 11: ...firebox enclosure where it can be accessed with a key through a wall as shown in Figure 13 Depending on the type of installation some local codes may require you to install two 2 manual shutoff valve...

Page 12: ...orepressure testing gas piping Damage to gas valve may result and an un safe condition may be caused The appliance and its individual shutoff valve must be disconnected from the gas supply piping syst...

Page 13: ...de door panel forward and up to remove tabs on panel from locating slots in firebox see Figure 16 3 Locatethetwostripsofhookandloopmounting strips on one side of the base of the lower com partment Ali...

Page 14: ...th Blower Receptacle Hook and Loop Mounting Strips Control Knob Lock Nut Speed Control Shaft Figure 18 Installing Optional Blower GA3500A Operating Optional Blower GA3500A Light your gas appliance wit...

Page 15: ...rners and circulating air passageways of the appliance be kept clean WARNING Children and adults should be alerted to the hazardsofhighsurfacetempera tures and to stay away to avoid burnsorclothingign...

Page 16: ...Illustrated Parts Breakdown Model FBST These items are used on both sides of fireplace 8 14 16 16 16 7 1 7 2 2 16 11 16 12 6 6 6 15 15 15 15 13 13 10 5 15 15 15 15 6 6 15 15 4 15 15 15 15 15 15 15 4 1...

Page 17: ...cer 4 5 26731 Deflector Hood 2 6 26740 Nailing Flange 8 7 1 02013 Side Refractory Brick Liner 2 7 2 02014 Bottom Refractory Brick Liner 2 8 24007 Side Refractory Retainer 4 9 12125 Screen 4 10 26752 E...

Page 18: ...with the FBST fireboxes for bidirectional heat circula tion and may be installed during or after firebox installation Brass Trim GA6093 Easily clips around firebox to provide a finished appearance co...

Page 19: ...___________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________...

Page 20: ...ring a defective heater will be the responsibility of the owner TO THE FULL EXTENT ALLOWED BY THE LAW OF THE JURISDICTION THAT GOVERNS THE SALE OF THE PRODUCT THIS EXPRESS WARRANTY EXCLUDES ANY AND AL...

Reviews: