background image

AUSTRALIA

1300 734 253

[email protected]

www.valen.com.au

NEW ZEALAND

0800 734 253

[email protected]

www.valen.co.nz

VALEN ENLiFEN LITHIUM
INSTALLATION AND 
OPERATING INSTRUCTIONS

VERSION 1  APRIL 2021

TO BE INSTALLED BY A SUITABLY QUALIFIED 
ELECTRICIAN ONLY

Summary of Contents for ENLiFEN

Page 1: ...valen com au www valen com au NEW ZEALAND 0800 734 253 sales valen co nz www valen co nz VALEN ENLiFEN LITHIUM INSTALLATION AND OPERATING INSTRUCTIONS VERSION 1 APRIL 2021 TO BE INSTALLED BY A SUITABL...

Page 2: ...e storing and transporting the batteries 5 When on charge float voltages must be measured Be particularly careful because shorting a battery at this time can cause severe equipment failure and persona...

Page 3: ...on delivery inspect the batteries for damage caused in transit Damaged pallets or packing material or disarrayed batteries could indicate rough improper handling in transit Describe in detail take pho...

Page 4: ...re is 5 C to 30 C VALEN ENLiFEN LiFePO4 Batteries must be charged at least every 6 months while in storage If stored at ambient temperatures above 30 C charge the batteries every 4 months Storage of b...

Page 5: ...gas during normal charging and discharging However ensure some air exchange is present in the ventilation 4 1 4 Floor Loading Whilst this is not quite as severe a problem as with VRLA batteries befor...

Page 6: ...te 4 5 1 Cabling Recommendations Battery ratings are specified at the terminals of the battery The cabling used to connect the battery terminals to the load has a voltage drop when the battery is disc...

Page 7: ...e terminal of the battery bank should be connected to the negative terminal of the charger 4 5 6 Paralleling of Batteries When greater capacity is desired than available from a single cell or string p...

Page 8: ...dust accumulations If required a solution of 1kg of baking soda in 4L of water may be used as a multipurpose cleaner if more stubborn stains or dirt accumulations are present Follow the rack or cabin...

Page 9: ...attery and determining the actual time the battery will support the load This test is done in the case of a UPS by switching into a test mode where the battery becomes the primary source and the norma...

Page 10: ...TRALIA 1300 734 253 sales valen com au www valen com au NEW ZEALAND 0800 734 253 sales valen co nz www valen co nz Company Details Legal Entity Valen Power Pty Ltd ACN 134 028 961 Telephone 1300 734 2...