Commissioning checklist 3
0020251823_01 System installation instructions
5
Work
Comments/settings
51
Status
Current value display (standby, heating, cooling, do-
mestic hot water)
52
Current flow temp.
Current value display
53
Additional module
54
Status
Current value display (standby, heating, cooling, do-
mestic hot water)
55
Current flow temp.
Current value display
56
HEATING 1
57
Type of circuit
Heating
58
Status
Current value display (off, heating mode, cooling, do-
mestic hot water)
59
Target flow temp.
Current value display
60
Max limit outs.temp.
21 °C, change in consultation with the customer, if re-
quired
61
Heating curve
0.4 to 0.6 for underfloor heating
62
Minimum temperature
15 °C
63
Maximum temperature
45 °C for underfloor heating
64
Auto Off mode
Set-back
65
Room temp. mod.
None
if the control is installed in the heat pump
Temp. mod.
if the control is installed in the living room
66
Cooling possible
Yes
for underfloor heating
No
; you should not use passive cooling for compact col-
lectors and flat collectors
67
Min. cool. fl. tgt temp.
18 °C
68
End OT cooling
15 °C
69
Pump status
Current value display:
off
/
On
70
Dew point monitoring
Yes
71
ZONE1
72
Zone activated
Current value display:
No
/
Yes
73
Day temperature
20 °C
74
Set-back temp.
15 °C
75
Room temperature
Current value display
76
Zone assignment
VRC 700
Condition: VRC 700 installed in the living room, room
temperature modulation activated
77
Zone valve status
Current value display (closed/open)
78
Domestic hot water
79
Cylinder active
Condition: Domestic hot water cylinder in the system
80
Target flow temp.
Current value display
81
Domestic hot water
50 °C
Inform the end user about the anti-legionella function
82
Domestic hot water
Current value display
83
Cyl. charging pump
Current value display (off/on)
841
Circulation pump
Current value display (off/on)
85
Anti-legionella day
Selection: Off, Mo, Tu, We, Th, Fr, Sa, Su, Mo-Su
Factory setting: Off
86
Anti-legionella time
04:00
Depending on the customer
87
Cyl. boost hysteresis
15 K
88
Cylinder boost offset
10 K
89
Max. cyl. charg. time
Off: KfW efficient house 40
60 min.: > KfW efficient house 40