out
.
Listen for a snap sound at the gas tap.
Note the time when the sound is
heard
.
This sound is caused by an electromagnetic valve shutting off the gas supply
through the tap. The valve is located in the body of the tap. The valve should operate
within 60 seconds of the pilot going out
.
If the valve does not operate within this
time limit do not allow the appliance to be used until the fault has been corrected.
This monitoring system must not be adjusted, bypassed or put out of
operation.
This monitoring system, or any of its parts, must only be exchanged using
authorised parts.
3.
Open the isolating valve on the inlet ‘T’ connector. Screw on the end cap and test
for gas soundness using a suitable leak detector.
4.
Set the slider to the “OFF’” position.
Page 33
©