background image

BUS BODY ELECTRONICS

 

 

 

10 

2.7.2  Error overview 

Error code 

Component 

Cause 

Remedy 

F001-016 

Not used 

 

 

F017 

Pressure sensor 

 Defective sensor 

 Wiring harness de-

fective 

 Inspect wiring harness 

 Replace sensor 

F018 

Duct/convector  temper-
ature sensor 

 Defective sensor 

 Wiring harness de-

fective 

F019 

Ice sensor 

 Defective sensor 

 Wiring harness de-

fective 

F020 

Room  temperature  sen-
sor 

 Defective sensor 

 Wiring harness de-

fective 

F021 

Environmental  tempera-
ture sensor 

 Defective sensor 

 Wiring harness de-

fective 

F022 

Ice sensor 

 Icing 

 Temperature too low 

Wait until sensor has de-
frosted 

F023

 

F024 

High pressure 
Low pressure 

Brief  system  over-
load 

because 

of 

high motor speed at 
high  environmental 
temperature 

The system turns off for 
5  minutes  and  tries  to 
restart. If the error code 
persists,  consult  our 
service center 

F025-32 

Not used 

 

 

Table  1 - Error code overview 

 

Summary of Contents for SC600 Marcopolo

Page 1: ...Rev 21 11 2018 Id No DOK30620 BUS BODY ELECTRONICS SC600 MARCOPOLO Operating instructions Busdriver...

Page 2: ...ctivation deactivation 6 2 1 1 Activation 6 2 1 2 Deactivation 6 2 2 Auto mode 6 2 2 1 Activation 6 2 2 2 Deactivation 6 2 3 Configuring the blowers manually 7 2 3 1 Activating the controller manually...

Page 3: ...ivated Cooling mode 6 Figure 8 SC600 Auto mode activated Heating mode 6 Figure 9 SC600 Auto mode deactivated 7 Figure 10 SC600 setting the blower level manually 7 Figure 11 SC600 recirculating air fun...

Page 4: ...functions for the roof Additionally this control panel can also be used to control the heating system on the floor The controller for the air conditioning systems components can operate automatically...

Page 5: ...f the display 1 Display 2 On off button 3 UP 4 DOWN 5 Function status light 6 Blower button 7 Fresh air recirculating air button 8 Auto button A Desired value display room temperature B Blower level m...

Page 6: ...unctions and infor mation summarized under point 2 as well as Error mode The normal operat ing display includes all of the elements provided here in the example Error detection mode Mode to display al...

Page 7: ...and function symbol light up on the display Figure 6 2 2 2 Deactivation Press button if Auto mode is on Mode is off corresponding status light and function symbol are off Figure 8 Note Auto mode can...

Page 8: ...ents of 0 blower speed 0 to 10 blower speed 100 Press button Blower level 1 Press button Blower level 1 Note When Auto mode is deactivated the air conditioning com pressor after a run time of 90 secon...

Page 9: ...ght up After running for 10 minutes the system turns off the recirculating air function Pressing the button again within 10 minutes will de activate the recirculating air function and open the fresh a...

Page 10: ...h or Reset the counter with after resetting the coun ter shower the value 1 if the error persists 2 7 1 3 Ending Press and buttons for 2 seconds Normal operating display appears Figure 16 Note Additio...

Page 11: ...rness de fective F020 Room temperature sen sor Defective sensor Wiring harness de fective F021 Environmental tempera ture sensor Defective sensor Wiring harness de fective F022 Ice sensor Icing Temper...

Page 12: ...Valeo Thermal Commercial Vehicles Germany GmbH Postfach 1371 82198 Gilching Germany Tel 49 0 8105 7721 0 Fax 49 0 8105 7721 889 www valeo thermalbus com service valeobus valeo com...

Reviews: