Parameters
vacon • 94
Service support: find your nearest Vacon service center at www.vacon.com
6
6.1.11
Group 3.10: Automatic reset
6.1.12
Group 3.11: Appl. Settings
Table 81. Autoreset settings
Code
Parameter
Min
Max
Unit
Default
ID
Description
P3.10.1
Automatic reset
0
1
0
731
0 = Disabled
1 = Enabled
P3.10.2
Wait time
0.10
10.0
m
1.0
717
Wait time before the first
reset is executed.
P3.10.3
Automatic reset tries
1
10
5
759
NOTE: Total number of trials
(irrespective of fault type)
P3.10.4
Restart Function
0
1
1
719
We can choose what kind of
start function we want to use
when doing an autorest of the
drive.
0 = Flying start
1 = Start Function
P3.10.5
Underload reset Time
1
0.1
1200.0
m
2.0
1927
P3.10.6
Underload reset Time
2
0.1
1200.0
m
30.0
1928
P3.10.7
Underload reset Time
3
0.1
1200.0
m
300.0
1929
P3.10.8
Underload Tries T1,T2
1
10
2
1930
Table 82. Application Settings
Code
Parameter
Min
Max
Unit
Default
ID
Description
P3.11.1
Parameter Password
0
9999
0
1806
P3.11.2
C/F selection
0
1
0
1197
0 = Celsius
1 = Fahrenheit
P3.11.3
kW/hp selection
0
1
0
1198
0 = kW
1 = hp
P3.11.4
Multimonitor View
0
2
1
1196
Division of keypad display
into sections in Multimon-
itor view.
0 = 2x2 sections
1 = 3x2 sections
2 = 3x3 sections
P3.11.5
FunctButtonConfig
0
15
15
1195
With this parameter it’s
possible to configure what
alternatives are visible
when pressing the function
button.
Summary of Contents for 100X series
Page 1: ...vacon 100 x ac drives Solar pump application manual ...
Page 2: ......
Page 6: ...vacon 3 Vacon 100X Solar Pump Application 1 ...
Page 8: ...2 vacon 5 Safety ...
Page 160: ...vacon 157 Parameters 6 ...
Page 169: ...Fault vacon 166 Service support find your nearest Vacon service center at www vacon com 7 ...
Page 170: ...7 vacon 167 Fault ...
Page 171: ......