Installation and maintenance manual ecoLEVEL 

 Note!

If a second hose is to be connected, remove the 
plug from the second feed opening (4) and con-
nect the additional hose as shown above.

•  Put the cover back onto the ecoLEVEL condensate 

pump from above.

5.2   Connecting and laying the discharge hose

•  Push the discharge hose onto the removed non-return 

valve as far as it will go.

•  Insert the non-return valve back into the cover, and 

lock it into place by rotating it a quarter turn to the 
right (clockwise).

Laying the discharge hose:
The pump‘s discharge hose should be connected to the 
building‘s waste water system.
•  Guide the discharge hose directly from the pump far 

enough upwards so that the height difference between 
the pump‘s outflow and the drainage point can be 
compensated for, and so that a slope in the hose can 
be created between the deflection point and the drain-
age point when the hose is laid. 

 Caution!

Observe the pump‘s maximum delivery height 
of 4 m!

•  Then lay the discharge hose with a constant slope 

down to the drainage point.

•  Position the discharge hose with a U-shape at the 

highest point to prevent backflow.

    max. 4 .

0

 m

ca 3˚

Fig. 5.2 Laying the discharge hose

5.3 

Connecting to the boiler

Using the feed hose supplied, the ecoLEVEL condensate 
pump can be connected to the siphon of any Vaillant 
condensing gas heating appliance.
•  If the condensate drainage hose on the boiler is long 

enough, it can be connected directly to the pump (see 
Sec. 5.1).

If the hose on the boiler is too short, you can replace it 
with the feed hose supplied.
•  Connect the feed hose to the boiler‘s condensate out-

let. 

•  Connect the feed hose to the ecoLEVEL condensate 

pump as shown in Fig. 5.1.

5 Installation

Summary of Contents for ecoLEVEL

Page 1: ...ecoLEVEL GB DE AT CH BE NL IT PL ...

Page 2: ......

Page 3: ... 2 2 Safety instructions and regulations 2 3 Instructions on operation 3 3 1 Vaillant warranty 3 3 2 Intended use 3 3 3 Care 3 3 4 Recycling and disposal 3 4 Operation and maintenance 3 4 1 General information 3 4 2 Display of operating status 3 4 3 Maintenance 3 For the owner Operating manual ecoLEVEL Condensate pump ...

Page 4: ...ymbol for a necessary task 2 Safety instructions and regulations In general modifications to the ecoLEVEL condensate pump are forbidden For modifications to the environ ment you must refer to a suitably qualified heating engineer who is responsible for it Caution Risk of damage due to improper modifications Under no circumstances should you ever attempt to make modifications to the pump or other p...

Page 5: ...rials Appliance Neither the pump or any of its accessories belong in the household waste Make sure the old appliance and any related accessories are disposed of properly Packaging Please leave the disposal of the transport packaging to the technician who installed the appliance 4 Operation and maintenance 4 1 General information The ecoLEVEL condensate pump is used for the extrac tion of condensat...

Page 6: ......

Page 7: ...nstallation site 4 4 3 Dimensions and clearances 4 4 4 Installing the wall bracket 4 5 Installation 5 5 1 Connecting the feed hose 5 5 2 Connecting and laying the discharge hose 6 5 3 Connecting to the boiler 6 6 Electrical connection 7 6 1 General information 7 6 2 Connecting the 230 V mains voltage 7 6 3 Connecting the overflow safety switch 7 7 Start up 10 7 1 Display of operating status 10 8 M...

Page 8: ...ating engineer Standards and regulations IEC 60364 7 712 Electrical installations of buildings Part 7 712 EMV test procedures in accordance with EN50081 1 1992 EN50082 1 1997 Emission interference EN 55014 1 1993 Interference resistance EN 55014 2 1997 Engineering rules The installation must correspond to the site conditions to local regulations and last but not least to the engi neering rules Acc...

Page 9: ...Caution Risk of damage due to improper modifications Under no circumstances should you ever attempt to make modifications to the pump or other parts of the system 3 Information on installation and operation 3 1 Vaillant warranty We only grant a Vaillant manufacturers warranty if a suitably qualified engineer has installed the system in accordance with Vaillant instructions The system owner will be...

Page 10: ...he provided mounting hardware If a suitable wall is not available a suitable mounting surface must be prepared The ecoLEVEL condensate pump should not be used as a storage shelf 4 3 Dimensions and clearances 100 mm 90 mm 165 mm 115 mm 150 mm 175 mm min 200 mm min 5 mm min 5 mm min 200 mm min 5 mm min 5 mm Fig 4 1 Dimensions and installation spaces 4 4 Installing the wall bracket Slide the pre asse...

Page 11: ...or kinks in the hose to ensure that condensate can flow unob structed into the pump Determine the required length of the hose When shortening the hose allow a min of 10 mm extra length for the insertion depth of the hose in the pump s cover Rotate the non return valve 1 one quarter turn to the left anticlockwise in order to open the cover 2 on the pump This unlocks both the cover and the return va...

Page 12: ...rainage point can be compensated for and so that a slope in the hose can be created between the deflection point and the drain age point when the hose is laid Caution Observe the pump s maximum delivery height of 4 m Then lay the discharge hose with a constant slope down to the drainage point Position the discharge hose with a U shape at the highest point to prevent backflow max 4 0 m ca 3 Fig 5 2...

Page 13: ...Connection cable fit a 3 pin plug if required 2 Connection cable for the overflow safety switch 6 2 Connecting the 230 V mains voltage There are two options for connecting the 230 V mains voltage You can connect the cable 1 to the 230 V mains via the mains connection on the boiler or You can install a mains plug on the cable 1 and con nect the pump with a mains socket the plug is not included in t...

Page 14: ...ectrical box Remove the cable bridge from the blue slot Anl Therm on the circuit board Plug the blue Pro E plug on the end of the ecoLEVEL condensate cable into this slot 9 8 7 5 4 3 N L N L Pumpe 2 Pumpe Anl Therm L N 24V I 230V RT 24V 230V RT 230V X 10 X 7 X 8 X 2 13 1 1 1 1 Codierwiderstand 1 2 Fig 6 2 Connecting the overflow safety switch connection type A 6 Electrical connection ...

Page 15: ... B Connection type C When installed as shown here the condensate pump will isolate the boiler in the event that the pump fails or in the event that the overflow safety switch in the pump is activated e g if it is blocked This will prevent the boiler from continuing to produce condensate and prevent the risk of flooding Connect the overflow safety switch to the boiler in the following manner Using ...

Page 16: ...d Note Maintenance on the pump can be scheduled to coincide with the maintenance intervals for the boiler The pump should be serviced at least once a year 9 Troubleshooting 9 1 Problems The ecoLEVEL condensate pump can rectify temporary faults during normal operation by itself The red LED sig nals the following operating conditions Green LED Red LED Meaning Flashes Lights up The maximum water leve...

Page 17: ...iance for wall mounted installation Nominal capacity l 0 5 Mains voltage V 230 Max current consumption A 1 Frequency Hz 50 Max power rating W 22 Max pump head m 4 Volume flow l h 150 Dimensions Height mm 160 Width mm 180 Depth mm 100 Weight when filled with water kg 1 8 Feed hose max outside diameter mm 24 Discharge hose min inside diameter mm 10 Water infeed temperature C 1 60 Ambient temperature...

Page 18: ......

Page 19: ......

Page 20: ...0020017507_00 GB DE AT CH BE NL IT PL 12 2005 ...

Reviews: