vacon • 90
Modbus TCP / Modbus UDP
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
7.6
Modbus - example messages
7.6.1
Example 1 - Write process data
Write the process data 42001…42003 with command 16 (Preset Multiple Registers).
Command Master - Slave:
Message frame:
The reply to Preset Multiple Registers message is the echo of 6 first bytes.
Answer Slave - Master:
Reply frame:
ADDRESS
01 hex
Slave address 1 hex (= 1)
FUNCTION
10 hex
Function 10 hex (= 16)
Starting address HI
07 hex
Starting address 07D0 hex (= 2000)
DATA
Starting address LO
D0 hex
No. of registers HI
00 hex
Number of registers 0003 hex (= 3)
No. of registers LO
03 hex
Byte count
06 hex
Byte count 06 hex (= 6)
Data HI
00 hex
Data 1 = 0001 hex (= 1). Setting control
word run bit to 1.
Data LO
01 hex
Data HI
00 hex
Data 2 = 0000 hex (= 0).
Data LO
00 hex
Data HI
13 hex
Data LO
88 hex
Data 3 = 1388 hex (= 5000), Speed Refer-
ence to 50.00%
ERROR CHECK
CRC HI
C8 hex
CRC LO
CB hex
CRC field C8CB hex (= 51403)
01
10
07
D0
00
03
06
00
01
00
00
13
88
C8
CB
ADDRESS
01 hex
Slave address 1 hex (= 1)
FUNCTION
10 hex
Function 10 hex (= 16)
Starting address HI
07 hex
Starting address 07D0 hex (= 2000)
DATA
Starting address LO
D0 hex
No. of registers HI
00 hex
Number of registers 0003 hex (= 3)
No. of registers LO
03 hex
ERROR CHECK
CRC HI
80 hex
CRC LO
85 hex
CRC 8085 hex (= 32901)
01
10
07
D0
00
03
80
85