Vallox VALLOX 121 SE Series Operating, Maintenance And Technical Instructions Download Page 5

5

© VALLOX • We reserve the right to make changes without prior notice.
What the units include can vary depending on the sales area.

Vallox

121

SE

OPERATING INSTRUCTIONS FOR CONTROL PANEL

3.3  

Choosing language version

Kieli / Language
English

The desired language is chosen with 

the + and – buttons.

3.4 

Adjusting time

Adjust time
Press + and -

You can adjust time by simultaneously 

pressing the + and – buttons. See se-

parate instructions in 4.2.

3.5  

Week programme programming

Adjust wk. prog.
Press + and -

To go to the week-clock programme 

programming mode press the + and – 

buttons simultaneously. See the instruc-

tions in 4.1.

3.6  

Erasing week programme

Erase wk. prog.
Press + and -

You can totally erase the week pro-

gramme by pressing the + and – but-

tons simultaneously.

3.7 

Choosing basic humidity level

Rh-level setting
automatic

The basic humidity level can be cho-

sen as either automatic or manual.
The selection is done with the + and 

– buttons.

3.8 

Basic humidity level setpoint

Basic %RH level
40%

The desired setpoint is chosen with the 

+ and – buttons when manual adjust-

ment has been selected as the Rh level 

setting (humidity setting, Section 3.7).

3.9 Changing setpoint for carbon dioxide adjustment

CO2 setting
0900 PPM

The setpoint for CO

2

 adjustment is cho-

sen with the + and – buttons.

3.10 

Adjustment interval

Adjust interval
10

The adjustment interval for humidity and 

carbon dioxide adjustments is selected 

with the + and – buttons. The adjust-

ment interval refers to minutes.

3.11 

Changing operating temperature of  

               heat recovery cell bypass

Cell bypass
10C

The desired cell bypass temperature 

is selected with the + and – buttons. If 

outdoor temperature is lower than cell 

bypass temperature, the summer/win-

ter damper is in the winter position.

3.12 

Mode of operation of fireplace/booster switch

Switch type
fireplace switch

The mode of operation of the switch 

(either fireplace or booster switch) is 

selected with the + and – buttons.

3.13 

Address of control panel

Panel address
1

The address of the control panel is 

changed with the + and – buttons. Two 

control panels cannot have the same 

address. If control panels have the 

same address, they go to bus fault state 

and do not work.

3.14 

Contrast of control panel display

Display contrast
05

The contrast setting for the control panel 

display is changed with the + and – 

buttons.

3.15  

Restoring factory settings

Factory settings
see manual

The general factory settings can be 

restored by pressing the + and – buttons 

simultaneously. Remember to ensure that 

the setpoints are in accordance with the 

factory settings for this unit. 

3.16 

Choosing cascade adjustment for supply air temperature

Cascade adjust
off

Cascade adjustment is chosen to be on 

or off with the + and – buttons.

3.17 

Choosing post-heating for the unit

Radiator type
Electric rad.

A water or electric radiator is selected 

with the + and – buttons, depending on 

the type of post-heating radiator the unit 

is equipped with.
Note! Choosing the wrong type of 

post-heating may cause a faulty post-

heating function.

3.18 

Choosing additional heater for unit

Extraheater type
MLV radiator

An electric or MLV radiator is chosen 

according to ventilation unit type with 

the + and – buttons. 

3.19 

MLV additional heater setpoint

MLV winter temp
0C

Changing MLV radiator setpoint. When 

outdoor air temperature goes below this 

setpoint, the ventilation unit starts the 

MLV pump. If a message “Preheating 

not in use” is displayed, no setpoint is 

in use.

3.20 

Choosing melting mode

Defrost mode
fan stop

Choose one of the two modes of mel-

ting to be used in the unit. Melting is 

done either by stopping the supply air 

fan or by bypassing the HR cell. This 

setting must not be changed.

3.21 

Winter parameter A

Winterparam. A

           

The winter function of the unit is adju-

sted from the menu when it is not too 

cold outside (warmer than –15 °C). 

Decreasing the value of the parameter 

increases the freezing of the HR cell. 

Increasing the value decreases the freezing of the HR cell. The unit ope-

rates optimally on the factory settings. There is no need to adjust this set-

point except in extreme problem situations, and even then it is advisable 

to contact Vallox Maintenance. The adjustment is made with the + and 

– buttons. See the table for the factory setting.

3.22 

Winter parameter B

Winterparam. B

           

The winter function of the unit is adju-

sted from the menu in very cold weat-

her (colder than –15 °C). Increasing 

the value of the parameter increases 

the freezing of the HR cell. 

Decreasing the value decreases the freezing of the HR cell. The unit 

operates optimally on the factory settings. There is no need to adjust this 

setpoint except in extreme problem situations, and even then it is advisab-

le to contact Vallox Maintenance. The adjustment is made with the + and 

– buttons. See the table for the factory setting.

3.23 

Setting base fan speed

MIN speed
1

The desired base fan speed (minimum 

fan speed) is chosen with the + and 

– buttons. Active when week-clock 

control is not on. Week-clock control 

changes this speed.

Summary of Contents for VALLOX 121 SE Series

Page 1: ...de A3560 Models VALLOX 121 SE R VALLOX 121 SE L Electrical connection 230 V 50 Hz 5 7 A Degree of protection provided by enclosures IP 34 Fans direct current Extract air 0 117 kW 0 9 A 106 dm3 s 100 Pa DC Supply air 0 117 kW 0 9 A 104 dm3 s 100 Pa Heat recovery Cross counter flow cell η 80 Heat recovery bypass Automatic Electric post heating unit standard 900 W 3 9 A Fans Supply air G4 and F7 Extr...

Page 2: ...ding to the highest measuring result 1 5 carbon dioxide sensors can be connected as options to the VALLOX 121 SE unit The adjustment is switched on off and if needed the setpoint 500 2000 ppm is set at the control panel The factory set ting is 900 ppm The recommended maximum carbon dioxide content in good indoor air is circa 1 000 ppm During control the control panel can be used to raise fan speed...

Page 3: ...amples of such situations are high humidity loads such as a swimming pool or a situation where the exhaust air duct has frozen through Remember Switch post heating off when it starts to get too warm in the dwelling because of warm weather Switch post heating on again when it gets cooler in autumn Post heating indicator light Maintenance reminder symbol Maintenance reminder The maintenance reminder...

Page 4: ...nu To settings menu see manual In order to move to the Settings menu press the and buttons simultaneous ly In the Settings menu you can chan ge setpoints for the ventilation unit 2 3 Week clock control Week program on Week clock control can be switched on with the button and off with the button Week clock control is on when the week clock control symbol is in the main display In week clock control...

Page 5: ...ctory settings can be restored by pressing the and buttons simultaneously Remember to ensure that the setpoints are in accordance with the factory settings for this unit 3 16 Choosing cascade adjustment for supply air temperature Cascade adjust off Cascade adjustment is chosen to be on or off with the and buttons 3 17 Choosing post heating for the unit Radiator type Electric rad A water or electri...

Page 6: ...fan speed 2 Sp 2 supply air temperature 17 C Temp 17 Move the cursor to the following hour Monday D 1 16 00 H 16 fan speed 4 Sp 4 supply air temperature 20 C Temp 20 Move the cursor to the following hour Monday D 1 19 00 H 19 fan speed 6 Sp 6 supply air temperature no change Temp N Move the cursor to the following hour Monday D 1 21 00 H 21 fan speed 4 Sp 4 supply air temperature no change Temp N ...

Page 7: ... by pulling carefully Place a thin sheet board or paper under the fan in order to prevent the bottom tank from being scratched when removing the fan Unfasten the fixing screw of the fan H hex socket head cap screw AV 4 mm and place the fan on the bottom tank Rotate the fan R model anticlockwise L model clockwise and slide the fan along the bottom tank Unfasten the quick couplings of the fan wires ...

Page 8: ...tes at speed 1 check the fan speed Wiring fault in the carbon dioxide sensor in the control panel or in the humidity sensor or the cable is of the wrong type Contact a maintenance company The connections have to be checked and corrected if necessary 9 Freezing alert message is displayed and the unit is stopped Antifreeze of the water circulating radiator is active NOTE If there is no non freezing ...

Page 9: ...ded operating range Volume flow rate Sound power level in supply air duct one duct by octave band LW dB Sound power level in extract air duct one duct by octave band LW dB ADJUSTMENT POSITION AIR FLOW dm3 s ADJUSTMENT POSITION AIR FLOW dm3 s Adjustment position 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 Air flow dm3 s 25 7 41 5 51 0 53 9 58 8 75 6 78 8 101 0 29 5 41 3 43 8 51 9 60 8 70 7 75 3 96 0 Medium fre...

Page 10: ...t R2 Post heating radiator M Damper motor 24 VAC Wire colours s blue m black r brown va white vi green p red h grey kv yellow green 16 V 0 V 0 V 230 V 7023500 2011 11 17 JK M1 GND A B PWM1 PWM2 S RH2 S RH1 L N NO NC 90 C 130 C R2 L N L r N N L L1 L2 L3 N1 L4 NC GND PWM 1 s s r r s s kv kv p p k k HK 0 10V DC A B M S S 1 2 S S RH1 RH2 12x0 25mm 3184600 PWM 2 r s s kv kv r r h h 5 10 3 1 NOL R r s T...

Page 11: ...ake sure that its address is 1 If control panels have the same address they go to bus fault state In this case remove one of the control panels and change the address of the other panel The above mentioned situation can arise in connection with the later installation of an additional control panel External electrical connection Vallox 121 SE code A3560 METAL M WHITE 2 B ORANGE 2 A WHITE 1 ORANGE 1...

Page 12: ...g water connections The delivery includes a Silent Kick water seal By connecting a pipe to the water seal the water condensing from extract air can be led to a floor drain not directly to the drain Silent Klick water seal prevents the sound caused by water as the water seal dries up The pipe must not rise after the water seal The condensation water discharge outlet is located at the rear edge in t...

Reviews: