2.
The flue must conform to BS 5440: Part 1 in design and installation.
The flue, measured from the bottom of the fireplace opening to the bottom of the
terminal, shall be not less than 3m in actual vertical height. When calculated in
accordance with BS 5440: Part 1 Annex A, the minimum
equivalent
height of the flue
shall be 2.0m of 125mm dia. flue pipe.
3.
The flue must not be used for any other appliance or application.
4
.
Proprietary terminals must comply with BS 715 or BS 1289. Any terminal or
termination must be positioned in accordance with BS 5440 Part 1 to ensure that the
products of combustion can be safely dispersed into the outside atmosphere. Where
the appliance is connected to an unlined brick chimney it is generally unnecessary for
the chimney pot to be replaced or for a terminal to be fitted unless the flue has a
diameter smaller than 170mm.
4. PACK CONTENTS
(See figure 8).
Carefully remove all the contents. Take special care in handling the ceramic fuel
effects. Check that all the listed parts are present and in good condition. The pack
may contain additional components to that stated above. These can be discarded.
1
Burner & Hotbox Unit
1
Spillage plate.
1
Nut & olive for 8mm inlet pipe
1
Inlet ‘T’ Connector
1
Flue restrictor
2
Screws (For flue restrictor)
2
Fireback spacing brackets
2
Screws (For Fireback spacing brackets)
1
Ceramic fuel effect pack (Not shown)
1
Strip of floor sealing tape.
6
Fibre / wooden plugs
2
Woodscrews
2
Fire retaining cables
2
Cable clamps
4
Eyebolts
1
Rubber grommet
1
Smoke match tube
2
Lengths of self adhesive foam seal
1
Literature pack (Not shown)
1
Fascia
1
Fascia casting
1
Spacer frame (This is supplied as three separate pieces and 2 screws)
6
Edge clips (For securing spacer frame to hotbox).
Page 17
©
Baxi Heating U.K. Limited 2009.
INSTALLER GUIDE