LTCA-10/LTCA-40 USER’S MANUAL
30
1.
YES
If you wish to convert readings to standard temperature, press the
[1]
key (
YES
).
The “WINDING MATERIAL” menu will be displayed:
a.
Press the
[1]
key to select copper as the winding material.
Continue to
step g.
b.
Press the
[2]
key to select aluminum as the winding material.
Continue to
step g.
c.
Press the
[3]
key to manually enter the Tk value. The following screen
will be displayed:
You can increase the Tk value by 0.5
°
C increments by pressing the
[PAPER
∧
Contrast]
key.
You can decrease the Tk value by 0.5
°
C increments by pressing the
[PAPER
∨
Contrast]
key.
Press the
[ENTER]
key to confirm your temperature selection.
Continue
to step g.
2.
NO
If you do NOT wish to convert readings to standard temperature, press the
[2]
key (
NO
) and
continue to step i
.
g.
After the Tk value has been selected, the “D.U.T. TEMP” screen will be displayed:
Use the
[PAPER
∧
Contrast]
and
[PAPER
∨
Contrast]
keys to adjust the D.U.T.
temperature.
Press the
[ENTER]
key to confirm the temperature selection.
D.U.T. TEMP
25.0
°
C 77.0
°
F
↑↓
to adjust temp
“ENTER” to accept
Tk:
230.0
°
C
↑↓
to adjust Tk
“ENTER” to accept
WINDING MATERIAL
1.
COPPER, Tk=234.5
2.
ALUMINUM, Tk=225.0
3.
MANUALLY ENTER Tk
Summary of Contents for LTCA-10
Page 17: ...LTCA 10 LTCA 40 USER S MANUAL 17 Figure 5 0 Typical LTCA 40 Connection Diagram 2 Windings...
Page 18: ...LTCA 10 LTCA 40 USER S MANUAL 18 Figure 6 0 Typical LTCA 40 Connection Diagram 3 Windings...
Page 28: ...LTCA 10 LTCA 40 USER S MANUAL 28 Figure 9 0 Typical Single Reading Test Report Printout...
Page 41: ...LTCA 10 LTCA 40 USER S MANUAL 41 Figure 12 0 Sample Dynamic LTC Test Expansion Plot...
Page 49: ...LTCA 10 LTCA 40 USER S MANUAL 49 Figure 13 0 Typical Test Record Printout...
Page 51: ...LTCA 10 LTCA 40 USER S MANUAL 51 Figure 14 0 Typical Record Directory Printout...