2 Product description
4
Operating and installation instructions
sensoCOMFORT
0020287900_00
2.10
Setting the heat curve
A
B
15
10
5
0
-5
-10
-15
-20
20
30
40
50
60
70
80
90
1.2
1.5
1.8
2
2.5
3
3.5
4
0.8
1.0
0.4
0.2
0.1
0.6
A
Outside temperature °C
B
Target flow temperature
°C
The figure shows the possible heat curves of 0.1 to 4.0 for a
target room temperature of 20 °C. If, for example, heat curve
0.4 is selected, a flow temperature of 40 °C is maintained at
an outdoor temperature of -15 °C.
A
B
C
D
18
22
20
0.4
70
60
50
40
30
15
10
5
0
-5
-10
-15
-20
A
Outdoor temperature °C
B
Target flow temperature
°C
C
Target room temperat-
ure °C
D
Axis a
If the heat curve 0.4 is selected and 21 °C is specified for the
target room temperature, the heat curve is then translated,
as shown in the figure. The heat curve is displaced accord-
ing to the value of the target room temperature along axis a
which is angled at 45°. At an outdoor temperature of -15 °C,
the control system provides a flow temperature of 45 °C.
2.11
Display, control elements and symbols
ĮİŰ
ĬĪƀ
ĬįŀĪ
ƀ
īĬƀ
2.11.1 Control elements
–
Calling up the menu
–
Back to the main menu
–
Confirming a selection/change
–
Saving set values
–
One level back
–
Cancelling input
–
Navigating through the menu structure
–
Reducing or increasing the set value
–
Navigating to individual numbers/letters
–
Calling up help
–
Calling up the time programme assistant
Active control elements light up green.
Press
once: You access the basic display.
Press
twice: You access the menu.
2.11.2 Symbols
Time-controlled heating active
Button lock active
Maintenance required
Fault in the heating installation
Contact the competent person
Noise reduction mode active
Most energy-efficient heating mode active