No. 417
PST error: Total timeout, pressure
Description
The pressure did not reach the start pressure after the partial stroke
Trouble shooting
This error can be caused by:
•
Low supply pressure
It can be solved by:
•
Increase pressure
•
Resolve the mechanical problem
•
Increase PST total timeout
No. 418
PST error: At 0% position
Description
The position measured to be 0%
Trouble shooting
This error can be caused by:
•
Position sensor was disconnected
•
Position sensor is operating in the illegal area
•
Wrong configuration of the position switches
•
The valve moved to 0%
It can be solved by:
•
Check the position sensor
•
Make sure the position sensor is operating within the legal area
•
Check the function of the position switches
•
Decrease the PST travel
No. 419
PST error: Wrong Switch. SP
Description
The SP switch was activated before the 100% switch was released
Trouble shooting
This error can be caused by:
•
Wrong configuration of the position switches