background image

Y2

MV

M

P

R

R

IP

R

Y

Circulation pump (not included in the delivery)
Because of the risk of condensing the pump should be suitable

for pumping liquid that is colder than the ambient temperature

(e.g. Magna1 25-60). When choosing a circulation pump, take

into account the pressure loss in the whole system.

MV  Solenoid valve (not included in the delivery)

The valve has to be suitable for the liquid in the ground collector

(for example ELV05006, Stig Wahlström).

Non-return valve (not included in the delivery)

Stop valve (not included in the delivery)

IP  Air bleeder (not included in the delivery)

Air bleeder is placed after the pump and at the highest point in

the network.

Y2  Non-return valve (not included in the delivery)

The pressure loss of the valve has to be lower than that of the

heat pump.

When the requirements for starting the heating or cooling function are met, the control function of the unit opens the solenoid valve (MV) and starts the pump (P).  The components of the MLV circuit
mentioned in the diagram are not included in the delivery. Observe the freeze resistance of the liquid used in the ground collector.  The connection pipes of the MLV radiator have to insulated against
condensation. 

If the heat pump has an open expansion tank, it must be situated at the highest point of the network.

Note! Because of the risk of humidity damage, supply air temperature in a duct with no condensation insulation should not go below +16...20 

°

C.

ALWAYS PRIMARILY FOLLOW THE CONNECTION PLAN PREPARED
BY THE HVAC PLANNER OR THE HEAT PUMP MANUFACTURER.

See the adjoining example of connecting an MLV unit to the ground collector.  The supply pipe of the MLV circuit is connected to the pipe
returning from the collector. The liquid returning from the MLV circuit is taken to the return pipe of the ground collector.If the internal
pressure losses of the heat pump in the ground collector are known to be high, it is recommended to bypass the heat pump. The liquid then circulates
when the heat pump is stopped. In this case the pressure loss of the bypass non-return valve (Y2) has to be lower than that of the heat pump.

RADIATOR HEATING

HEAT PUMP

UNDERFLOOR HEATING

Heating water

adjustment

T

MV

Y2

P

R

R

IP

R

PATTERILÄMMITYS

S

S

M

E

Y

It is sometimes convenient to connect the unit directly into the heating network. The connection involves a risk of freezing for the radiator although efforts have been made in the unit to minimise the risk of
freezing of the radiator. The unit stops if supply air temperature goes below the set temperature and automatically starts as soon as temperature rises above the value set. The unit also issues an alarm of
freezing risk at the controller.
It is recommended to have e.g. a spring-actuated check valve (E) in the outdoor air duct (and possibly also in the exhaust air duct). This valve closes the duct from the unit to outdoor air and prevents cold air
from flowing into the unit while it is stopped The base volume of water flow into the radiator of the unit can be adjusted with valves (S), which can also act as stop valves. No water must be led into the radiator
of the unit until the system has been adjusted for operation and heating is on in the heating network, or other measures have been taken to ensure that the radiator will not freeze. Water circulation in the
heating network connected to the unit and the circulation pump must not be stopped during the heating season. With the exception of valve (T), the components of the VKL circuit mentioned in the diagram
are not included in the delivery.

VKL post-heating radiator connection
Sample connection: Direct connection to underfloor heating or radiator network

When the requirements for starting the heating or cooling function are met, the control function of the unit opens the solenoid valve (MV) and starts the pump (P).  The components of the MLV circuit
mentioned in the diagram are not included in the delivery. Observe the freeze resistance of the liquid used in the ground collector.  The connection pipes of the MLV radiator have to insulated against
condensation. 

If the heat pump has an open expansion tank, it must be situated at the highest point of the network.

Note! Because of the risk of humidity damage, supply air temperature in a duct with no condensation insulation should not go below +16...20 

°

C.

ALWAYS PRIMARILY FOLLOW THE CONNECTION PLAN PREPARED
BY THE HVAC PLANNER OR THE HEAT PUMP MANUFACTURER.

See the adjoining example of connecting an MLV unit to the ground collector.  The supply pipe of the MLV circuit is connected to the pipe
returning from the collector. The liquid returning from the MLV circuit is taken to the return pipe of the ground collector.If the internal
pressure losses of the heat pump in the ground collector are known to be high, it is recommended to bypass the heat pump. The liquid then circulates
when the heat pump is stopped. In this case the pressure loss of the bypass non-return valve (Y2) has to be lower than that of the heat pump.

© Vallox • We reserve the right to make changes without prior notification.
What the units include can vary depending on the sales area.

VALLOX 200SE

18

RADIATOR CONNECTIONS

P  Circulation pump, not included in the delivery. Because

of the risk of condensing, the pump should be suitable
for pumping liquid colder than the ambient
temperature (e.g. Grundfos MAGNA 1 25-80).

MV  Solenoid valve, not included in the delivery. The valve

has to be suitable for the liquid in the ground collector
(e.g. ELV05006, Stig Wahlström).

Y  Non-return valve, not included in the delivery.
R  Stop valve, not included in the delivery.
S  Control valve, not included in the delivery.
IP  Air bleeder, not included in the delivery. Is placed after

the pump and at the highest point in the network.

T  Two-way control valve, included in the unit delivery.
E  Spring-actuated check valve, not included in the

delivery.

Y2  Non-return valve (not included in the delivery)

The pressure loss of the valve has to be lower than that

of the heat pump.

HEAT PUMP

GROUND COLLECTOR

Connection of MLV preheating/cooling radiator
to the ground collector of ground-source heat pump

Summary of Contents for 200 SE L

Page 1: ...tems MODELS Vallox 200 SE L Vallox 200 SE R 1 09 280b E 26 10 2014 Code 3486 Vallox Input power 230 V 50 Hz 15 2 A Class of protection IP34 Fans Extract air 2 x 117 W 0 9 A 220 dm3 s 100 Pa Supply air...

Page 2: ...r air filter G4 Condensing water outlet Electrical connection lead ins Control panel Measurement outlets behind the cover strip 1 2 3 5 6 4 7 8 9 10 10 11 124 MODEL L 215 215 222 124 720 160 183 183 O...

Page 3: ...AIR FLOW ADJUSTMENT POSITION AIR FLOWS supply extract A weighted sound pressure level dB A coming from the unit through the envelope to the rooms where the unit has been installed 10 m2 sound absorpti...

Page 4: ...ng from the unit through the envelope to the rooms where the unit has been installed 10 m2 sound absorption VALLOX 200SE PERFORMANCE WITH SILENCER UNIT 2 4 63 125 250 500 1000 2000 4000 8000 Lw dB LwA...

Page 5: ...g with a voltage signal In case of disturbances a potential free relay contact signal is issued With an optional Vallox LON converter the whole operation of the unit can be controlled via remote monit...

Page 6: ...f humidity sensors are used connect them to the terminal block of the con nection box by connecting the first hu midity sensor to RH1 in place of the 6K8 resistor in the terminal block re move the res...

Page 7: ...PRESSURE DIFFERENCE SWITCH FOR THE EXTRACT AIR DUCTWORK OPTION H U3 N4 L2 S PWM L3 L4 N PWM L5 RD YE L PDS K GND 1 2 SV TE 4 EXTRACT AIR TE 3 OUTDOOR AIR TE 2 SUPPLY AIR TE 1 WASTE AIR HEAT RECOVERY C...

Page 8: ...ge signal 0 10 VDC A M PDS 20 RH 1 RH 1 S RH 2 S RH 2 19 REMOTE MONITORING additional control option 14 DISTRIBUTION PANEL VAK S 18 16 VAK GND 17 15 13 8 A 10 11 12 M B 9 7 6 LON Converter Option R 6K...

Page 9: ...r fan operation Clogging of the supply extract air filters and of the ductwork can be monitored by equipping the unit with a pressure difference switch Heat recovery and heating With efficient heat re...

Page 10: ...m3 s Water flow 160 dm3 s 120 dm3 s 80 dm3 s Air flow Temperature of air coming to the radiator ta1 15 C Temperature of water coming to the radiator tf1 70 C Total power of radiator kW 0 100 dm3 s 0 0...

Page 11: ...include can vary depending on the sales area VALLOX 200SE 11 HEATING VKL WATER RADIATOR VKL WATER RADIATOR PRESSURE LOSS IN WATER CIRCULATION Defined for 100 water Water flow Total pressure loss kPa d...

Page 12: ...pped with an electric post heating unit Equipped with a water circulating post heating unit 12 CONTROL DIAGRAM electric preheating unit PREHEATING UNIT LP1 ELECTRIC TZ1 TZ2 M TF PDS2 HR TE1 PDS1 INTER...

Page 13: ...erature control The control unit directs the operation of post heating unit LP2 on the basis of the measurement data given by temperature sensor TE2 aiming at keeping supply air temperature at the tem...

Page 14: ...NTERNAL ELECTRICAL AND CONTROL CONNECTIONS PRESSURE DIFFERENCE SWITCH LON CONVERTER DISTRIBUTION PANEL CARBON DIOXIDE SENSOR 5 AT MOST CONTROL PANEL 3 AT MOST HUMIDITY SENSOR 2 AT MOST VENTILATION ZON...

Page 15: ...ost heating unit LP2 on the basis of the measurement data given by temperature sensor TE2 aiming at keeping supply air temperature at the temperature value set on control panel H 10 30 C The cooling f...

Page 16: ...3 5 x 9 5 Mount and connect the needed cables to the screwed terminal block as specified in the connection instructions The external connection diagram is shown in these instructions and inside the co...

Page 17: ...rmation on adjustments see the instructions for using the unit Condensing water connections Water condensing from extract air going through the unit can be removed from the bottom tank in two ways Whe...

Page 18: ...lume of water flow into the radiator of the unit can be adjusted with valves S which can also act as stop valves No water must be led into the radiator of the unit until the system has been adjusted f...

Page 19: ...without prior notification What the units include can vary depending on the sales area VALLOX 200SE 19 RADIATOR CONNECTIONS Connection of mlv preheating cooling radiator The radiator is connected to...

Page 20: ...connection See the adjoining figure Lift the unit on top of Vallox 200 SE See the adjoining figure Mount the lead in pipes included in the delivery for cables in place by pushing them first through th...

Reviews: