background image

5

55504

Figure 12

Figure 13

ATTACH BRACKET
TABS TO OUTER
PIPE (3 PLACES)
SECURE WITH
SCREWS

OVERLAP
SHINGLES
TOP AND SIDES

TERMINATION

FLUE PIPE OF
TERMINATION INSIDE
INNER PIPE OF
CHIMNEY

CAULK

COLLAR

FLASHING

UNDERLAP SHINGLES

BOTTOM ONLY

2"

2"

STEP 4: Remove the shingles around the opening measured and cut
out this section.

STEP 5: Add the next sections of the pipe until the end penetrates the
roofline.  Check to see that proper clearances are maintained.  Extend
chimney by adding sections of double wall pipe until pipe has reached
a minimum of 30 inches above highest point of roof cutout.  Termina-
tion and chimney must extend a minimum of 36 inches above highest
point where it passes through the roof.  (See 10'  Rule, Figure 12).

TERMINATIONS

The firebox and chimney system must be vented to the out-of-doors
and must be terminated with the listed round top or chase termina-
tions.  If a chase termination is desired, refer to the instructions
supplied with the termination.

FOR ROUND TOP TERMINATION

STEP 1: Slide the flashing over the pipe (No firestop is needed at the
roof level).  Tack the flashing down at the top two corners with roofing
nails.  Lay tile over the top and sides of the flashing and secure them
to the roof through the flashing with the roof nails.  Lay tiles under the
lower edge and secure these to the roof.  Mastic all nail heads.

STEP 2: Install storm collar (VSC1-20-8DM, VSC2-20-8DM) on double
wall chimney, apply waterproof caulking around flashing top and push
storm collar down securely on sealer and flashing (see Figure 13).

STEP 3: Place the VRTL-8DM TERMINATION into the pipe end
as illustrated in Figure 13 and secure with screws provided.

10 FOOT RULE

All chimney terminations must extend a minimum of 3 feet in height
above the highest point where it passes through the roof and must be
at least 2 feet above the peak of the roof if within a horizontal distance
of 10 feet from the peak (see Figure 12).

OUTSIDE OF
FIREPLACE

GAS LINE
CONDUIT

REMOVE
KNOCKOUT

SIDE FIREBRICK
FINISHED SIDE

REFRACTORY
KNOCKOUT PLUG
REMOVE BY TAPPING
LIGHTLY WITH A 
1/2" DOWEL

AFTER REMOVING
GAS LINE COVER
PLATE, REPLACE
SCREWS

REMOVE
INSULATION
TEMPORARILY
(DO NOT
DISCARD)

REMOVE
GAS CONDUIT
COVER

Figure 14

OUTSIDE OF
FIREPLACE

GAS LINE
CONDUIT

REPACK
INSULATION

INCOMING
1/2" BLACK
IRON PIPE

PROVIDE ENOUGH
THREADED END
FOR FITTING
CONNECTION

SEAL OPENING
WITH REFRACTORY
CEMENT

SIDE FIREBRICK
FINISHED SIDE

Figure 15

IMPORTANT:  If an exposed portion of chimney is greater than 5
feet above the roof line, use support wires to keep chimney secured.
The support wires may be attached to the outer pipe of the chimney
with screws, provided the screws are not long enough to penetrate the
inner flue pipe.

CAUTION:  Do not seal ventilation openings on the
rooftop flashing.  Follow the installation instructions
provided with the termination being used.

A gas line may be installed for the purpose of installing a gas appliance
available through your local distributor. Use only 

1

/

2

" black iron pipe

and appropriate fittings. When installing a gas line, a shut-off valve
designed for installation outside the firebox is recommended.

The gas pipe is intended for connection to an unvented gas log set or
to a decorative gas appliance.

If you will install an unvented gas log set, ONLY UNVENTED GAS
LOG SETS WHICH HAVE BEEN FOUND TO COMPLY WITH
THE STANDARD FOR UNVENTED ROOM HEATERS, ANS/IAS/
AGA Z21.11.2, ARE TO BE INSTALLED IN THIS FIREPLACE.

NOTE: An appropriate Vanguard hood must be installed when
using an unvented gas log set.

WARNING: DO NOT OPERATE AN UNVENTED GAS
LOG SET IN THIS FIREPLACE WITH THE CHIMNEY
REMOVED.

If you will install a decorative gas appliance, the decorative gas
appliance must comply with the Standard for Decorative Gas
Appliances for Installation in solid Fuel burning Fireplaces,
ANS Z21.60-1996
 and shall also be installed in accordance with the
National Fuel Gas code, ANS Z223.1-1996.

WARNING: WHEN USING A DECORATIVE APPLIANCE,
THE DAMPER MUST BE REMOVED OR PERMANENTLY
LOCKED IN THE FULLY OPEN POSITION.

To install the gas line, remove the gas line plug located in the side
firebrick approx. 2 inches above the bottom. The plug must be tapped
out from the finished side towards the unfinished side (see Figure
14). Insert the gas line parallel to the face. Fill any gap between the
gas line and the hole in the firebrick with refractory cement or
commercial furnace cement (see Figure 15).

10 FOOT RULE

2' MIN.

2' MIN.

LEVEL OF FLUE

GAS OUTLET

10'

3' MIN.

3' MIN.

10'

OR LESS

Summary of Contents for ARISTOCRAT V36EC2

Page 1: ...NG GREEN KY 42102 9004 55504 Rev B 08 99 ARISTOCRAT MODEL V36EC2 LOUVERED CIRCULATING WOOD BURNING FIREBOX 21 3 8 42 35 36 41 23 1 4 0 IN TO TOP SPACER AIR KIT K O GAS LINE K O 3 4 AIR SPACE BACK AND...

Page 2: ...ar sidewall A 2 inch minimum air space clearance between combustible materials and the chimney must be absolutely maintained A 16 1 2 inch inside chase dimension is recommended as a minimum size A 3 4...

Page 3: ...rt if properly locked It is not necessary to add screws to keep the chimney together FIRESTOP SPACERS VFS 8DM Firestop spacers are required at each point where the chimney penetrates a floor or ceilin...

Page 4: ...ar opening must be cut STEP 1 Determine the center point through which the pipe will penetrate the roof STEP 2 Determine the pitch of the roof Pitch is the distance the roof drops over a given span us...

Page 5: ...TION TEMPORARILY DO NOT DISCARD REMOVE GAS CONDUIT COVER Figure 14 OUTSIDE OF FIREPLACE GAS LINE CONDUIT REPACK INSULATION INCOMING 1 2 BLACK IRON PIPE PROVIDE ENOUGH THREADED END FOR FITTING CONNECTI...

Page 6: ...handling during installation These should be sealed with non combustiblematerials Ifthefireboxismountedonaraisedplatform insulate below the platform to prevent the entry of cold air through the firebo...

Page 7: ...e sides and the top of the firebox face It is important that combustible materials do not overlap the face itself Brick tile or other noncombustible materials may be applied to the face provided that...

Page 8: ...8DM 0 to 6 12 V12F 8DM 6 12 to 12 12 EMBER PROTECTOR EP 36 ROUND TOP TERMINATION VRTL 8DM VRTTL 8DM VADS 8DM ECONO TOP TERMINATION VETO 8DM VETLO 8DM GLASS DOOR KIT VDG36E Brushed Brass VDP36E Polishe...

Reviews: