System without system control (0020253231) 3
0020243831_00 System assistant
9
Work step
Selected information/measures
10
Outdoor unit
►
Evacuating the refrigerant circuit
►
Drain the nitrogen that was poured in.
►
Connect a vacuum pump.
►
Drain the refrigerant circuit in two rounds of 30 minutes each.
►
After each round, check whether the pressure is stable:
–
0.1 kPa (1.0 mbar) absolute pressure
11
Outdoor unit
►
Adding additional refrigerant
Condition:
Basic length of the refrigerant pipe > 15 m
►
For each additional metre (above 15 m), add additional refrigerant:
–
30 g/m for an output of up to 5 kW
–
70 g/m for an output of 7 kW or higher
12
Outdoor unit
►
Releasing the refrigerant
►
Turn the isolation valves as far as they will go.
3.4
Installing the heating and domestic hot water circuit
→
uniTOWER installation and maintenance instructions, from section 5.1 onwards
→
Accessory set-up instructions
Work step
Selected information/measures
13
Indoor unit
►
Installing the domestic hot and cold water
connection
►
Installing heating circuit connections
►
Observe the connection symbols.
→
uniTOWER installation and maintenance instructions, section 3.7
14
Heating circuit
►
Connecting the buffer cylinder
►
Connecting the bypass valve
15
Heating circuit
►
Connecting the additional expansion vessel
Condition:
The dimension of the installed expansion vessel is not sufficient
16
DHW circuit
►
Connecting the expansion vessel
►
Ensure that there is sufficient dimensioning.
►
If required, adjust the pre-charge pressure.
17
Safety devices
►
Installing the safety devices
►
Ensure that all of the required safety device have been installed in the sys-
tem.
3.5
Installing the electrical connections
→
aroTHERM installation and maintenance instructions, from section 6.1 onwards
→
uniTOWER installation and maintenance instructions, from section 6.1 onwards
→
multiMATIC installation instructions, from section 4.1 onwards
→
Accessory set-up instructions
Work step
Selected information/measures
18
Outdoor temperature sensor
►
Connecting the outdoor temperature sensor
19
Outdoor unit
►
Establishing the power supply
►
Select a correct cable cross-section.
►
Comply with the connection conditions for the energy supply company.
►
Determine whether an electrical connection 1~/230 V or 3~/400 V (
→
data
plate) is required.
►
Determine whether the power supply should be set up using a single-tariff
meter or a dual-tariff meter.
Condition:
Depending on the installation site
►
Install one or two type-B residual-current circuit breakers for the outdoor unit,
depending on the connection type.
20
Indoor unit
►
Establishing the power supply
►
Route the cables from the rear into the product and, from there, to the front
through the strain relief.
Condition:
Depending on the installation site
►
Install a type-A or type-B residual-current circuit breaker for the indoor unit.
21
Indoor unit, electrical house installation
►
Installing components for the energy supply
company lockout function
Condition:
Power supply via a dual-tariff meter
Option 1: Disconnect the power supply with contactor
Option 2: Actuating the ESC contact
→
uniTOWER installation and maintenance instructions, section 6.4