NOTE 

 

WSP150 can also be mounted on a wall or to 
a boom, with two screws inserted to the 
lowermost through-holes behind the cover's 
fixing screws. If the screws are entered from 
the rear, no nuts are needed, since the M4 
threads in the holes can be utilized. 

 

 

 

1011-125 

Figure 3 Wiring Instructions for RS-485 

 

 

1011-126 

Figure 4 Wiring Instructions for RS-422 

 

 

1011-127 

Figure 5 Wiring Instructions for SDI-12 

 

1011-128 

Figure 6 Wiring Instructions for RS-232 

 

TECHNICAL DATA 

Property Description 

lue 

Va

Allowed input voltage 
(across channel line pair and 
from line to GND, terminals #3) 

Power channels:  
Data channels:     

max. ±43 V 
max. ±13 V 

Allowed input common mode 
voltage 

Any line to earth:  max. ±72 V 

Power lines:  

max. 1.5 A 

Allowed throughput current 

Data lines: 

max. 0.16 A 

Power lines: 

0.3 ohms 

Throughput resistance 
(per line) 

Data lines: 

15  ohms 

Power channels:  max. ±60 V 

Turn-on voltage 

Data channels: 

max. ±16 V 

Surge current  

To earth: 
Differential:           

max. 10 kA 
max. 5 kA      

EMC surge tolerance 

EN 61000-4-5  (4 kV, 2 kA) 
IEEE C62.45    (6 kV, 3 kA) 

Installation and maintenance 
work temperature 

-40...+70 °C  (-40...+158 °F) 

Operating and storage 
temperature 

-52...+70 °C  (-60...+158 °F) 

Environmental protection class  IP66  (NEMA 4X) 
Dimensions (w × h × d) 

130 × 94 × 58 mm 

with cable glands & mounting 
assembly 

130 × 120 × 69 mm 

Weight 0.65 

kg 

Housing materials 

Polycarbonate, stainless steel  

Cable dimensions 
Wire dimensions 

Ø 5 - 10 mm 
Ø 0.4 - 1.7 mm  (AWG 26 - 14) 

DIMENSIONS 

1106-029 

Figure 7 Dimensions in mm  

 

0611-029 

Figure 8 Shielding Procedure in Cable Gland 

 

 

N17728 

 

 