Vallox 252 M Manual Download Page 17

VALLOX 252 M

MOUNTING INSTRUCTIONS

17

VALLOXs Electrical Connections

• The unit is connected permanently to the electrical power network. The connection

box is located inside the unit, next to the extract air duct outlet.

• The cables to be connected are led to the unit through the sleeves with draught-

limiters and the cable sleeves located beside the extract air duct outlet.

Mounting

• Detach the upper door of the unit (screw M8x70, 5 pcs).
• Detach the cover of the connection box (screw 3.5x9.5, 2 pcs).
• Mount and fasten the cables needed to the terminal block following the connection

instructions.

• The external wiring diagram is included in these instructions, and it is also found

inside the cover of the connection box.

• The internal wiring diagram is included in these instructions, and it is also found on

the cover of the fuse box inside the unit.

Installation of the Manual Control Unit

• The control panel that comes with the unit is in a surface mounting case. The

manual control unit can also be flush mounted in a double gang box (U 17.2
ENSTO).

• The manual control unit cannot be used in connection with remote monitoring

control.

Connection to Remote Monitoring

• The ventilation unit is connected to remote monitoring according to the wiring

diagrams attached.

• The manual control unit cannot be used in connection with remote monitoring control.

Selection of Control Voltages for Capacity Modes (Min., 1/2 and Max.)

BEFORE SELECTING CONTROL VOLTAGES, MAKE SURE THAT THE UNIT HAS BEEN DISCONNECTED
FROM THE MAINS SUPPLY!

• If needed, the factory settings for adjusting fan capacity modes (Min., 1/2 and

Max.) can be modified.

• The factory setting for the Min. mode control voltage is 90V. You can modify the

control voltage by moving the conductor between contact 13 of the K2 contactor
and the transformer to the desired voltage (100V, 110V, 130V, 140V, 160V,
200V, and 230V).

• The factory setting for the 1/2 mode control voltage is 140V. You can change the

control voltage by moving the conductor between contact 14 of the K3 contactor
and the transformer to the desired voltage (90V, 100V, 110V, 130V, 160V,
200V, and 230V).

• The factory setting for the Max. mode control voltage is 230V. You can change the

control voltage by moving the conductor between contact 13 of the K1 contactor
and the transformer to the desired voltage (90V, 100V, 110V, 130V, 140V,
160V, and 200V).

ONLY AN AUTHORIZED PERSON MAY PERFORM
ELECTRICAL CONNECTIONS!

BEFORE CONNECTING THE CABLES, MAKE SURE
THAT THEY HAVE BEEN DISCONNECTED FROM THE
MAINS SUPPLY!

FEEDER CABLE
• Distribution panel

CONNECTION CABLE
• Remote monitoring
• Manual control
CONNECTION CABLE
• Duct damper motor

OUTDOOR

AIR TO THE

UNIT

EXTRACT AIR

GOING OUT

SUPPLY AIR

FROM THE

UNIT

DISCHARGE

AIR TO THE

UNIT

SUPPLY WATER
TO THE
RADIATOR

VALLOX 252 M-L

ELECTRICAL
CONNECETIONS

RETURN WATER
FROM THE
 RADIATOR

Manual control unit

Summary of Contents for 252 M

Page 1: ...charge air 210 dm3 s 100 Pa 230 dm3 s 100 Pa 2 heat recovery cells 70 Manual or remote monitoring control 2 5 kW 11 A 2 5 kW 11 A Approx 5kW EU 3 EU 7 EU 3 EU 5 210 kg 2x230 W 1 A 2x230 W 1 A Fans Hea...

Page 2: ...tarts when outdoor air temperature falls below ca 5 C VALLOX 252 M can be operated with the manual cont rol unit contained in the delivery With the manual control unit you can select the min or max ve...

Page 3: ...8 Fan speeds 90 100 110 130 140 160 200 230 Control voltage V 200 230 275 350 390 450 590 675 Input power W 3 1 2 3 4 5 6 7 8 90 100 110 130 140 160 200 230 200 230 275 350 390 450 590 675 74 85 99 1...

Page 4: ...OW Sound power level from VALLOX to discharge air ducts by octave band Lw dB CONTROL POSITION AIR FLOW Medium frequency of the octave band Hz Sound power level coming from VALLOX through the envelope...

Page 5: ...ntering the radiator tv 55 C Temperature of air entering the radiator ti 15 C Cooling of water in the radiator C Water flow dm3 s Total output of the radiator kW Cooling of water in the radiator C Wat...

Page 6: ...OL 2 6 Control Diagram VALLOX 252 M MANUAL CONTROL UNIT Distribution Panel 2x16A if equipped with a preheater Internal electrical and control connections Post heating unit electric Preheater electric...

Page 7: ...entilation zone Supply Air Temperature The control adjustment center of the unit directs the operation of the post heating unit LP2 on the basis of the measuring data on the sensor of the TS2 temperat...

Page 8: ...L CONTROL UNIT 2 8 Control Diagram VALLOX 252 M VKL MANUAL CONTROL UNIT Distribution Internal electrical and control connections Post heating unit water circulation Preheater electric Sound attenuator...

Page 9: ...ir Temperature A regulating valve not included in the VALLOX 252 M delivery directs the operation of the LP2 post heating unit on the basis of the measurement data given by the thermostat sensor in th...

Page 10: ...CONTROL Distribution Panel Internal electrical and control connections Post heating unit electric Preheater electric VENTILATION ZONE 2x16A if equipped with a preheater Pressure unit Pressure unit Sou...

Page 11: ...ccording to the control signal 24VAC received by the Min 1 2 and Max contacts in the connection box Remote monitoring receives potential free operation mo de information on the mode selected Min 1 2 M...

Page 12: ...L MANUAL CONTROL UNIT Distribution Panel Internal electrical and control connections Post heating unit water Preheating electric Ventilation zone Pressure switch REMOTE MONITORING CONTROL CENTER OF TH...

Page 13: ...l 24VAC received by the Min 1 2 and Max contacts in the connection box Remote monitoring receives potential free operation mo de information on the mode selected Min 1 2 Max Supply Air Temperature A r...

Page 14: ...he unit is equipped with an adjustable socle If the unit is mounted on a wall keep in mind the weight of the unit 190kg and vibration damping The unit is splash proof IP34 so it can also be mounted in...

Page 15: ...enuator unit also features detachable attenuation segments in supply and discharge air ducts 4 250 external fittings enable the laying of ducts straight from the unit by using bends etc The top of the...

Page 16: ...to be connected through the lead through tubes to the connection box inside VALLOX 252 If a water heating unit is used lead the supply and return pipes not included in the delivery of the heating uni...

Page 17: ...ith remote monitoring control Selection of Control Voltages for Capacity Modes Min 1 2 and Max BEFORE SELECTING CONTROL VOLTAGES MAKE SURE THAT THE UNIT HAS BEEN DISCONNECTED FROM THE MAINS SUPPLY If...

Page 18: ...al reset PDS1 Supply air duct pressure difference switch optional PDS2 Discharge air duct pressure difference switch optional F1 Fuse 4A F2 Fuse 1 6A TF Supply air fan 2x230W PF Discharge air fan 2x23...

Page 19: ...with a PREHEATER and a POST HEATING UNIT WITH WATER CIRCULATION the L1 and L on the terminal block are connected In this case THE PREHEATER DOES NOT NEED a separate power supply NOTE When the VALLOX...

Page 20: ...n on the 1 2 mode Operation mode information on the Max mode Operation mode information from the pressure difference switch Operation mode information from Pos 1 discharge air duct Entering operation...

Reviews: