7.6.3
Example 3 - Exception response
In an exception response, the Slave sets the most-significant bit (MSB) of the function code to 1. The
Slave returns an exception code in the data field.
Command Master - Slave:
Message frame:
Exception response
Answer Slave - Master:
Reply frame:
ADDRESS
01 hex
Slave address 1 hex (= 1)
FUNCTION
04 hex
Function 4 hex (= 4)
Starting address HI
17 hex
Starting address 1770 hex (= 6000)
DATA
Starting address LO
70 hex
No. of registers HI
00 hex
Invalid number of registers 0005 hex (=
5)
No. of registers LO
05 hex
ERROR CHECK
CRC HI
34 hex
CRC LO
66 hex
CRC 3466 hex (= 13414)
01
04
17
70
00
05
34
55
ADDRESS
01 hex
Slave address 1 hex (= 1)
FUNCTION
84 hex
Most significant bit set to 1
DATA
Error code
04 hex
Error code 04 => Slave device failure
ERROR CHECK
CRC HI
42 hex
CRC LO
C3 hex
CRC 42C3 hex (= 17091)
01
84
04
42
C3