background image

4006080-04

DO NOT USE thermostatic handset supplied with 

appliance when installing outdoors!

USE 1265WSK or RBWSK (appliance installed under 

overhang)

FIREPLACE

BATTERY

ACCESS

UP

ON-OFF

DOWN

ACCÈS

PILES

DU FOYER

X X

Use with Valor Zero Clearance heater models 530, 534, 650, 1000, 1100, 1150, 1400, 

1500, 1600, 1700, 1800 and Insert heater models 700, 738K, 739, 780, 785, RF24KB, 

RF24JD installed into existing approved solid-fuel burning fireplaces having weather 

protection as specified in this manual.

GV60 Outdoor Fireplace Conversion Kit

INSTALLATION MANUAL

GV60CKO

© Copyright Miles Industries Ltd., 2021.

WARNING

This conversion kit shall be installed by 

a qualified service agency in accordance 

with the manufacturer’s instructions and 

all applicable codes and requirements 

of the authority having jurisdiction. If 

the information in these instructions is 

not followed exactly, a fire, explosion 

or production of carbon monoxide may 

result causing property damage, personal 

injury or loss of life. The qualified service 

agency is responsible for the proper 

installation of this kit. The installation 

is not proper and complete until the 

operation of the converted appliance is 

checked as specified in the manufacturer’s 

instructions supplied with the kit.

Use this manual in conjunction with the 

installation manual supplied with the 

appliance.
LEAVE THIS MANUAL WITH THE HOMEOWNER.

WARNING

Electrical shock hazard - Do not install 

electrical accessories (fans, lighting, wifi) 

when converting the appliance for use 

outdoors.

General notes regarding conversion

This manual contains instructions for adapting natural 

gas or propane models listed above for use outdoors. 

For the purpose of this manual the term “outdoor” 

means installed outside of the insulated building 

envelope within a weatherproof enclosure or existing 

solid-fuel burning fireplace having a minimum required 

overhang. The outdoor space may be attached or free 

standing to the main/primary structure and may or may 

not include walls. See page 6 for further information 

regarding locating your outdoor fireplace.
Use this manual in conjunction with the installation 

manual supplied with the appliance. The outdoor 

fireplace must be permanently situated and connected 

to a fixed piping system and must not be portable.

Notes

•  No electrical accessories (fans, lighting or wifi) per-

mitted when adapting the appliance for outdoor use.

•  Any of the optional available trims and fronts may 

be used in the outdoor environment including 

optional HeatShift components although please 

note that some fading or corrosion may occur due to 

environmental conditions.

 Cast iron fronts are not 

recommended outdoors.

•  Thermostatic controls are not allowed for outdoor 

fireplaces. Use the wall switch supplied with the 

appliance or when not supplied, order an optional 

RBWSK Remote battery and wall switch kit to control 

the appliance. 

Do not use the thermostatic remote 

controled handset supplied with the appliance!

1265WSK–

Wall Switch

RBWSK–

Remote Batteries & 

Wall Switch Kit

Summary of Contents for GV60 SYMAX

Page 1: ...zard Do not install electrical accessories fans lighting wifi when converting the appliance for use outdoors General notes regarding conversion This manual contains instructions for adapting natural gas or propane models listed above for use outdoors For the purpose of this manual the term outdoor means installed outside of the insulated building envelope within a weatherproof enclosure or existin...

Page 2: ...t supplied separately to the outdoor receiver see installation instructions supplied with the kit Valve Wire Harness Red Yellow Wall Switch Harness RBWSK Remote Battery Wall Switch kit power connector 6 Insert 4 AA alkaline batteries into the outdoor receiver or the RBWSK kit only after all connections are completed 7 Test the operation of the wall switch see appliance s or wall switch kit instruc...

Page 3: ...der and turning the gas shut off valve to the off position Upon ensuring the fireplace cannot be turned on you can then apply a weather protective cover over the front of the fireplace to help preserve the finish and further protect the appliance from weather Note Do not operate your outdoor fireplace during cold weather below freezing point 32 F 0 C Fix the conversion label and replace the lighti...

Page 4: ...tch 1 Wait ve 5 minutes to clear out any gas then smell for gas including near the Àoor If you smell gas STOP Follow B in the safety information above on this label If you don t smell gas go to the next step 3 AUTOMATIC IGNITION MAN knob 2 in ON position Ensure Flame Adjustment knob 3 is set to lowest setting 3 Fig 1 Locate the pilot Fig 3 inside of rebox On the wall switch press the ON button a s...

Page 5: ...rm as an exterior wall If installed against an exterior wall we recommend the appliance enclosure or chase be constructed completely outside of the insultated building envelope and weather membrane The fireplace must be permanently situated and connected to a fixed piping system it is not portable Weather Protection Moisture Resistance This outdoor fireplace will tolerate moderate amounts of water...

Page 6: ... fireplace insert 1600 See through Continuous insulated building envelope and weatherproof membrane is NOT interrupted by fireplace installation INSIDE INSIDE OUTSIDE Min weatherproof overhang in front and at sides Sidewall vent terminations within 7 of grade or where easily accessible require a terminal guard DO NOT INTERRUPT BUILDING ENVELOP WITH ZERO CLEARANCE GAS FIREPLACE INSTALLATION See app...

Page 7: ...6 914 mm of front of appliance Min required weatherproof overhang Combustible Overhang 54 Min to Combustible Overhang non combustible construction permited lower Note Use of the optional HeatShift System Kits affects mantel and hearth clearances See instructions in fireplace s Installation manual not to scale ...

Page 8: ... 30 of the total perimeter wall area surrounding the outdoor space must be openings KEY VENT TERMINAL LOCATIONS MINIMUM DISTANCES Measured from the center of vent MINIMUM CLEARANCE Inches Cm A Clearance above grade verandah porch deck or balcony 12 30 B Clearance to window or door that may be opened 12 30 C Clearance to permanently closed window recommended to prevent condensation on window 12 30 ...

Page 9: ...e install repaired or replacement parts f The initial owner of the unit will be responsible for any shipping charges for replacement parts as well as travel time incurred by the dealer to perform the warranty work g This warranty applies to non commercial use and service and is void if it is apparent that there is abuse misuse alteration improper installation accident or lack of maintenance to the...

Page 10: ...rupteur mural fourni avec le foyer ou lorsque non fourni commandez le Porte piles et interrupteur mural RBWSK pour contrôler le foyer NE PAS UTILISER la manette thermostatique de télécommande fournie avec l appareil 1265WSK Interrupteur mural RBWSK Porte piles et Interrupteur mural Utilisez avec les foyers Valor à dégagement zéro ZC 530 534 650 1000 1100 1150 1400 1500 1600 1700 1800 et encastrabl...

Page 11: ...avoir rebranché toutes les connexions 7 Vérifiez le fonctionnement de l interrupteur con sultez le guide du foyer ou de l interrupteur mural pour savoir comment fonctionne l interrupteur Harnais connexion soupape Connexion du fil d allumage cosse Faites attention quand vous débranchez et rebranchez le fil d allumage de ne pas plier ou briser la cosse Rouge Jaune Harnais de connexion Interrupteur m...

Page 12: ...n position off En vous assurant bien que le foyer ne peut se rallumer vous pouvez en couvrir la devanture avec une paroi de protection à l épreuve des intempéries afin d en préserver le fini et de protéger l appareil Note Ne pas faire fonctionner le foyer extérieur lorsque la température est au point de congélation ou plus froide 0 C 32 F Renseignements additionnels pour les consommateurs Apposez ...

Page 13: ...TOMATIQUE Bouton MAN à ON 2 Assurez vous que le bouton de réglage des Àammes 3 est au réglage le plus bas 3 g 1 Repérez la veilleuse g 3 dans la boîte de foyer Sur l interrupteur mural appuyez le bouton ON OFF un court signal sonore indiquera le début du procédé d allumage De courts signaux sonores seront entendus jusqu à ce que l allumage soit complet et que le gaz ait circulé dans les tuyaux jus...

Page 14: ... murs ou non Note Le foyer ne peut être installé à titre de mur extérieur Si le foyer est installé contre un mur extérieur nous conseillons la construction de l encastrement ou de la charpente complètement en dehors de l enveloppe du bâtiment et du revêtement d étanchéité Le foyer doit être installé de façon permanente et raccordé à un système de tuyauterie fixe il n est pas portatif Protection co...

Page 15: ...nt Encastrement à l épreuve des intempéries Enveloppe isolante continue de l édifice et membrane à l épreuve des intempéries NE SONT PAS interrompues par l installation du foyer Taille minimale du surplomb à l épreuve des intempéries à l avant et de chaque côté du foyer Taille minimale du surplomb à l épreuve des intempéries à l avant et de chaque côté du foyer Taille minimale du surplomb à l épre...

Page 16: ...du foyer Minimum 54 1372 mm jusqu au surplomb construction incombustible permise plus bas Surplomb minimum à l épreuve des intempéries exigé Note L utilisation du Système Heat Shift optionnel affecte les dégage ments aux manteau et dalle protec trice Consultez le Guide d installation HeatShift fourni en appendice du Guide d installation du foyer pas à l échelle ...

Page 17: ...l à partir de l axe central du compteur régulateur situé à moins de 15 pieds 4 6 m sous la sortie d évacuation 36 90 I Dégagement à partir de la sortie d air vicié du régulateur 36 90 J Dégagement à partir d une entrée d air non mécanisée de l immeuble ou d une entrée d air comburant de tout autre appareil 12 30 K Dégagement à partir d une entrée d air mécanisée 72 180 L Dégagement au dessus d un ...

Page 18: ...ctueuses ou la réinstallation de pièces réparées ou remplacées f Le propriétaire original de l appareil sera responsable des frais d expédition pour le remplacement de pièces de même que des frais de déplacement encourus par le réparateur pour e ectuer une réparation couverte par la garantie g Cette garantie s applique seulement dans les cas d utilisation non commerciale et elle est nulle lorsqu i...

Reviews: