OPERATING INSTRUCTIONS

Adjustment of supply air temperature 

and summer/winter function

The temperature of air coming to the dwelling can be adjusted 

between circa +10 °C and +30 °C. When there is a light on the 

post-heating indicator, post-heating is activated and the unit heats air 

as needed. The need for heating depends on the setpoint of supply 

air temperature. 
When there is no light on the post-heating indicator, post-heating is 

off. This means that summer function is activated for the ventilation 

unit. The unit has a motorised summer/winter function. When the 

summer function is on, the heat recovery cell is bypassed as soon 

as outdoor air temperature has risen above the setpoint. See the 

setpoint for cell bypass, factory s12 ºC. When outdoor air 

temperature goes below the setpoint (factory s12 °C), the unit 

starts to recover heat. If there is water-circulating post-heating in the 

unit, supply air fi nds the desired value very slowly. It takes hours for 

the unit to reach the correct setpoint. The amount of time depends on 

the temperature of the fl uid circulating in the post-heating radiator.
Two different kinds of supply air temperature adjustment can be 

chosen at the unit: constant temperature control or cascade control. 

In constant temperature control, the unit controls the temperature of 

supply air directly in accordance with the measurement information 

on  the  temperature  of  supply  air  blown  to  the  ventilation  area.  In 

cascade control, the unit controls supply air temperature according 

to the temperature of air extracted from the ventilation area. The unit 

calculates the difference between the air extracted and the setpoint 

for supply air and uses this difference to control the need for post-

heating.

Winter function of ventilation unit

A set of parameters has been set at the factory for the freezing of 

the heat recovery cell. When these parameters are undercut, the 

ventilation unit start to melt the heat recovery cell. Melting is done by 

stopping the supply air fan. A normal melting period takes from 15 to 

45 minutes depending on the extent of ice on the heat recovery cell 

and on the amount of extract air fl ow. The unit operates optimally on 

the factory settings in normal operation in dwellings and detached 

houses. The parameters only need to be touched in extreme problem 

situations. Examples of such situations are high humidity loads such 

as a swimming pool or a situation where the exhaust air duct has 

frozen through.

Remember!

Switch post-heating off when it starts to get too warm in the 

dwelling because of warm weather.

Switch post-heating on again when it gets cooler in autumn.

Post-heating indicator light

Maintenance reminder 

symbol

Maintenance reminder

•  The maintenance reminder switches on the maintenance re-

minder symbol ( ) in the control panel at defi ned intervals, 

the factory setting being 4 months.

•  The maintenance reminder symbol is reset at the main 

display of the control panel (see the operating instructions 

for the control panel, Section 3.1.).

•  The interval can be set between 1 and 15 months at the 

control panel.

Fireplace switch function/boosting

Fireplace switch function

•   The fi replace switch stops the extract air fan for 15 minutes and 

produces overpressure in the ventilation zone. This makes it 

easier to light a fi replace.

•   The function is started on the main display of the control panel 

by simultaneously pressing and holding down the + and - but-

tons for 2 seconds.

•   The function can also be started at a separate auto-reset push-

button switch, wired from the connection box of the unit for 

example to a wall in the fi replace room. Upon each pressing, 

the stopping function continues for 15 minutes (the switch is not 

included in the delivery).

•   During the function, the fi replace/booster switch symbol ( ) is 

visible in the main display of the control panel.

Boosting switch function

•   The booster switch function raises fan speed to the set maximum 

fan speed for 45 minutes.

The function is started on the main display of the control panel 

by simultaneously pressing and holding down the + and – but-

tons for 2 seconds.

•   The function can also be started at a separate auto-reset push-

button switch, wired from the connection box of the unit to 

for instance a wall in a classroom. Upon each pressing, the 

boosting function continues for 45 minutes.

•   During the function, the fi replace/booster switch symbol ( ) is 

visible in the main display of the control panel.

•   The function is chosen at the control panel.

Fireplace/

booster switch 

symbol

Fault signal relay (remote monitoring)

•   The fault signal relay has potential-free contacts (24 VDC, 

1 A).

•   The contacts provide information on various failure modes 

of the unit.

•   Alarm of high carbon dioxide content switches the relay at 

1-second intervals.

•   In other fault situations, the contacts are closed.

NOTE! The starting of 

the extract air fan may 

weaken draught in the 

fi replace! In winter, this 

situation may disturb 

the winter function of 

the unit. The situation 

will normalise in a 

while, after the fi replace 

function stops.

Summary of Contents for VALLOX 121 SE L

Page 1: ...de A3560 Models VALLOX 121 SE R VALLOX 121 SE L Electrical connection 230 V 50 Hz 5 7 A Degree of protection provided by enclosures IP 34 Fans direct current Extract air 0 117 kW 0 9 A 106 dm3 s 100 P...

Page 2: ...ing to the highest measuring result 1 5 carbon dioxide sensors can be connected as options to the VALLOX 121 SE unit The adjustment is switched on off and if needed the setpoint 500 2000 ppm is set at...

Page 3: ...ples of such situations are high humidity loads such as a swimming pool or a situation where the exhaust air duct has frozen through Remember Switch post heating off when it starts to get too warm in...

Page 4: ...u To settings menu see manual In order to move to the Settings menu press the and buttons simultaneous ly In the Settings menu you can chan ge setpoints for the ventilation unit 2 3 Week clock control...

Page 5: ...tory settings can be restored by pressing the and buttons simultaneously Remember to ensure that the setpoints are in accordance with the factory settings for this unit 3 16 Choosing cascade adjustmen...

Page 6: ...n speed 2 Sp 2 supply air temperature 17 C Temp 17 Move the cursor to the following hour Monday D 1 16 00 H 16 fan speed 4 Sp 4 supply air temperature 20 C Temp 20 Move the cursor to the following hou...

Page 7: ...by pulling carefully Place a thin sheet board or paper under the fan in order to prevent the bottom tank from being scratched when removing the fan Unfasten the fixing screw of the fan H hex socket he...

Page 8: ...es at speed 1 check the fan speed Wiring fault in the carbon dioxide sensor in the control panel or in the humidity sensor or the cable is of the wrong type Contact a maintenance company The connectio...

Page 9: ...ed operating range Volume flow rate Sound power level in supply air duct one duct by octave band LW dB Sound power level in extract air duct one duct by octave band LW dB ADJUSTMENT POSITION AIR FLOW...

Page 10: ...R2 Post heating radiator M Damper motor 24 VAC Wire colours s blue m black r brown va white vi green p red h grey kv yellow green 16 V 0 V 0 V 230 V 7023500 2011 11 17 JK M1 GND A B PWM1 PWM2 S RH2 S...

Page 11: ...ke sure that its address is 1 If control panels have the same address they go to bus fault state In this case remove one of the control panels and change the address of the other panel The above menti...

Page 12: ...water connections The delivery includes a Silent Kick water seal By connecting a pipe to the water seal the water condensing from extract air can be led to a floor drain not directly to the drain Sil...

Reviews: