Active Front End (AFE)
vacon • 35
24-hour s358 (0)201 212 575 • Email: [email protected]
4
4.11
Active Front End unit – Fuse selection
4.11.1
Introduction
AC fuses are used to protect the input network in case the Active Front End unit or the LCL filter is
faulty. DC fuses are used to protect the Active Front End unit and the LCL filter in case there is a
short circuit in the DC buses. If DC fuses are not used, short-circuit in the DC buses will cause a
loading of the Active Front End unit. Vacon Plc will not assume any responsibility for damages
caused by insufficient protection.
4.11.2
Fuses; mains voltage 380–500 V
4.11.2.1
AC fuses
NOTE!
Fuses for FI9 and FI10 are blade type and for FI13 flush-end type. If some other type is needed, please
contact Vacon.
NOTE!
All fuses are blade type. If some other type is needed, please contact Vacon.
Table 10. Ferraz Shawmut AC fuse selection, mains voltage 380–500 Vac
Module
AC fuses
Type
Code
Frame
Ferraz Shawmut
type [aR]*
U
N
[V]
I
N
[A]
Size
Q'ty
AFE
NXA_0261 5
FI9
NH2UD69V500PV
690
500
2
3
NXA_0460 5
FI10
NH3UD69V800PV
690
800
3
3
NXA_1300 5
FI13
PC44UD75V22CTQ
750
2200
44
3
Table 11. Bussman AC fuse selection, mains voltage 380–500 Vac
Module
AC fuses
Type
Code
Frame
Bussman
type [aR]*
U
N
[V]
I
N
[A]
Size
Q'ty
AFE
NXA_0261 5
FI9
170M6202
1250
500
3SHT
3
NXA_0460 5
FI10
170M6277
1250
1000
3SHT
3
NXA_1300 5
FI13
170M6277
1250
1000
3SHT