CANopen protocol description
vacon • 11
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
3
Protocol reset communication
The reset communication message makes the node(s) apply communication reset. See Figure 1.
NMT state machine. Communication reset does not affect the object dictionary values. If the node
ID in the message is set to ‘0’, the message affects all nodes (broadcast). After the node has made
the communication reset, it will enter the pre-operational state automatically from the initialising
state. This also creates a boot-up event and the boot-up message is sent after the reset.
3.3
Error control protocols
It is not allowed to use guarding protocol and heartbeat protocol on one NMT slave at the same
time. If the heartbeat producer time is unequal 0, the heartbeat protocol is used.
3.3.1
Heartbeat protocol
Heartbeat protocol defines the producer and consumer. The producer node sends its NMT status
that is then available for any consumer node. The consumer node is the receiver of heartbeat
messages. The producer node has a timing parameter that indicates how often the heartbeat
message should be sent. The consumer node has a relative parameter that indicates how often the
heartbeat message should be received. If the consumer does not receive the heartbeat message
within the time defined in the heartbeat object entry, an error event occurs.
Table 6: Reset communication message
CAN ID
LENGTH
DATA0
DATA1
DATA2
DATA3
DATA4
DATA5
DATA6
DATA7
0x0
0x2
0x82
NODE
ID
Table 7: Node status description
Value
Description
0x0
Boot-up
0x4
Stopped
0x5
Operational
0x7F
Pre-operational
Table 8: Heartbeat message
CAN ID
LENGTH
DATA0
DATA1
DATA2
DATA3
DATA4
DATA5
DATA6
DATA7
0x700 +
Node ID
0x1
Status
Table 9: Heartbeat-related objects in OD
Index
Description
0x1016
Consumer heartbeat time
0x1017
Producer heartbeat time
0x1029
Error behaviour