![Val Controls I 24-AF Series Hardware Manual Download Page 3](http://html1.mh-extra.com/html/val-controls/i-24-af-series/i-24-af-series_hardware-manual_3196217003.webp)
DHW-UM-004
Val Controls A/S
•
Sallingsundvej 5
•
DK-6715 Esbjerg N
•
Tel. +45 7547 0600
•
www.valcontrols.com
Revision: 4
3/20
1
General
This manual covers the following products:
IHP24-AF
IDP24-AF with software DID-SW-001
IVC24-AF
IDC24-AF
ILB24-AF
ILC24-AF
IPC24-AF
1.1
Safety instructions
For a safe installation of a Val Controls device, the following must be observed. The module must
be installed by qualified personnel who are familiar with the national and international laws,
directives and standards that apply to this product as well as all instructions in this manual.
The information in this manual is subject to changes without notice.
1.2
Environment
Operating temperature
1
: -30 to 80
˚
C
Storage temperature
1
: -30 to 80
˚
C
1
Depending on model. Please contact Val Controls
Relative Humidity: < 95% (No condensation)
The printed circuit boards are coated for tropical climate and harsh environments to resist airborne
contamination according to G3, ISA-71.04-2013.
Ingress protection
2
: IP68
2
Ex d enclosure only. For Ex e enclosure see certification label.
1.3
Mounting and dimension
Screw torque: 3.5 lb in
Wire diameter: AWG14-22 (0.5mm² til 2.5mm²)
All external components must have specifications that fit the desired performance and requirements
of the valve/actuator system.
After installation the lid has to be closed properly to maintain the IP rating.
The O-ring is as standard treated with Molykote 55 O-ring grease. To maintain the IP rating the O-
ring has to be treated every 2
nd
year with Molykote 55 O-ring grease or similar.
Dimensional drawing can be found on www.valcontrols.com