16. Route the wires along the cable ducts.
1
Galvanic isolator wires connected
2
Galvanic isolator power wires connected to power block
3
Data logger wires connected
17. For wiring of the intrinsically safe screw terminals in the isolators, refer to the wiring
instructions printed on the side of the isolator and the
Safety Manual
leaflet provided in
the isolator packaging.
18. Cut the original cable duct and its cover to the appropriate length and screw it back
into place, to the left of the partition plate.
Vaisala recommends that you label the cable duct cover with the text INTRINSICALLY
SAFE CONNECTIONS. Alternatively, use a blue cable duct as shown in
.
19. Insert any extra length of wire into the cable ducts and replace the cable duct covers.
20. Reconnect power in the cabinet.
a. Switch on the circuit breaker.
b. Switch on mains power.
For instructions on configuring measurement units and scaling in DL4000 data loggers,
see
Vaisala viewLinc Enterprise Server Version 5.0 User Guide
(M211975EN).
More information
‣
CAB100B wiring diagrams (page 126)
‣
CAB100B layout diagrams (page 135)
Chapter 6 – Adding devices to CAB100B