UK
ENGLISH
DSBA3002 • Rév. 19/03/2018
20
1)
The actuator tolerates voltage fluctuation of the electrical grid up to ± 10 % of its nominal system operating voltage
2)
The actuator tolerates temporary overvoltage of the electrical grid
VT600 VT1000
Location
Materials
Housing: Alu EPOXY paint / cover: PA6 UL 94 V-0 or Alu EPOXY paint
Drive : Steel + Zn treatment / Axles and screws : Stainless steel
Sealing
IP68
Environment
Both inside and outside (wet environments possible)
Operating temperature
-20°C to +70°C
Operating altitude
Up to 2000m
Hygrometry
maximum relative humidity 80% for temperatures up to 31°C decreasing linearly to 50% rela-
tive humidity at 40°C
Pollution degree
Applicable POLLUTION DEGREE of the intended environment is 2
(in most cases).
Weight
25kg
Mechanical data
Nominal torque
450Nm
600Nm
Maximum torque
600Nm
1000Nm
Operating time (90°)
42s
65s
Angular range
90° (180°-270° on request)
Duty cycle
50%
Drive ISO5211
Star 36 (depth 41mm) • F10/F12 (depth F10 : 25mm / F12 : 30mm)
Manual control
Secured hand wheel without clutching system
Electrical data
Voltages
1)
230V AC (50/60Hz) • 400V 3-phase
Overvoltage category
2)
Power
250W
Rated current
10 to 12A
Torque limiter
Mechanical
Number of feedback switches
2 (4 on request)
Limit switches maximum voltage
4 to 250V AC/DC (Overvoltage category II)
Limit switches maximum current
1mA to 5A max
Anticondensation heaters
10W