UK
ENGLISH
DSBA3401 • Rév. 13/03/2018
39
1 Shunts positioning K1, K2 and K3
Position the shunts as follows (before modification, switch off the card):
Selection of the flow direction of the valve
2.1 Normal flow direction (by default)
- Press the
OPEN
button and apply the operating voltage to the card while keeping this button pressed.
- The
green LED
lights up. Release the OPEN button.
- Disconnect the card.
2.2 Inverse flow direction
- Press the
CLOSE
button and apply the operating voltage to the card while keeping this button pressed.
- The
red LED
lights up. Release the CLOSE button.
- Disconnect the card.
3 Selection of the type of input control signal
3.1 Voltage control signal 0-10V
- Press the
MEM
button and apply the operating voltage to the card while keeping this button pressed.
- The
red LED
will light up 3 times. Release this button.
- Disconnect the card.
3.2 Current control signal 0-20mA
- This configuration can be performed only in our factory
3.3 Current control signal 4-20mA (by default)
- Press the
MEM and CLOSE
buttons and apply the operating voltage to the card while keeping these
buttons pressed.
- The
red LED
will light up 3 times. Release these buttons.
- Disconnect the card.
4 Learning mode
- Press the
OPEN and CLOSE
buttons and apply the operating voltage to the card while keeping these
buttons pressed.
- The
2 LED
will light up. Release these buttons and the
2 LED
will extinguish. The card is now in the
learning mode.
- Press the
CLOSE
button to put the valve in its closed position. The
red LED
will light up.
- Store this selected closed position by pushing
MEM + CLOSE
, the
red LED
will light up 2 times as a
confirmation of acknowledgement.
- Press the
OPEN
button to put the valve in its open position. The
green LED
will light up.
- Store this selected open position by pushing
MEM + OPEN
, the
green LED
will light up 2 times as a
confirmation of acknowledgement.
- Now, the positions selected have been stored. Disconnect the card.
NORMAL OPERATING MODE
- Apply the operating voltage to the card. The
green LED
will light up 3 times.
- Under normal operating conditions, the
green LED
will light up when the drive motor opens the valve,
and the
red LED
will light up when the drive motor closes it.
- If
both LED
remain extinguished, it means that the drive motor has not been triggered.
- In the case of an over torque, the motor stops and the
2 LED
lights then together to indicate the action of the
torque limiter. To re-start it, you must either reverse the sense of rotation, either switch the power off and on.
G
R
R
R
G
R
R
R
G
G
G
G
R
K3 ON
K3 OFF
OFF
ON
Set-point signal
Output
signal
Schunt K1
Schunt K2
Schunt K3
A
B
A
B
0-10V 0-10V
ON
OFF
ON
OFF OFF
0-10V 0-20mA
ON
OFF OFF
ON
OFF
0-10V 4-20mA
ON
OFF OFF
ON ON
4-20mA 0-10V
OFF
ON ON
OFF OFF
4-20mA 0-20mA
OFF
ON
OFF
ON
OFF
4-20mA 4-20mA
OFF
ON
OFF
ON ON
0-20mA 0-10V
OFF
ON ON
OFF OFF
0-20mA 0-20mA
OFF
ON
OFF
ON
OFF
0-20mA 4-20mA
OFF
ON
OFF
ON ON
This configuration can be
performed only in our
factory
POSI: parameter selection sequence