42
Installation and maintenance instructions ecoTEC pro 0020244995_04
Code Parameter
Values or explanations
Factory
setting
Own setting
D.016 Controller 24 V DC: Heating mode
Heating mode off/on
Not ad-
justable
D.017 Control type
Control type:
0 = Flow, 1 = Return
Return: Automatic detection function for heat output
inactive. Max. possible partial heat load when
D.000
is on
Auto
.
0 = Flow
D.018 Pump operating mode
1 = Comfort (continuously operating pump)
Internal pump is switched on when the heating flow tem-
perature is not at
Heating off
and the heat requirement
is enabled via an external control
3 = Eco (intermittently operating pump)
Internal pump is switched on every 25 minutes for 5
minutes once the overrun time has elapsed
3 = Eco
D.019 Pump operating mode: 2-stage
pump
Setting for two-stage pump operating mode
0: Burner mode stage 2, pump prerun/overrun stage 1
1: Heating mode and pump prerun/overrun stage 1,
domestic hot water mode stage 2
2: Automatic heating mode, pump prerun/overrun
stage 1, domestic hot water mode stage 2
3: Always stage 2
4: Automatic heating mode, pump prerun/overrun
stage 1, domestic hot water mode stage 1
2
D.020 Max. DHW temperature target
value
Adjustment range: 50
–
70 °C (
actoSTOR
65 °C)
65 °C
D.022 DHW demand
On, Off
Not ad-
justable
D.023 Heating mode status
Heating on, heating off (summer mode)
Not ad-
justable
D.025 Ext. eBUS signal: Cylinder char-
ging
On, Off
Not ad-
justable
D.026 Auxiliary relay
1 = Circulation pump
2 = External pump
3 = Cylinder charging pump
4 = Extraction hood
5 = External solenoid valve
6 = External fault message
7 = Solar pump (not active)
8 = eBUS remote control (not active)
9 = Anti-legionella pump (not active)
10 = Solar valve (not active)
2 = External
pump
D.027 Accessory relay 1
Switching of relay 1 on the VR 40 "2 in 7" multi-func-
tional module
1 = Circulation pump
2 = External pump
3 = Cylinder charging pump
4 = Extraction hood
5 = External solenoid valve
6 = External fault message
7 = Solar pump (not active)
8 = eBUS remote control (not active)
9 = Anti-legionella pump (not active)
10 = Solar valve (not active)
2 = External
pump