Parameter lists
vacon • 11
24-hour s358 (0)40 837 1150 • Email: [email protected]
3.4
Output signals (Control keypad: Menu M2 G2.3)
3.4.1
Analogue output 1
Code
Parameter
Min
Max
Unit
Default
Cust
ID
Note
P2.3.1.1
0
13
13
307
0=Not used
1=Output freq. (0—f
max
)
2=Freq. reference (0—f
max
)
3=Motor speed (0—Motor
nominal speed)
4=Motor current (0—I
nMotor
)
5=Motor torque (0—T
nMotor
)
6=Motor power (0—P
nMotor
)
7=Motor voltage (0-U
nMotor
)
8=DC-link volt (0—1000V)
9=PI controller temp ref
10=PI contr. act. temp.
11=PI contr. temperature
error value
12=PI controller output
13=Pressure from PT11,
pump inlet
P2.3.1.2
0,00 10,00 s 1,00
308 0=No filtering
P2.3.1.3
0
1
0
309 0=Not inverted
1=Inverted
P2.3.1.4
0
1
1
310 0=0 mA
1=4 mA
P2.3.1.5
10 1000 % 100
311
Table 12. Analogue output 1 signals
3.4.2
Analogue output 2
Code
Parameter
Min
Max
Unit
Default
Cust
ID
Note
P2.3.2.1
0 13
10
1530
0=Not used
1=Output freq. (0—f
max
)
2=Freq. reference (0—f
max
)
3=Motor speed (0—Motor
nominal speed)
4=Motor current (0—I
nMotor
)
5=Motor torque (0—T
nMotor
)
6=Motor power (0—P
nMotor
)
7=Motor voltage (0-U
nMotor
)
8=DC-link volt (0—1000V)
9=PID controller ref. value
10=PI contr. act. temp
11=PI contr. temperature
error value
12=PI controller output
13=Pressure from PT11,
pump inlet
P2.3.2.2
0,00 10,00 s 1,00
1531 0=No filtering
P2.3.2.3
0
1
0
1532 0=Not inverted
1=Inverted
P2.3.2.4
0
1
0
1533 0=0 mA
1=4 mA
P2.3.2.5
10 1000 % 100
1534
Table 13. Analogue output 2 signals