OM-MP80 E V1.15
January 29, 2015
Page 23
MP80
FAN OPERATION
Th
e blower will be turning on and off automatically based on the heat output off the wood furnace. At 155°F in
the plenum the fan will turn on and at 105°F it will turn off .
If the fan turns on regularly in standby mode (no call for heat) adjust the low output so less heat will be produced
at low (see “OPERATING INSTRUCTIONS” on page 22,
Fig. 25
).
PLEASE NOTE: Th
e limit /safety switches have an auto / manual switch. Normal operation is set to AUTO.
CONTROL SYSTEM - SUMMER FAN / AUTO
A manual fan switch has been added to the fan speed / limit control located on the
furnace plenum. Th
is will provide air circulation during the summer time when the
furnace is not being used.
DO NOT HAVE THE SWITCH ON “MAN” ANYTIME A FIRE IS GOING.
OPERATING SOUNDS AND SMELLS
Expansion / contraction noises during heating up and cooling down cycles are normal
and to be expected. When fi rst installed, the furnace brick and metal are cold and must become hot before the
appliance will function well. During the break-in period (the fi rst 2 or 3 fi res) create only small, hot fi res using
kindling; this will allow the cast liners to cure. Th
e paint may also smell a little for the fi rst few fi res as it cures
and you may wish to open a door or window to alleviate the smell. Th
ere are many diff erent ways to start a fi re,
review the hints and warnings in this section to ensure the fi re is started properly.
LIGHTING THE FIRE
O
O
OM
O
OM
M
M
P8
P8
0
0
E
E
V1
V1
1
1
5
5
Ja
Ja
nu
nu
ar
ar
y
y
29
29
20
20
15
15
•
ALWAYS OPERATE THIS APPLIANCE WITH THE FIREBOX DOOR CLOSED AND LATCHED EXCEPT
DURING START UP AND RE-FUELING. ALWAYS WEAR GLOVES TO PREVENT INJURY. DO NOT LEAVE
THE FIRE UNATTENDED WHEN THE DOOR IS UNLATCHED AS UNSTABLE WOOD COULD FALL OUT OF
THE FIRE CHAMBER CREATING A FIRE HAZARD TO YOUR HOME. INSTALLATION REQUIRES WIRING
BY A CERTIFIED ELECTRICIAN. ALL WIRING TO CONFORM TO CSA 22.1.
•
NEVER LEAVE CHILDREN UNATTENDED WHEN THERE IS A FIRE BURNING IN THE APPLIANCE.
•
DO NOT USE CHEMICALS OR FLUIDS TO START THE FIRE.
•
DO NOT OPERATE WITH FLUE DRAFT GREATER THAN -0.06” W.C. (-15 Pa).
•
DO NOT STORE FUEL OR OTHER COMBUSTIBLE MATERIAL WITHIN MARKED INSTALLATION
CLEARANCES OF THE APPLIANCES OR WITHIN THE SPACE REQUIRED FOR FUELING, ASH REMOVAL,
AND OTHER ROUTINE MAINTENANCE OPERATIONS.
•
INSPECT AND CLEAN FLUES AND CHIMNEY REGULARLY.
•
HOT SURFACES - DO NOT TOUCH DURING OPERATION.
•
FREQUENTLY EXAMINE DOOR SEAL / GASKET, REPLACE IF WORN. FAILURE TO SHUT DOOR TIGHTLY
AND IGNORING LEAKING GASKET CAN RESULT IN EXTREME OVER FIRING CONDITIONS.
•
RISK OF FIRE OR EXPLOSION - DO NOT BURN GARBAGE, GASOLINE, DRAIN OIL, NAPHTHA, ENGINE
OIL OR OTHER FLAMMABLE LIQUIDS.
OPERATING INSTRUCTIONS cont.
SWITCH ON “
MAN
” = MANUAL FAN OPERATION
SWITCH ON “
AUTO
” = AUTO FAN OPERATION
(PLENUM TEMPERATURE DEPENDANT)