9
Interface to SPC Panel/System
56
Vanderbilt
Seismic Detectors Application Guide
I-200153-1
08.2016
9.3
Test and indication flow
9.4
User Interface
When using the compact keypad as the user interface the following menu options will be available
for automatic and manual testing of all of the detectors on a system.
To perform a seismic test, enter the required passcode and follow the steps indicated below;
a) Scroll to TEST > SEISMIC TEST.
b) Press SELECT.
c) Select TEST ALL AREAS, or select an individual area to test.
d) If you select an individual area to test, you can select either TEST ALL ZONES or select a
specific seismic zone to test.
The message ‘SEISMIC TEST’ is displayed on the keypad and flashes while the test is being
performed,
If the test fails, the message ‘SEISMIC FAIL’ is displayed. If the “i” or VIEW key is pressed, a
scrollable list of the failed zones is displayed.
If the test succeeds, ‘SEISMIC OK’ is displayed.
SPC Panel
Zones 1-8
Output 3 allocated Seismic
test
Expander 1
Zones 9-16
Relay #1 allocated seismic test
Expander 2
Zones 17- 24
Relay #1 allocated seismic test
Seismic Inputs
Zones 1, 3, 4 & 8 = GM775
Zones 1 & 8 tested via GMXS1
Zones 3 & 4 tested via GMXS5
Seismic Outputs
Output simultaneously activates
all GMXS1 and GMXS5 test trans-
mitters
Seismic Inputs
Zone 9 = GM730
Zone 10 = GM775
Zones 9 & 10 tested via GMXS1
Seismic Outputs
Output simultaneously activates
all GMXS1 test transmitters
Seismic test command
Automatic
Auto/set
Manual command from keypad
Seismic Inputs
Zones 21, 23 & 24 = GM775
Zones 21 & 24 tested via GMXS1
Zones 23 & 4 tested via GMXS5
Seismic Outputs
Output simultaneously activates all
GMXS1 and GMXS5 test transmit-
ters