Operating instructions 0020262548_01

Setting level

Values

Unit

Increment, select

Default setting

Min.

Max.

Everything

Yes

,

No

No

Installer level

Enter code

000

999

1

000

B

Troubleshooting

Symptom

Possible cause

Measure

Display remains dark

Software error

1.

Switch off the mains switch on all heat generators for ap-
prox. 1 minute and then switch them on again.

2.

If the fault persists, inform the competent person.

No changes in the display when
the rotary knob is turned

Software error

1.

Switch off the mains switch on all heat generators for ap-
prox. 1 minute and then switch them on again.

2.

If the fault persists, inform the competent person.

No changes in the display
when the selection buttons are
pressed

Software error

1.

Switch off the mains switch on all heat generators for ap-
prox. 1 minute and then switch them on again.

2.

If the fault persists, inform the competent person.

Display view:

Button lock act-

ive To unlock, press OK for
3 seconds

, it is not possible to

change the settings or values

Button lock is active

1.

If you would like to change any of the values, follow the in-
structions on the display.

2.

Also read through the

Button lock

Activate (

Page 13)

function.

Display view:

Restricted opera-

tion/ comfort protection

, insuf-

ficient heating up of the heating
and the domestic hot water

Heat pump does not work

1.

Inform the competent person.

2.

Select the setting for limp home mode until the competent
person arrives.

3.

To do this, read through the Implementing the setting when
the heat pump fails (

Page 17) function.

Display view:

Fault F. Fault:

Heat generator 1

, the specific

fault code (e.g. F.33) and the
specific heat generator appear
behind F. in the display

Heat generator faults

1.

Carry out a

Reset

fault message (

Page 16).

2.

If the fault persists, inform the competent person.

C

Maintenance messages

The maintenance message

Service heat pump 1

is an example of a maintenance message that may appear for heat pumps

1 to 7.

The maintenance message

Service heat generator 1

is an example of a maintenance message that may appear for heat

generators 1 to 7.

#

Code/meaning

Description

Maintenance work

Interval

1

Service heat
pump 1

The heat pump requires main-
tenance work.

Refer to the operating instruc-
tions of the relevant heat pump
for information on the mainten-
ance work required

See the operating instructions
for the heat pump

2

Service heat
generator 1

The heat generator requires
maintenance work.

Refer to the operating instruc-
tions of the relevant heat gener-
ator for information on the main-
tenance work required

See the operating instructions
for the heat generator

3

Service ventila-
tion unit

The ventilation unit requires
maintenance work.

Refer to the operating instruc-
tions of the ventilation unit for
information on the maintenance
work required

See the operating instructions
for the ventilation unit

4

Low water pres-
sure

The water pressure is too low in
the heating installation.

Refer to the operating instruc-
tions for the relevant heat gen-
erator for information on filling
with water

See the operating instructions
for the heat generator

5

Service date
Next service on

The competent person has
entered a date on which main-
tenance is due for the heating
installation.

Inform the competent person if
maintenance work is required

Date entered in the control

Summary of Contents for VRC 700/6

Page 1: ...en Operating instructions Weather compensated system control VRC 700 6 0020262548_01 28 11 2022...

Page 2: ...4 Operation 5 4 1 Operating structure 5 4 2 Basic display 6 4 3 Operating concept 6 5 Operating and display functions 8 5 1 Information 8 5 2 Settings 10 5 3 Operating modes 14 5 4 Advanced functions...

Page 3: ...physical sensory or mental capabil ities or lack of experience and knowledge if they have been given supervision or instruc tion concerning use of the product in a safe way and understand the hazards...

Page 4: ...flow temperature of the heating installation If the outdoor temperature increases the system control reduces the flow temperature The system control responds to the fluctuations in the outdoor temper...

Page 5: ...ine 3 9 CE marking The CE marking shows that the products comply with the basic requirements of the applicable directives as stated on the declaration of conformity The declaration of conformity can b...

Page 6: ...energy Off Day Set back off Empty line 4 2 3 2 Basic display for the Cooling operating mode Mode Time periods Symbol Information field Auto On Desired cooling temp Off Empty line Day Desired cooling...

Page 7: ...nge to the Max vent stage Day Set back Direct permanent change to the Max vent stge Night 4 3 1 4 Desired temperature in the Manual cooling advanced function Mode Time periods Effect Activated On Dire...

Page 8: ...inform ation that provides an overview of the current system status and current settings that you can change there 5 1 1 1 System Menu Information System status Fault status If no maintenance is requ...

Page 9: ...set the desired set back temperature for the zone Set back temp heat is the temperature that you want to have in the rooms during the night or when you are away from home night mode Menu Information S...

Page 10: ...e total yield is displayed on the bottom right The highest value achieved in one month for the last two years is dis played in the top right 5 1 2 4 Diagram Reading the electrical consumption Menu Inf...

Page 11: ...ge 12 You can create up to three time periods for each individual day and for predefined blocks Monday Friday Saturday Sunday Monday Sunday When entering time periods for individual days or blocks the...

Page 12: ...n Within the time period the circulation is switched on Outside the time period the circulation is switched off 5 2 3 8 Setting the Ventilation time programme Menu Time programmes Ventilation The time...

Page 13: ...g Button lock Menu Basic settings Display Button lock You can use this function to activate the button lock After one minute of not pressing any button or operating the rotary knob the button lock is...

Page 14: ...ogrammes or for Everything to the default setting Menu Basic settings Default setting Time pro grammes With Time programmes you reset all the settings you have made in the Time programmes function to...

Page 15: ...of air using the value that you set in the Max vent stage Day ventilation level Set back The operating mode constantly controls the ex change of air using the value that you set in the Max vent stge N...

Page 16: ...st The Cylinder boost advanced function heats the water in the domestic hot water cylinder until it reaches the set desired temperature Domestic hot water The advanced function is active for one hour...

Page 17: ...ears again in the display 7 Care 7 1 Caring for the product Clean the casing with a damp cloth and a little solvent free soap Do not use sprays scouring agents detergents solvents or cleaning agents t...

Page 18: ...ription of the functions for ZONE1 also applies for all available zones Setting level Values Unit Increment select Default setting Min Max Information System status System Fault status Current value N...

Page 19: ...ast month kWh Hot water Electricity Total value since start up kWh Fuel Total value since start up kWh Information Consumption History Heating Electricity Total value since start up kWh Fuel Total val...

Page 20: ...NE1 Cooling Time programmes Circulation Time programmes Ventilation Individual days and blocks Monday Tuesday Wednes day Thursday Friday Sat urday Sunday and Monday Friday Saturday Sunday Monday Sunda...

Page 21: ...Button lock off On off Preferred display Heating Cooling Vent Heating Basic settings Costs Tariff for aux heater 1 999 1 12 Low tariff elec rate 1 999 1 16 High tariff elec rate 1 999 1 20 Basic setti...

Page 22: ...Fault Heat generator 1 the specific fault code e g F 33 and the specific heat generator appear behind F in the display Heat generator faults 1 Carry out a Reset fault message Page 16 2 If the fault p...

Page 23: ...basic display 6 Outdoor temperature setting the offset 14 P Party 16 Preventing a malfunction 5 R Reading the article number 5 10 Reading the electrical consumption 10 Reading the environment yield 1...

Page 24: ...24 Operating instructions 0020262548_01 Time programme 11 quick setting 11 Setting 11 V Ventilation 4 Ventilation boost 16 Ventilation level 11 Z Zone 4 10 Zone in the basic display 6...

Page 25: ......

Page 26: ......

Page 27: ......

Page 28: ...isher manufacturer Vaillant GmbH Berghauser Str 40 D 42859 Remscheid Tel 49 2191 18 0 Fax 49 2191 18 2810 info vaillant de www vaillant de These instructions or parts thereof are protected by copyrigh...

Reviews: