If the difference is less 100: 

1.

 

Verify that the position sensor is connected to the actuator 

 
If the difference is less 1500: 

1.

 

Increase signal span from the sensor: See sensor manual 

 
The difference between the Open ADC value and the 50% ADC value shall be approximately equal 
to the difference between the Close ADC value and 50% ADC value. 

1.

 

  Check the signal from the position sensor 

2.3

 

Test the control loop / AI0 

Send 4mA followed by a 20mA signal from DCS or a loop calibrator 
 
Push Status 

1.Live status and push down arrow down until SP-mA is shown. 

 

From DCS or loop calibrator  IHP24 Live menu - SP-mA 

4mA 

 

20mA 

 

 
If signals are 0 mA 

1.

 

Check wiring 

If 4 mA and 20 mA signals are “off” 

1.

 

Perform a signal calibration of AI0/Control loop: See IHP24 manual 

2.4

 

Test the transmitter loop / AO0 

Verify that the position signal transmitted from the IHP24 and the position signal received by DCS 
or loop calibrator are identical 
 
Push Status 

1.Live status and push down arrow down until TM-mA is shown. 

 

IHP24 Live menu - TM-mA 

Readout from DCS or loop calibrator 

 

 

 
If TM-mA is 3.5 mA 

1.

 

Verify that there are no errors in the error log 

 
If 0 mA is received by DCS or loop calibrator 

1.

 

Check wiring 

1.

 

Check if the sensor is active or passive. AO0 is for use of passive transmitters, i.e. output is 
active: See IHP24 manual 

 

Summary of Contents for IHP24

Page 1: ...DHP UM 026 Val Controls A S Limfjordsvej 3 DK 6715 Esbjerg N Tel 45 7547 0600 Fax 45 7547 0611 vc valcontrols com www valcontrols com Revision 2 1 7 IHP24 Troubleshooting ...

Page 2: ...Esbjerg N Tel 45 7547 0600 Fax 45 7547 0611 vc valcontrols com www valcontrols com Revision 2 2 7 Table of contents 1 Identification 3 2 Basic trouble shooting 4 2 1 Valve configuration 4 2 2 Position feedback 4 2 3 Control loop 5 2 4 Transmitter loop 5 ...

Page 3: ...ct information Name Company Phone Mail Nos are printed on device name plate Software ID Software version On the IHP24 keyboard push Status 2 Identification System information Actuator type Hydraulic Pneumatic Rotary Linear Position sensor mounted on the actuator 4 20mA passive 4 20mA active Potentiometer Sensor model only for 4 20mA Problem description Model no Serial no ...

Page 4: ...can stay put 2 2 Test the position feedback By manual calibration operate the actuator and note the ADC values shown on the screen Push Calibration 2 Manual ADC value at open ADC value at approx 50 travel ADC value at close If both values are less than 100 1 Check that the IHP24 is configured with correct position input 2 Check sensor wiring 3 Check if the 4 20mA sensor is active or passive Active...

Page 5: ...rator Push Status 1 Live status and push down arrow down until SP mA is shown From DCS or loop calibrator IHP24 Live menu SP mA 4mA 20mA If signals are 0 mA 1 Check wiring If 4 mA and 20 mA signals are off 1 Perform a signal calibration of AI0 Control loop See IHP24 manual 2 4 Test the transmitter loop AO0 Verify that the position signal transmitted from the IHP24 and the position signal received ...

Page 6: ...S Limfjordsvej 3 DK 6715 Esbjerg N Tel 45 7547 0600 Fax 45 7547 0611 vc valcontrols com www valcontrols com Revision 2 6 7 If 4 mA and 20mA signals are off 2 Perform a signal calibration of the transmitter loop See IHP24 manual ...

Page 7: ...the IHP24 through ValConnect export the configuration and mail it to Val Controls 3 2 4 20mA loop When troubleshooting a 4 20 mA loop it is generally a good idea to 1 Break the loop 2 Connect a loop calibrator to the position transmitter and verify that a signal is transmitted 3 Connect a loop calibrator to the receiver and verify that a signal is measured 3 3 Factory reset If troubleshooting does...

Reviews: