71
vacon
vacon 50x parameters
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
7
The V/Hz Characteristic Selection parameter determines the characteristic of the V/Hz
curve and whether any boost will be applied at starting. (The amount of boost may be au-
tomatically determined or set with parameter 502 (Voltage Boost).) The following data
values may be assigned:
The following data values may be assigned to this parameter:
Parameter Value
Description
Linear Auto
The Linear Auto selection operates the Vector algorithm and
activates current limiting functionality.
Linear Fxd
V/Hz curve with the amount of boost fixed at the value set in
parameter 502 (Voltage Boost).
Pump Fxd
V/Hz curve with the amount of boost fixed at the value set in
parameter 502 (Voltage Boost).
Fan Fxd
V/Hz curve with the amount of boost fixed at the value set in
parameter 502 (Voltage Boost).
Linear 2pc
Activates parameters 512 (Midpoint Frq) and 513 (Midpoint
Volt). These parameters are used to define a midpoint through
which the V/Hz curve passes so a custom curve may be creat-
ed for special motor applications.
Vector
Activates the sensorless vector algorithm for high torque /
low speed operation. A vector-duty motor should be used for
this mode of operation. Vector mode does not use of the pa-
rameter (parameter 502).
501 V/Hz Select
Default: Linear Fxd
Range: n/a
Level 2
501 =
Linear Auto
501 =
Linear Fxd
501 =
Pump Fxd
501 =
Fan Fxd
501 =
Linear 2pc
501 =
Vector
Limiting
Feature
4-Quad
Current Lim-
it
4-Quad
Current Lim-
it
4-Quad
Current Lim-
it
4-Quad
Current Lim-
it
4-Quad
Current Lim-
it
4-Quad
Trq Limit
Parameter Value Changes
Slip Comp Enable 0 = No
0 = No
0 = No
0 = No
0 = No
1 = Yes
Start Field En
0 = No
0 = No
0 = No
0 = No
0 = No
1 = Yes
Find Mtr Data
0 = No
0 = No
0 = No
0 = No
0 = No
1 = Motor RS
Parameter Lock Status Changes
Slip Comp Enable Unlocked
Locked
Locked
Locked
Locked
Unlocked
Start Field En
Unlocked
Locked
Locked
Locked
Locked
Unlocked
Filter Fstator
Unlocked
Locked
Locked
Locked
Locked
Unlocked
Filter Time Slip
Unlocked
Locked
Locked
Locked
Locked
Unlocked
Power Fail Config Unlocked
Locked
Locked
Locked
Locked
Unlocked
Voltage Boost
Locked
Unlocked
Unlocked
Unlocked
Unlocked
Locked
Parameter Visibility Changes
Slip Comp Enable Level 2
Invisible
Invisible
Invisible
Invisible
Level 1/Level 2
Start Field En
Level 2
Invisible
Invisible
Invisible
Invisible
Level 1/Level 2
Filter Fstator
Level 2
Invisible
Invisible
Invisible
Invisible
Level 2
Filter Time Slip
Level 2
Invisible
Invisible
Invisible
Invisible
Level 2
Power Fail Config Level 2
Invisible
Invisible
Invisible
Invisible
Level 2
ID Percent
Level 2
Invisible
Invisible
Invisible
Invisible
Level 2
IQ Percent
Level 2
Invisible
Invisible
Invisible
Invisible
Level 2
Voltage Boost
Invisible
Level 2
Level 2
Level 2
Level 2
Invisible
Summary of Contents for 50X
Page 1: ......
Page 5: ...introduction vacon 4 24 hour support 358 0 40 837 1150 Email vacon vacon com 1 ...
Page 23: ...receiving and installation vacon 22 24 hour support 358 0 40 837 1150 Email vacon vacon com 3 ...
Page 39: ...connections vacon 38 24 hour support 358 0 40 837 1150 Email vacon vacon com 4 ...
Page 101: ...vacon 50x parameters vacon 100 24 hour support 358 0 40 837 1150 Email vacon vacon com 7 ...
Page 132: ......