INSTALLATION, OPERATION and 

MAINTENANCE  

2

”x1”, 2” & 3”x 2” Figure 939SS Air & Vacuum Valves 

 
 

INTRODUCTION 

This  manual  will  provide  the  information  to 
properly  install,  operate  and  maintain  the  valve 
to  ensure  a  long  service  life.      The  Air  Release 
Valve is ruggedly constructed to provide years of 
trouble-free 

operation 

with 

minimal 

maintenance.  
 

CAUTION 

The  valve  is  NOT  recommended  for  use  with 
toxic  fluids,  fuels  or  fluids  containing  hazardous 
gases 
 

CAUTION 

The  valve  will not  function  if  used  at  a  pressure 
higher  than  the  maximum  working  pressure 
indicated on the nameplate. 
 
The  Shop  Order  (SO)  Number,  Figure  Number, 
size  and  pressure  rating  are  stamped  on  a 
nameplate attached to the valve.  Please refer to 
the SO number when ordering parts.  
 

DESCRIPTION OF OPERATION

 

The Figure 939SS Durovent

™ Short Body Air & 

Vacuum Valve vents air and sewage gas as the 
system  is  being  filled  with  fluid.    When  the 
system is full, fluid rises in the valve and lifts the 
float  to  close  the  valve.    The  valve  remains 
closed  until  the  system  is  drained  or  a  negative 
pressure occurs within the valve/system.  At that 
time  the  Figure  935SS  automatically  opens  to 
admit air to alleviate the vacuum.  Figure 939SS 
Durovent

™  Air  &  Vacuum  valves  are  usually 

installed  at  high  points  in  the  system  where  air 
rises  as  during  filling  and  vacuum  first  forms 
during  draining.    Its  short  body  facilitates 
installation when there is 

“shallow cover.” 

 
RECEIVING AND STORAGE 

Inspect  the  valve  upon  receipt  for  damage 
during  shipment.    Carefully  unload  all  valves  to 
the ground without dropping.   
 
The  valves  should  remain  in  a  clean,  dry  and 
weather  protected  area  until  installed.    For  long 
term storage (greater than 6 months) the rubber  

 
 
 
surfaces  of  the  seat  should  be  coated  with  a 
non-toxic  lubricant  such  as  "SuperLube"  made 
by  Synco  Chemical.    Do  not  expose  the  rubber 
parts to sunlight or ozone. 
 

INSTALLATION 

The Figure 939SS is standard with 

2” or 3” NPT 

screwed pipeline connections. A flanged pipeline 
connection is provided on special order.  
 
Consult  the  drawings  of  record  to  verify  the 
configuration supplied and installed. 
 
The valve must be installed in an upright vertical 
orientation,  normally  at  a  high  point  in  the 
system.   
 
If  installed  outdoors,  below  ground  in  a  vault  or 
in an unheated area, adequate freeze protection 
must be provided.   
 
An  isolating  valve  should  be  installed  between 
the valve and the pipeline or system to facilitate 
maintenance 

(included 

with 

backflushing 

attachments).    
 
Carefully  screw  threaded  end  valves  onto  pipe 
nipple using compatible thread sealant.  Tighten 
valve  using  wrench  flats.    DO  NOT  OVER-
TIGHTEN. 
 
Flat-faced  flanged  valves  should  be  mated  with 
flat-faced  flanges  and  full-face  gaskets.    If  ring 
gaskets  are  used  the  bolt  material  shall  be 
ASTM  A307  Grade  B  (or  equivalent).    Higher 
strength  bolting  should  only  be  used  with  full-
face gaskets.  
  
Lower  heavy  valves  over  the  mating  flange 
using  slings  or  chains  around  the  valve  body.  
Lubricate  the  bolts  or  studs  and  insert  around 
flange.    Lightly  tighten  bolts  until  gaps  are 
eliminated.    Torque  bolts  in  an  alternating 
pattern  in  graduated  steps.    If  leakage  occurs 
wait 24 hours and re-torque the bolts but do not 
compress  the  gasket  more  than  50%  or  exceed 
bolt maximum torque rating. 