Vaillant climaVAIR VAM 2-085 W3N Installation Manual Download Page 16

Split Type Installation Manual

14

10.2  Planning the Refrigerant Return

The refrigerant circuit contains a special oil to lubricate 
the outdoor unit compressor. To assist the return of the 
oil to the compressor the following is recommended:
-  that the indoor unit is located higher than the outdoor 

unit and,

-  that the suction pipe (the thickest one) is assembled 

with a gentle slope towards the compressor.

If the outdoor unit is mounted higher than the indoor 
unit, the suction pipe must be mounted in a vertical 
position. At heights exceeding 7.5 m (where this is 
permissible):
•  Additional oil traps must be installed at each 7.5M 

interval

10.3  Connection of the Refrigerant Pipes

 

  Note!

Installation is easier if the gas suction pipe is 
connected up first. The suction pipe is the 
thickest one.

•  Mount the outdoor unit in the required position.
•  Remove the flare nuts and bonnets from the shut off 

in the outdoor unit.

•  Carefully bend the installed pipe towards the outdoor 

unit.

  Warning

!

Danger of breakdowns or malfunction. Danger of 
damage in the refrigerant pipes. 
Bend the pipe carefully to prevent kinks or 
breaks.

•  Cut the pipes, leaving enough extra piping hanging 

over to enable the unit to be connected at the outdoor 
unit joins.

•  Flare the refrigerant pipe after first placing the flare 

nut on the pipe.

•  Join the refrigerant pipes to the corresponding 

outdoor unit connection.

•  Insulate the refrigerant piping correctly and 

separately. To do so, cover any joins in the insulation 
with masking tape or insulate any bare coolant piping 
with the corresponding insulation material suitable for 
air conditioning.

10.4  Connection of the Condensate Drain Pipe to 

Outdoor Unit

 

  Note!

Applicable only to heat pump units.

Whilst the unit is running with the heat pump function, 
condensation forms in the outdoor unit and has to be 
drained.

•  Insert the elbow included in the supply in the hole 

provided at the bottom of the outdoor unit and turn it  
90º to fix it (see Figure 10.2).

Fig. 10.2 Assembly of the drainage elbow for condensed water

Legend

1  Outdoor Unit
2  Drainage elbow
3  Drainage hose

•  Mount the drainage hose ensuring that it leaves the 

equipment with a downward slope.

•  Verify the correct drainage of the water by pouring 

the water into a collection tray located at the bottom 
of the outdoor unit.

•  Protect the condensate water hose with thermal 

insulation to avoid freezing.

10 Installation of the outdoor unit 

Summary of Contents for climaVAIR VAM 2-085 W3N

Page 1: ...VAM 2 050 W2N VAM 2 060 W2N VAM 2 085 W3N VAM 2 110 W4N climaVAIR DE EN HR IT TR...

Page 2: ......

Page 3: ...For the fitter VAM 2 050 W2N VAM 2 060 W2N VAM 2 085 W3N VAM 2 110 W4N Installation Manual Air conditioner climaVAIR Split Type EN...

Page 4: ...n of the Pipe Work 10 9 3 1 Correct Removal of the Condensate Water 10 9 3 2 Handling the Refrigerant Pipes 10 9 3 3 Correct installation of the condensate pipe work 11 9 3 4 Making Holes for the Pipe...

Page 5: ...f maintenance operations involving the handling of the refrigerant fluid must have the necessary certification to comply with all local and international regulations 2 Extreme Operating Conditions Thi...

Page 6: ...or Unit 2 Outdoor Unit 3 Remote controller 4 Interconnecting pipework not supplied 5 Condensed water drainage pipe 5 1 Indoor Unit The indoor unit heats and cools air to be supplied to the room to be...

Page 7: ...onsult the model nameplate The dimensions are given in mm Fig 5 3 Dimensions of the outdoor unit Legend H Height L Length D Depth A Length of valves B Distance between valves C Distance from the secon...

Page 8: ...outdoor and indoor unit they allow the water to be properly discharged which condenses during the normal operation of the unit Electric connections these supply electric energy to the unit 5 5 Suppli...

Page 9: ...38 26 32 38 26 32 38 Sound Pressure level 2 dB A 26 32 38 28 35 40 26 32 38 26 32 38 Sound Pressure level 3 dB A 28 35 40 26 32 38 Sound Pressure level 4 dB A 28 35 40 Outdoor Unit Air Flow volume m3...

Page 10: ...s in force Do not dispose of packaging irresponsibly recycle where possible 8 Installation 8 1 Qualification of the Installation Personnel Ensure that this unit is installed by suitable qualified pers...

Page 11: ...clearances are met Choose a position site that will allow air to reach all parts of the room evenly Avoid beams obstructions or lights which would interfere with the airflow Install the indoor unit a...

Page 12: ...to refrigerant pipes through the use of unsuitable materials Use only pipes specifically intended for refrigeration and R410A refrigerant Note In specialised dealers you will find refrigerant pipes a...

Page 13: ...pipe with a rising bend see Figure 9 2 Fig 9 2 Avoid rising bends If the drain is run to a tank or butt avoid installing the condensed water pipe with it free end submerged in water see Figure 9 3 Fi...

Page 14: ...pipes Carefully bend the installation pipe in the right direction taking care not to overbend or kink the pipe Warning Danger of breakdowns or malfunction Danger of damage to the coolant pipes Bend th...

Page 15: ...sure that the pipework is not trapped behind the unit 10 Installation of the Outdoor Unit 10 1 Selecting the Assembly Location Warning Outdoor units must be placed in accessible areas for subsequent m...

Page 16: ...breaks Cut the pipes leaving enough extra piping hanging over to enable the unit to be connected at the outdoor unit joins Flare the refrigerant pipe after first placing the flare nut on the pipe Joi...

Page 17: ...ocal electrical sockets only use with a suitable adaptor or replace the plug with a UK style one Danger Danger of electric shock Use wiring in accordance with the respective local national and interna...

Page 18: ...Danger of breakdowns or malfunction If the fuse on the PC board is blown please change it with type T 3 15A 250V Open the front panel of the indoor unit by pulling it upwards Remove the wiring cover o...

Page 19: ...Warning Danger of malfunction and breakdowns resulting from water penetration Always terminate the interconnecting cable from below the cable entry to avoid water penetration into the terminal box War...

Page 20: ...up to 25 meter in mm2 2 5 2 5 4 6 Indoor Outdoor Outdoor Outdoor Outdoor Outdoor Thermal magnetic circuit breaker type D A 16 16 20 25 Interconnection section up to 25 meter mm2 These units already in...

Page 21: ...efrigerant circuit must be periodically checked for leakage Take the necessary actions to ensure these tests are performed and the results correctly logged into the maintenance record of the machine T...

Page 22: ...checking for leaks Warning Danger of malfunction and leaks Ensure that the service valves on the outdoor unit are closed 12 3 Start Up Fig 12 5 Filling the installation Legend 1 Two way valve 2 Actuat...

Page 23: ...igerant from the system You will need the correct refrigerant recovery unit and refrigerant reclaim cylinder to achieve this Warning Never release refrigerant into the environment Refrigerant R410A is...

Page 24: ...ion for Multi OUTDOOR UNIT DISPLAY LED STATUS E0 EEPROM error E1 N 1 Indoor units pipe temp sensor or connector of pipe temp sensor is defective E2 N 2 Indoor units pipe temp sensor or connector of pi...

Reviews: