VALLOX 252 D

MOUNTING OF CONTROL PANELS AND SENSORS

2

12

VALLOX electrical connections

• The unit is connected permanently to the distribution network. The connection box

is located inside the unit, next to the exhaust air duct outlet.

• The cables to be connected are led to the unit through the cable glands with

draught-limiters and the cable sleeves located beside the exhaust air duct outlet.

Mounting

• Detach the upper door of the unit (screw M8x70.5 pcs).
• Detach the cover of the connection box (screw 3.5x9.5, 2 pcs).
• Mount and connect the cables needed to the terminal block following the

connection instructions.

• The external wiring diagram is included in these instructions, and it is also found

inside the cover of the connection box.

• The internal wiring diagram is included in these instructions, and it is also found

on the cover of the fuse box inside the unit.

Control panel addresses

If two or more control panels are connected to the system, the addresses of the
control panels have to be changed. (See Section 1.3.9 in the instructions for use
and maintenance.)

For example 3 control panels.

• Connect the first control panel to the unit and change its address to 3.
• Connect the second control panel to the unit and change its address to 2.
• Connect the third control panel and check to see if its address is 1.

If control panels have the same address, they go to bus fault state. In this case, remove one of the
control panels and change the address of the other panel. The above mentioned situation can arise in
connection with the later installation of an additional control panel.

The control panel is wired directly from the VALLOX 252D connection box. The
control panel can also be wired serially with a CO

2

 sensor or another control

panel (see the external electrical diagram, page 16).

ONLY AN AUTHORIZED PERSON MAY PERFORM
ELECTRICAL CONNECTIONS!

BEFORE CONNECTING THE CABLES, MAKE SURE
THAT THEY HAVE BEEN DISCONNECTED FROM THE
MAINS SUPPLY!

FEEDER CABLE

DISTRIBUTION PANEL

ELECTRICAL

CONNECTIONS

• HUMIDITY SENSOR

CONNECTION CABLE

• CONTROL PANEL

• CO

2

 SENSOR

• LON CONTROLLER

EXHAUST

AIR GOING OUT

OUTDOOR

AIR TO THE

UNIT

SUPPLY AIR

FROM

THE UNIT

EXTRACT

AIR TO

THE UNIT

SUPPLY WATER

TO THE RADIATOR

VALLOX 252 D-L

electrical connections

RETURN WATER

FROM THE RADIATOR

Surface mounting of a controlpanel

A control panel is mounted on
the wall or on a 1-part
instrument box.

Wiring

Width 90 

mm

Height

110 mm

Depth

23 mm

Control panel electronics board

1 = orange 1 

= +

2 = white 1 

= –

3 = orange 2

= A

4 = white 2

= B

5 = metal

signal ground

ca. 21 VDC

}

Cable: 
NOMAK 2 x 2 x 0.5 mm

2

 + 0.5 mm

2

NOTE!

Faulty coupling of the (+) wire destroys
the control panel!

1   2   3   4   5

+   –   A   B   M

Mounting the control panel

• The control panel comes in a surface-mount box. The control panel can be

mounted on the instrument box or on the wall.

• Connect the control panel as stated in the connection instructions for VALLOX

252 D.

Connection cable type for instance NOMAK 2 x 2 x 0.5mm

2

+0.5mm

2

.

Note! If two or more control panels are mounted, they are connected serially, and they have to be
given different addresses.

Summary of Contents for 252 D-L

Page 1: ...2 5kW 11A ca 5kW EU3 EU7 EU3 EU5 2x230W 1 A 2x230W 1 A Fans Heat recovery Heat recovery bypass Preheater Electric post heating unit Water circulated post heating unit Filters Filters Manual control D...

Page 2: ...recovery most of the heat of contaminated extract air can be transmitted to outdoor air coming inside The efficiency of the heat recovery cells is approx 70 or 75 80 if supply air fan heat is taken i...

Page 3: ...collar HRC Heat Recovery Cell Fan curves indicate the total pressure available for duct losses 3 1 2 3 4 5 6 7 8 90 100 110 130 140 160 200 230 200 230 275 350 390 450 590 675 74 85 99 127 143 170 20...

Page 4: ...OSITION AIR FLOW l s LpA dB A Sound power level from VALLOX to supply air ducts by octave band Lw dB Sound power level from VALLOX to extract air ducts by octave band Lw dB Sound power level coming fr...

Page 5: ...ater entering the radiator tv 55 C Temperature of air entering the radiator ti 15 C Cooling of water in the radiator C Water flow dm3 s Total radiator capacity kW Air flow dm3 s Total pressure loss kP...

Page 6: ...ions TE3 EU 3 VALLOX 252 D TZ2 LP2 Pressure difference switch EU 5 TE2 Post heating unit electric CONVERTER LON Distribution panel 230 V 16 A RH CO 2 sensor max 5 pcs Control panel max 3 pcs Humidity...

Page 7: ...erheating protection of the heating unit The overheat protection thermostats TZ1 and TZ2 monitor the surface temperature in the LP1 and LP2 heating units If surface temperature exceeds the threshold o...

Page 8: ...H 1 RH 2 TE4 SV Ljp Ljm EU 5 S TE1 CO 2 sensor max 5 pcs Control panel max 3 pcs Humidity sensor Booster switch Fireplace switch ALARM RUNNING MODE CONTROL MEASUREMENT REGULATION REMOTE MONITORING CEN...

Page 9: ...tifreeze protection of the water radiator On the basis of the measuring data of the outdoor air temperature sensor TE3 outdoor air 0 C and of the supply air temperature sensor TE2 supply air 7 C the c...

Page 10: ...n two ways When extract air humidity is great as in the bathroom the condensing water is led via a screw type hose coupling and through the condensing water outlet water seal and hose delivered with t...

Page 11: ...ift the silencer unit on top of VALLOX 252 Make sure that the cable sleeves go through See the figure item D Mount the lead through cable tubes included in the delivery pushing them through the lead i...

Page 12: ...one of the control panels and change the address of the other panel The above mentioned situation can arise in connection with the later installation of an additional control panel The control panel...

Page 13: ...5 mm2 CO2 sensor bottom panel CO2 sensor electronics board NOTE Faulty coupling of the wire destroys the carbon dioxide sensor 14 125 38 76 Carbon dioxide sensors Connect the carbon dioxide sensors on...

Page 14: ...on box Humidity sensors Connect any humidity sensors to the terminal board in the connection box by connec ting the first RH sensor in RH1 in place of the 6K8 resistor remove the resistor in this case...

Page 15: ...ormer 230V 4A 24V 25VA C Capacitor 6 F H1 Interference suppressor motherboard H2 Interference suppressor motherboard FG Damper motor 24V TE Temperature sensors R3 Auxiliary resistor 4 7kOhm R4 Auxilia...

Page 16: ...TER CIRCULATION the L1 and L on the terminal block are connected In this case THE PREHEATER DOES NOT NEED a separate power supply NOTE When the VALLOX 252 D unit is equipped with a PREHEATER and an EL...

Reviews: