Valor DuraVent 46DVA FF Co-axial DV Flex Series Installation Manual Download Page 3

3

Typical Applications

Wall termination
with “slip”
connection

Short rigid pipe
section thru wall

Rigid elbow
(used to keep pipe closer to
wall and avoid/eliminate
possible gooseneck in flex)

Flex pipe to
provide offset

This end will ONLY fit to
DuraVent style collars

Wall thimble
(required for 
combustible 
construction)

Wall termination
with “slip”
connection

Short rigid pipe
section thru wall

Flex pipe to
provide bend

This end will ONLY fit to
DuraVent style collars

Wall thimble
(required for 
combustible 
construction)

Min. 7”
radius

DuraVent rigid pipe
section or
DuraVent collar/adapter
on appliance

Minimum 5% rise between
end collars of flex when
running horizontally - 
i.e. min. 2” rise for 36“ length
and min. 6” rise for 120” length

Flex pipe to
provide offset

Rigid pipe
section

DuraVent rigid pipe
section or
DuraVent collar/adapter
on appliance

Summary of Contents for DuraVent 46DVA FF Co-axial DV Flex Series

Page 1: ...ature 2 wide self adhesive aluminum foil tape Nashua 322 2 brand or similar Wrap the tape completely around all joints and press firmly to seal DO NOT cut flex DO NOT run flex through walls floor ceil...

Page 2: ...ce required above pipe and min 1 at sides and below pipe 36FF 22 overall 60FF 32 overall 36FF 15 120FF 58 overall 60FF 25 120FF 51 36FF 36 approximately 60FF 60 approximately 120FF 120 approximately D...

Page 3: ...l termination with slip connection Short rigid pipe section thru wall Flex pipe to provide bend This end will ONLY fit to DuraVent style collars Wall thimble required for combustible construction Min...

Page 4: ...flex Always inspect the in ternal and external flex for tears particularly around rivets after stretching flex 3 After independently stretching the inner and outer flex to the desired length and shape...

Page 5: ...ute qualit certifi pour les hautes temp ratures tel que la marque Nashua 322 2 ou similaire Couvrez compl tement tous les joints et pressez le ruban fermement pour bien le sceller AVERTISSEMENT Si les...

Page 6: ...uit 36FF total 22 60FF total 32 36FF 15 120FF total 58 60FF 25 120FF 51 36FF approximativement 36 60FF approximativement 60 120FF approximativement 120 NE COUPEZ PAS LE CONDUIT FLEX 3 3 4 4 Buse d tac...

Page 7: ...d vacuation raccordement coulissant Section de conduit rigide travers le mur Conduit flex pour une courbe Ce bout se raccorde SEULEMENT qu des buses de style DuraVent Fourreau exig pour construction...

Page 8: ...Une fois tir s inspectez toujours les flex interne et externe pour vous assurer qu ils ne sont pas d chir s par ticuli rement autour des rivets 3 Apr s avoir tir s par ment les flex int rieur et ext...

Reviews: