Installing the flue gas pipe on the external wall
Installation manual for the flue pipe for ecoTEC plus 0020137851_02
23
8
225
Ø15
9
60-175
8.8 Adjustment range of the pipe brackets
The adjustment range of the pipe brackets spans from
55 mm to 95 mm. Adjust the two fastening screws within
this range.
If the pipe is installed at a greater distance from the wall,
extensions for the
external wall brackets are required. This enables you to use
a wall clearance of 175 mm.
175
55
8.9 Adjustment range of the support console
The support console can also be adjusted to a distance of
175 mm using an extension.
8.10 Flue gas components of the external wall system
>
Install:
– The air intake piece
– The flue gas pipes
– The cleaning eye, if necessary
– The diversions
– The terminal.
i
The air intake piece must not be fitted any fur-
ther away from the unit than is specified in
¬
section 5
.
i
Only the terminal is equipped with a clamp as
standard. For all other connections, the clamps
must be ordered as additional parts.
i
The terminal is made from black plastic on the
flue gas side. This means that the flue opening
is also resistant to UV radiation. Tighten all wall
fastenings.
i
The opening must be at a minimum distance of
100 cm from the roof area.
>
If applicable, install additional extensions and elbows
starting from the wall and working towards the unit.
>
Attach one fastening clamp for each extension.
>
Finally, insert the elbow of the flue gas pipe into the flue
gas connection of the unit.
>
Connect all connecting points of the air pipes using a
safety screw as described in
¬
section 10
.