VACON CX
Modbus user’s manual
Page
18
________________________________________________________________________________________
________________________________________________________________________________________
Vacon Oy
Phone +358-201-2121
Fax: +358-201-212 205
n8
Temperature
1
°C
Temperature of the heat sink
n9
Operating day counter
DD.dd Operating days 1), not resettable
n10
Operating hours, "trip
counter”
HH.hh Operating hours 2), can be reset with program-button
#3
n11
MW-hours
0,001
MWh
Total MW hours, not resettable
n12
MW-hours, "trip counter"
0,001
MWh
MW-hours, can be reset with programmable button #4
n13
Voltage/analogue input
0,01
V
Voltage of the terminal Uin+ (control board)
n14
Current/analogue input
0,01
mA
Current of terminals Iin+ and Iin- (control board)
n15
Digital input status, gr. A
0 = Open Input, 1 = Closed Input (Active)
n16
Digital input status, gr. B
0 = Open Input, 1 = Closed Input (Active)
n17
Digital and relay output
status
0 = Open Input, 1 = Closed Input (Active)
n18
Control program
Version number of the control software
n19
Unit nominal power
0,1
kW
Shows the power size of the unit
n20
Motor temperature rise
1
%
100%= temperature of motor has risen to nominal
value
1)
DD = full days, dd = decimal part of a day
2)
HH = full hours, hh = decimal part of an hour
Table 7-1 Monitored Items
Example 1:
Read value of Vacon variable 3.
Response: Value of monitored item ( 156 = 15,6 A).
Query:
01
04
00
02
00
01
CRC16
Slave addr
Function
Address HI
Address LO
Number of
points HI
Number of
points LO
2 bytes
Response:
01
04
02
00
9C
CRC16
Slave addr
Function
Byte count
Data HI
Data LO
2 bytes
7.3.3
Active Fault Code
When a fault status is active, fault code can be read by using the function code 3. Modbus address
according to the fault code as follows.
Modbus address
Vacon variable
30100
Active fault code
List and description of the fault codes are in
USER’S MANUAL VACON CX/CXL/CXS
Example 1:
Read active fault code.
Response: fault code 1 = Overcurrent
Query:
01
04
00
64
00
01
CRC16
Slave addr
Function
Address HI
Address LO
Number of
points HI
Number of
points LO
2 bytes
Response:
01
04
02
00
01
CRC16
Slave addr
Function
Byte count
Data HI
Data LO
2 bytes