background image

Outdoor air coming to
the dwelling is cold.

SYMPTOM

REASON

DO THIS

• Air cools down in the attic ducts.

•  The heat recovery cell is frozen, which is

why extract air cannot heat outdoor air.

•  The post-heating radiator does not work.

•  The extract air filter or cell is clogged.

•  The initial adjustment of ventilation has not

been done.

1

• Measure the temperature of supply air in the unit and com-

pare it with the air coming from the valve.

• Check the insulation of the attic ducts.

• If the heat recovery cell is frozen, check the setpoints for

heat recovery cell freeze protection and preheating (see
Section 2.4.). The setpoint for freezing protection can be
raised by 1 or 2 

°

C, or the sensor can be bent closer to the

cell, in which case the supply air fan stops earlier. Thaw the
cell before closing the door.

• If the post-heating radiator does not operate, check to see if

overheat protection prevents it from operating: press the
black button at the end of the radiator. If the protector has
tripped, you hear a click when pressing the button. Pressing
the button resets the radiator in working order after the
tripping of the overheat protector.

• Consult an expert to find out why the overheat protector

tripped.

• Check that the filters and the heat recovery cell are clean.

• Check the initial adjustment.

Supply air fan keeps
stopping.

•  The stopping of the supply air filter is

active.

2

• The fan stops more rarely and the efficiency of the heat

recovery cell gets better when the setpoint is decreased by
1 or 2 

°

C.

NOTE! If you decrease the setpoint too much, the cell may freeze.
 Compare with list item 1.

Supply air fan stops and
starts too frequently.

•  The difference between the stopping and

starting temperatures is too small.

•  The preheating radiator does not work.

3

• Raise the difference between the stopping and starting tem-

peratures by 1 or 2 

°

C. It extends the period between the

stopping and starting of the supply air fan.

• If the (electric) preheating radiator does not function, check

if overheat protection prevents it from operating: press the
black button at the end of the radiator. Also check whether
the preheating radiator has been taken into use and adju-
sted correctly.

• If the radiator does still not work, i.e. the fan does not stop

more rarely, contact a maintenance company.

VKL unit has stopped.

• Antifreeze of the water-circulating radiator

is active.

NOTE! If there is no non-freezing solution in the water
of the radiator, the radiator is at risk of freezing and
breaking down. If the radiator breaks down, there is a
risk of water damage.

4

•  Immediately troubleshoot the situation. Check if the

circulation pump is broken, the boiler out of operation etc.
The situation may pass by itself as soon as supply air
temperature exceeds 10 

°

C, but do not wait till it happens.

Filter guard indicator is lit
and the unit operates
otherwise normally.

•  The pressure in the filter guard (pressure

difference switch) has risen above the
adjustment value or fan speed is 3 or 4.

5

• If fan speed is 3 or 4, no maintenance activities are needed.

• If fan speed is 1 or 2, check the cleanliness of the filters and

the unit, and clean or replace the filters if needed. Also
check the external grille.

11

TROUBLESHOOTING

VALLOX 132 E/VKL

© VALLOX • We reserve the right to make changes without prior notification

Summary of Contents for 132 E Series

Page 1: ...1 09 410E 29 1 2010 Code 3550 E VALLOX INSTRUCTIONS FOR USE AND MAINTENANCE MODELS VALLOX 132 E VALLOX 132 E VKL VALLOX We reserve the right to make changes without prior notification Vallox E 132...

Page 2: ...hood VALLOX 1302 E has been initially adjusted for normal circumstances in your home Ventilation adjustment is needed mainly in the following circumstances VALLOX 132 E models Code 3550 E Models Vallo...

Page 3: ...1 2 What are the characteristics of adequate ventilation Indoor air stays fresh in all the rooms of the dwelling also in bedrooms during night Without adequate ventilation carbon dioxide content tends...

Page 4: ...m and maximum speeds and one of them is chosen in accordance with occupancy on the basis of the instructions given by automatic remote monitoring control with week clock for instance For more detailed...

Page 5: ...at not included in the unit delivery In detached houses it is customary to use water glycol mixture as the liquid in order to prevent the freezing of the radiator Heating of air depends on the tempera...

Page 6: ...tor 2 switches off when exhaust air temperature is by circa 3 C higher than the value set for the thermostat Note You can adjust the antifreeze thermostats C and A for Vallox 132 E preheating radiator...

Page 7: ...hich captures fine dust pollen and dust not seen to the eye and a G3 class coarse filter A for insects and heavy pollen for instance There is a G3 coarse filter C on the extract air side The filters n...

Page 8: ...ance When you open the door of Vallox132 E the security switch T turns voltage off You can also wash the filters with 25 30 C warm water and washing up liquid pressing them smoothly Do not handle the...

Page 9: ...o remove the balancing pieces attached to the propellers If you use water in cleaning the unit or its parts do not let it flow into the electrical parts 3 2 1 Radiators I Post heating radiator Electri...

Page 10: ...xternal grille contrary to what is said in the installation instructions and has been clogged or by the closing of the supply air valves in the rooms 3 4 Condensing water During the heating season hum...

Page 11: ...ch the cell may freeze Compare with list item 1 Supply air fan stops and starts too frequently The difference between the stopping and starting temperatures is too small The preheating radiator does n...

Page 12: ...VALLOX We reserve the right to make changes without prior notification 1 09 410 E 29 1 2010 PDF VALLOX 132 E VKL Vallox Oy Myllykyl ntie 9 11 FI 32200 Loimaa Tel 358 10 7732 200 www vallox com...

Page 13: ......

Reviews: