6.2 Communication protocols
6 Communication
Technical description
142
VAMP 24h support phone +358 (0)20 753 3264
VM265.EN011
Parameters
Parameter Value
Unit Description
Note
Addr
1
247
Modbus address for the
device.
Broadcast address 0 can
be used for clock
synchronizing. Modbus
TCP uses also the TCP
port settings.
Set
bit/s
1200
2400
4800
9600
19200
bps
Communication speed for
Modbus RTU
Set
Parity
None
Even
Odd
Parity for Modbus RTU
Set
Set = An editable parameter (password needed)
6.2.3.
Profibus DP
The Profibus DP protocol is widely used in industry. An
external VPA 3CG or an internal Profibus module (see the
order code in chapter 12.) is required.
Device profile "continuous mode"
In this mode the device is sending a configured set of data
parameters continuously to the Profibus DP master. The
benefit of this mode is the speed and easy access to the data in
the Profibus master. The drawback is the maximum buffer size
of 128 bytes, which limits the number of data items transferred
to the master. Some PLCs have their own limitation for the
Profibus buffer size, which may further limit the number of
transferred data items.
Device profile "Request mode"
Using the request mode it is possible to read all the available
data from the VAMP device and still use only a very short
buffer for Profibus data transfer. The drawback is the slower
overall speed of the data transfer and the need of increased
data processing at the Profibus master as every data item must
be separately requested by the master.
NOTE! In request more it is not possible to read continuously only one single
data item. At least two data items must be read in turn to get updated
data from the device.
There is a separate manual for VPA 3CG with the code
VMVPA.ENXX available for the continuous mode and request
mode.