VAI3-WN-I_EN - 07/14 - Vaillant
- 18 -
INSTALLATION
11.5 Electrical characteristics
Fig. 11.4
Electrical layout for outdoor and indoor connection for
VAI 3-025 WN and VAI 3-035 WN.
Legend
1 Connector strip for the outdoor unit
2 Connector strip for the indoor unit
VAI 3-025 WN
VAI 3-035 WN
VAI 3-050 WN
Power supply (V/Ph/Hz)
230 / 1 / 50
230 / 1 / 50
230 / 1 / 50
Supply
Supply section up to 25 meter (in mm
2
)
2.5
2.5
2.5
Indoor / Outdoor
Indoor
Indoor
Outdoor
Thermal-magnetic circuit breaker, type D (A)
16
16
16
Interconnection section up to 25 meter (mm
2
)
2.5
2.5
2.5
Inteconnect shielded cable or not (YES/NO)
NO
NO
NO
Immediatte residual current protector (A)
0.03
0.03
0.03
Table 11.1 Electrical Characteristics
2
1
Fig. 11.5
Electrical layout for outdoor and indoor connection for
VAI 3-050 WN
2