0020253094_05 ecoTEC sustain Installation and maintenance instructions
45
#
Maintenance work
Interval
32
Checking leak-tightness
Annually
33
Completing inspection and maintenance work
Annually
B
Check programmes
–
Overview
Display
Meaning
P.00
Purging the domestic hot water and heating circuit:
The function is activated in the small domestic hot water circuit for three minutes and then in the heating circuit
for one minute.
The pump runs and stops at regular intervals.
If required, this function can be manually switched off.
P.01
The burner operates with an adjustable heat input in heating or domestic hot water mode:
The product operates after ignition with the heat input set between "0" (0% = Pmin) and "100" (100% = Pmax).
The function is active for 15 minutes.
P.02
The burner operates at ignition load in heating or domestic hot water mode:
After ignition, the product works at ignition load.
The function is active for 15 minutes.
P.06
Filling the product:
The prioritising diverter valve is moved to the mid-position. The burner and pump switch off (to fill or drain the
product).
Automatic air vent
function
Purging the product:
If the pressure is lower than 0.03 MPa (0.3 bar) for longer than 15 seconds and then is above 0.07 MPa (0.7
bar), the automatic purging function is activated.
The function is activated in the small hot water circuit for four minutes and then in the heating circuit for six
minutes.
This function cannot be manually switched off.
C
Overview of diagnostics codes
Note
Since the code table is used for various products, some codes may not be visible for the product in question.
Dia-
gnostics
code
Parameter
Values
Unit
Increment, select, explanation
Factory set-
ting
Own setting
Min.
Max.
d.00
Maximum heating output
is fixed or adjusts auto-
matically
–
–
kW
The maximum heating output
varies depending on the product.
→
Section "Technical data"
Automatic: Unit automatically
adjusts the maximum output to
the current system demand
→
Section
"Technical
data"
Adjustable
d.01
Pump overrun time in
heating mode
1
60
min
1
5
Adjustable
d.02
Maximum burner anti-
cycling time in heating
mode
2
60
min
1
20
Adjustable
d.04
Water temperature in the
cylinder
Current value
℃
Applies to: Product with heat-
ing mode only, connected to do-
mestic hot water cylinder with
temperature sensor
–
Not
adjustable
d.05
Determined target heat-
ing flow temperature
Current value
℃
–
–
Not
adjustable
d.06
Target domestic hot wa-
ter temperature
Current value
℃
Applies to: Combi boiler
–
Not
adjustable
d.07
Target temperature for
the domestic hot water
cylinder
Current value
℃
Applies to: Product with heat-
ing mode only, connected to do-
mestic hot water cylinder with
temperature sensor
–
Not
adjustable