3.10 Configuring IEC 61850 Protocol
Figure 26 IEC 61850 Settings Page
IEC 61850 protocol is an optional feature and requires a license. If a license is not
installed on the DGA monitor, you cannot enable the protocol. Contact Vaisala for
acquiring the license.
1. Connect to the user interface as the
Admin
user. See
.
2. In the user interface, select
Settings > Network > IEC 61850
.
3. Select if the IEC 61850 protocol should be
Enabled
or
Disabled
.
4. Select
Apply
to save your changes.
You can download the following supporting documents from this page:
• IED Capability Description (ICD) file
• Protocol Implementation Conformance Statement (PICS)
• Model Implementation Conformance Statement (MICS)
Chapter 3 – User Interface
39