36
• vacon
Profinet IO
Tel. +358 (0)201 2121 • Fax +358 (0)201 212 205
2
It is possible to read and write parameters from and to the drive. In order to process them through
the Base Mode Parameter Access mechanism, you should:
o
set requested PNU to 10001 (0x2711)
o
set requested subindex with the drive parameter ID
NOTE:
Parameters which are read from the drive have always the format set to “Word” – 0x42.
Error
Value
Meaning
0x00
Impermissible PNU
0x01
Cannot change value
0x02
Low or high limit exceeded
0x03
Faulty subindex
0x04
No array
0x05
Incorrect data type
0x06
Setting not permitted
0x07
Cannot change description
0x09
No description
0x0B
No operation priority
0x0F
No text array available
0x11
Cannot execute the request. Rea-
son not specified
0x14
Value impermissible
0x15
Response too long
0x16
Parameter address impermissi-
ble
0x17
Illegal format
0x18
Number of values inconsistent
0x19
Axis/DO nonexistent
0x20
Cannot change text
0x65
Invalid Request Reference
0x66
Invalid Request ID
0x67
Invalid Axis number / DO-ID
0x68
Invalid number of parameters
0x69
Invalid attribute
0x6B
Request too short
Table 6 PROFIDRIVE parameter request error codes