background image

18

TECHNIC

AL SPECIFIC

ATIONS

Always follow first and foremost the connection diagram 

provided by the HVAC designer or heat pump manufacturer. 

Also read the duct radiator manual. 
The accompanying figure shows an example of the 

arrangement for connecting the heating/cooling radiator unit 

to the heat collection circuit.
Connect the radiator output pipe to the heat collection circuit 

return pipe. Direct the fluid returning from the radiator unit to 

the heat collection circuit return pipe. If you know that there 

is a large loss of internal pressure inside the heat pump, the 

heat pump should be bypassed. If this is done, the fluid circuit 

will come into operation when the heat pump comes to a halt. 

When this happens the pressure loss in the one-way bypass 

valve Y2 must be lower than the pressure loss in the heat 

pump.

Heating:

 The pump starts when the outdoor air temperature 

drops below the winter limit value set at the factory (-5 °C).

Cooling 

The supply air setpoint value for the active mode 

(for example, At home) controls the pump start-up. The pump 

starts when the supply air setting is below the temperature of 

the supply air that is blown into the apartment.
The duct radiator can be installed in both the supply air 

duct and the outdoor air duct. If the radiator is installed in 

the outdoor air duct, it can be used for both preheating and 

cooling. If the radiator is installed in the supply air duct, it can 

be used for heating or for cooling only. 

The duct radiator can be set to function either automatically 

or manually. 

•  Automatic

 - In summer, the supply air temperature will 

be maintained at the level specified in the temperature 

setting. In winter, the duct radiator will turn on, when the 

outdoor temperature falls below the winter setting.

•  Manual

 - In summer, the duct radiator will turn on, when 

the outdoor temperature rises above the summer setting. 

In winter, the duct radiator will turn on, when the outdoor 

temperature falls below the winter setting.

To prevent the risk of condensation in the supply air duct, you 

can set the adjustment of the supply air limit to automatic or 

manual. 

•  Automatic

 - The supply air limit is adjusted automatically 

based on the dew point of the extract air. When the supply 

air temperature falls too low, the duct radiator will turn off.  

•  Manual

 - The supply air limit can be set manually. When 

the supply air temperature falls down to the set value, the 

duct radiator will turn off.

If an external sensor is in use, it is selected from the settings of 

the external sensor whether it is used to control the outdoor air 

duct radiator or the supply air duct radiator. The temperature of 

the external sensor can be read from the service menu: 

menu >  

service menu > 

unit information page 5 ”

External sensor

”.

NOTE:

 If the duct 

radiator is used in 

the supply air duct, it 

can only be used for 

cooling. 

NOTE:

 When used to 

control the outdoor air 

duct radiator, the exter-

nal NTC sensor is ins-

talled in the outdoor air 

duct before the radiator. 

When used to control 

the supply air duct ra-

diator, the external NTC 

sensor is installed after 

the radiator.

NOTE:

When selecting the 

relay (C), take account 

of the maximum 

allowed combined 

power supply (6W) of 

the circuit board in the 

external MV electrical 

box, if the relay power 

supply comes from the 

circuit board’s +24V 

connector.

NOTE:

Due to the risk of humi-

dity damage, in a duct 

that has not been insu-

lated for condensation 

the supply air tempera-

ture must not fall below 

+16 … 20 °C.

DUCT RADIATOR OPERATION

Summary of Contents for Vallox 101 MV

Page 1: ...Manual Model Vallox 101 MV Type B3741 Document D5331 Valid from 31 08 2020 Updated 21 08 2020 Ventilation unit MANUAL ...

Page 2: ...e required by the alternative Vallox Silent Klick siphon installation method elbow 9 Measuring and adjusting the air flows of the ventilation unit 9 Dimensions and duct outlets 10 MAINTENANCE 11 Before beginning maintenance work 11 Changing the filters 11 Cleaning the heat recovery cell 12 Condensing water 12 Cleaning the fans 13 TECHNICAL SPECIFICATIONS 14 Internal electrical connection 15 Extern...

Page 3: ...cal installations and connections must be carried out only by an electrician and in compliance with local regulations GUARANTEE The guarantee and liability exclude damage resulting from Inappropriate use of the ventilation system or the control unit Incorrect or inappropriate installation setup or use Neglect of instructions concerning transportation installation use or maintenance Structural or e...

Page 4: ...n result in death or serious injury if not avoided IMPORTANT Indicates a hazard that can result in damage to property or loss of data if not avoided CAUTION Indicates a hazard that can result in minor or moderate injury if not avoided NOTE Indicates essential information about the product TIP Provides additional information about the use of the product and its benefits INTRODUCTION SYSTEM DESCRIPT...

Page 5: ...ows for controlling ventilation remotely also using e g a smartphone or tablet Also the unit software is updated automatically through the cloud service To connect to the cloud service the ventilation unit must be connected to the Internet via LAN and registered with the cloud service At the same time you create a MyVallox Cloud account for yourself Read more about the service at www myvallox com ...

Page 6: ... figure MAIN PARTS Post heatingresistor in the supply air duct 8 Safety switch 9 Internal carbon dioxide and humidity sensor 10 Control panel 11 Carbon dioxide sensor optional 12 Humidity sensor optional 13 VOC sensor Optional 14 Ceiling bushing for electric wires 15 INTRODUCTION 1 5 3 6 8 9 10 7 2 4 13 12 11 14 15 A NNUAL EFFICIENCY R A T I N G O F E X T R A C T A I R H E A T R E C O V E R Y A ...

Page 7: ...his determines the position of the unit The top edge of the white covering strip of the ceiling mounting plate can be installed against the ceiling Alternatively a concealed mounting method can be used in which case the ceiling can be 30 mm below the top of the white covering strip Insulate the ducts against condensation also between the unit and the ceiling mounting plate Mounting the ceiling mou...

Page 8: ...ox can be accessed The distance between the service door and the ceiling mounting plate must be around 500 mm Alternatively the cables can be fed between the ceiling mounting plate and the ventilation unit to the rear wall When the ventilation unit is lifted against the ceiling mounting plate the unit locks in place Where needed guide the mounting hooks on the ceiling mounting plate B to the groov...

Page 9: ...ring tubes These can be inserted in the ducts to allow for easier ventilation adjustment NOTE The Vallox Silent Klick siphon package is delivered with the unit Installation instructions for the siphon are enclosed with the packaging and can also be found online at www vallox com When the alternative siphon installation method is used the ring seal and the locking part must be moved to the pipe con...

Page 10: ...eating resistor in the supply air duct 9 Safety switch 10 Internal humidity and carbon dioxide sensor Dimensions and duct outlets Dimensions Duct outlets R model Inner diameter of the female collar 125mm 1 Supply air from the unit to the apartment 2 Extract air from the apartment to the unit 3 Exhaust air flowing outdoors from the unit 4 Outdoor air to the unit L model Inner diameter of the female...

Page 11: ...overy cell clean The filter replacement interval depends on the ambient particle concentration It is recommended that the filters be replaced every spring and autumn or at the very least once a year To replace the filters 1 Disconnect the ventilation unit from the mains electricity supply 2 Open door of the Vallox ventilation unit by undoing the finger screws 3 Lift the door off 4 Remove the old f...

Page 12: ...trip E in place so that the strip is supported by the corner bracket G at the rear 13 Install the extract air filter C in place 14 Close the door Ensure that the safety switch catch of the door is touching the safety switch 15 Plug the ventilation unit back into the mains The heat recovery cell has now been checked and cleaned MAINTENANCE IMPORTANT If the unit has an enthalpy cell it must not be w...

Page 13: ...n the fans J 3 screws per fan Undo the mounting screws K 3 screws of the air flow control grille of the extract air fan and remove the grille 8 Remove the fan from the unit by pulling it forward and by tilting it slightly backwards at the same time 9 Remove the mounting screws K 3 screws of the air flow control grille of the supply air fan and remove the grille You can now clean the fan Put the co...

Page 14: ...dm s 15 24 34 42 51 62 69 77 83 23 31 41 50 60 70 78 86 92 Air flow m h 54 86 122 151 184 223 248 277 299 83 112 148 180 216 252 281 310 331 Medium frequency of the octave band Hz 63 62 64 69 73 77 82 84 87 88 54 55 62 66 69 75 78 79 80 125 53 63 65 65 67 71 74 76 78 46 50 53 56 59 62 65 67 68 250 48 56 60 65 70 71 73 75 75 39 45 51 55 60 59 61 62 64 500 43 49 56 60 64 67 69 71 73 29 35 40 44 47 5...

Page 15: ...signal RS_B Local hardware Modbus B signal NTC External temperature sensor connector D I1 Digital input 1 D I2 Digital input 2 11V1 11 1 V operating voltage AN I Analog input 0 10VDC RM I 24V relay input RM O 24V relay output T Supply air fan P Extract air fan M Damper motor TK Safety switch AHS Post heating control RH Internal humidity sensor RH CO2 Internal humidity and carbon dioxide sensor R1 ...

Page 16: ...put EXTERNAL ELECTRICAL CONNECTION 3x1 5S 2x2x0 5 0 5 2x0 5 2x0 5 7028350 2014 08 29 JS 2x2x0 5 0 5 2x0 5 2x2x0 5 0 5 2x2x0 5 0 5 2x2x0 5 0 5 2x0 5 2x0 5 CAT Analog input two different functions Potential free contact data 24VDC can be programmed to display information such as errors or to control the valve and pump of the MLV radiator Plug connection 1 2 m on top of the unit MyVallox Control MyVa...

Page 17: ...ard MLV control External temperature sensor NTC 4K7 MB_A External Modbus A signal MB_B External Modbus B signal 24V 24V voltage DC GND Digital and analog ground potential RS_A Local hardware Modbus A signal RS_B Local hardware Modbus B signal NTC External temperature sensor connector D I1 Digital input 1 D I2 Digital input 2 11V1 11 1 V operating voltage AN I Analog input 0 10VDC RM I 24V relay in...

Page 18: ...rature setting In winter the duct radiator will turn on when the outdoor temperature falls below the winter setting Manual In summer the duct radiator will turn on when the outdoor temperature rises above the summer setting In winter the duct radiator will turn on when the outdoor temperature falls below the winter setting To prevent the risk of condensation in the supply air duct you can set the ...

Page 19: ...lve Not included in the delivery The valve that is chosen must be compatible with the heat collection circuit fluid for example ELV05006 Stig Wahlström K Condensing water tube Not included in the delivery IP De aerator Not included in the delivery S External electrical junction box for the MV N External NTC sensor for Vallox MV ventilation units C 24 VDC relay contactor for controlling the pump an...

Page 20: ...nt Klick 3494701 14 Door 4102334 24 MyVallox humidity sensor optional 946149 5 Coarse and fine filter for supply air 978225 15 Mounting screw of the door 990712 25 MyVallox carbon dioxide sensor optional 949111 6 HR cell 933260 16 Motherboard 949032 1 26 MyVallox VOC sensor optional 949112 7 Lower support for HR cell 4102504 17 Safety switch 948370 27 Supply air filter frame 4108194 8 Upper suppor...

Page 21: ...CONFORMITY CERTIFICATES ...

Page 22: ...22 ...

Page 23: ...23 Vallox Oy All rights reserved ...

Page 24: ...D5331 12 08 2020FIN 21 08 2020ENG PDF www vallox com Vallox Oy Myllykyläntie 9 11 32200 LOIMAA FINLAND Customer service 358 10 7732 200 Aftersales 358 10 7732 270 ...

Reviews: