P2.8.4.4
Voltage at field weakening point
ID603
“Voltage at FWP”
Above the frequency at the field weakening point, the output voltage remains at the set
maximum value. Below the frequency at the field weakening point, the output voltage
depends on the setting of the U/f curve parameters.
When the parameter
Motor nominal frequency
is set, the parameter
Field weakening
point
is automatically given the corresponding value. If you need different values for the
field weakening point and the maximum output voltage, change these parameters
after
setting the
Nominal frequency
.
In closed loop control this defines maximum voltage to the motor, can be increases if
sufficient DC voltage is available.
P2.8.4.5
U/f curve, middle point frequency
ID604
“U/f Mid Freq”
If the programmable U/f curve has been selected with parameter U/f ratio this parameter
defines the middle point frequency of the curve. See also parameter
Middle point
voltage
.
When the programmable U/f curve is selected this value is set to 10% of motor nominal
frequency.
P2.8.4.6
U/f curve, middle point voltage
ID605
“U/f mid Voltg”
If the programmable U/f curve has been selected with the parameter U/f ratio this
parameter defines the middle point voltage of the curve. See also parameter
Middle point
frequency
.
When the programmable U/f curve is selected this value is set to 10% (of motor nominal
voltage).
P2.8.4.7
Output voltage at zero frequency
ID606
“Zero Freq Voltg”
This parameter defines the zero frequency voltage of the U/f curve. The default value is
unit size dependent.
NOTE
: If the value of parameter
U/f Ratio Select
is changed this parameter is set to zero.